Skip to main content

ORIGINAL RESEARCH article

Front. Energy Res., 23 September 2022
Sec. Smart Grids
Volume 10 - 2022 | https://doi.org/10.3389/fenrg.2022.1005593

Droop-based active voltage regulation control and robust stability analysis for VSCs in the large-scale RES-integrated power system

www.frontiersin.orgZhengkui Zhao1 www.frontiersin.orgXiaoling Su1* www.frontiersin.orgJun Yang2 www.frontiersin.orgPeng Zhou2 www.frontiersin.orgHui Chen2 www.frontiersin.orgGuoqiang Lu2
  • 1Qinghai Key Lab of Efficient Utilization of Clean Energy, Qinghai University, Xining, China
  • 2State Grid Qinghai Electric Power Company, Xining, China

New features like high penetration level, low inertia, and weak damping are decreasing voltage support capacity in the power system as it sees large-scale renewable energy source (RES) integration continuously. The reasonable solution to this challenge is developing an additional active voltage regulation function for voltage source converters (VSCs). This study proposes a droop-based active voltage control strategy for VSCs in large-scale RES-integrated power systems to make VSCs continue to operate and regulate the voltage at the point of common coupling (PCC) during a fault without causing overcurrent. In order to meet the requirements of RESs and grid code, all control boundary conditions are designed based on practical engineering data. Meanwhile, plant uncertainty and parameter disturbance are introduced into a robust stability margin analysis model based on the component connection method (CCM) and structured singular value (SSV) to improve the engineering application prospect. The effectiveness and feasibility of this control strategy are proved by logical deduction and practical simulation based on a generalized small-signal model.

1 Introduction

Driven by the energy crisis and environmental pollution, the world energy structure is undergoing dramatical changes. Promoting low-carbon energy or RESs is a global consensus (Yuan et al., 2017; Wang and Blaabjerg, 2019); therefore, large-scale RESs integration is an inevitable status for a power system. Most of the RESs connected power grid by VSCs, and the time scales of their electrical characteristics are different from convention synchronous motor-dominated power systems. Therefore, PV stations and wind farms install a static VAR compensator (SVC), static VAR generator (SVG), or static synchronous compensator (STATCOM) to regulate voltage at PCC and the reactive power compensation equipment capacity value in each station no less than 10% of the station capacity according to the grid code. As power systems see large-scale RES integration continuously, features like low inertia and weak damping make reactive power compensation equipment in the power system no longer sufficient for voltage regulation (Sun et al., 2015; You et al., 2017; Wang et al., 2020; Zhuo et al., 2021). On the other hand, the efficiency of original relay protection, stable measures, and monitoring devices decreases with the dramatic increase of power electronic equipment in the large-scale RES-integrated power system, especially during a fault. Su et al. (2021) gives an on-site engineering test for PV stations and wind farms in an AC–DC hybrid power grid under extreme fault conditions, with over three quarters of SVC and SVG blocked or disconnected from the grid. Meanwhile, RESs have the capability of disturbance-rejection under extreme fault conditions after parameter modification or equipment upgrading. So, it is reasonable for RESs to regulate voltage at PCC (GE et al., 2007; Lu et al., 2018; Lu, 2020).

The VSC control strategy can be divided into grid following and grid forming. VSCs in PV stations and wind farms adopt active and reactive power decoupling control (Su et al., 2020), which usually operates with a constant unit power factor. SVC, SVG, or STATCOM is reactive power sources for each RES (Ma et al., 2018). RESs could control their active and reactive power flexibility only if all the equipment operates with the same static/dynamic characteristics and communicate with each other without time delay. There are a large number of VSCs scattered geographically in PV stations and wind farms (Mahdian Dehkordi et al., 2017a; Mahdian Dehkordi et al., 2017b; Han et al., 2018; Wei et al., 2021; Xiao et al., 2021) with different dynamic response characteristics. It is difficult to achieve precise reactive power distribution in small time scale using a centralized control strategy in existing automatic voltage control (AVC). The autonomous response without global coordination cannot meet coordinated voltage support at PCC. On the other hand, active voltage regulation requires autonomous response and adaptability in static and transient stability. In addition, overcurrent, reactive power shortage, and time delay are the main obstacles for voltage regulation control in VSCs.

VSCs with grid-forming control operate with self-built voltage/frequency and respond to the disturbance autonomously which is independent of communication (Li et al., 2016). A virtual synchronous generator (VSG) and robust droop control are promising grid-forming control strategies, since VSCs operate as an equivalent voltage source and synchronized through power synchronization (Zhang et al., 2010; Zhong and Weiss, 2011; Zhong et al., 2014; Natarajan and Weiss, 2017; Rodriguez et al., 2018; Wei et al., 2022). Due to a synchronization mechanism and power-sharing design, the VSC switching process has a great impact on the other units. VSC parallel operation control analysis introduces plant uncertainty in modeling, parameter design, and stability analysis to characterize on-site practical engineering features. Sumsurooah et al. (2013) propose instruments to model and analyze the VSC system with uncertainty to represent perturbation effects such as system parameter variations. Sumsurooah et al. (2018) give insights into robust stability measure µ for equilibrium point stability with multiple parametric uncertainties and make the µ approach application-friendly. Le et al. (2020) develop a state–space model for VSCs to operate as VSG under time-delay and parameter uncertainty using the Lyapunov stability theorem and linear matrix inequality to obtain conservative time-delay uncertainty stability conditions and calculate its time-delay stability margin.

VSC output impedance is another engineering application for VSC dynamic stability analysis because of its intuitive physical meaning. First, the impedance matrix in different coordinate systems is developed based on a small-signal model, and then the output impedance and return matrix of grid impedance can be determined according to the Nyquist stability criterion. It allows to locally assessing converter stability by applying the Nyquist stability criterion to the ratio between the equivalent output admittance of the converter and the equivalent grid admittance at the converter terminals. However, it cannot reflect the overall operation status of the whole system. Le et al. (2020) and Xiao et al. (2021) establish a state–space equation and determine its stability based on the state matrix eigenvalue. Both methods are only applicable to a specific operating point. For engineering application, on-site operation of inverters interfaced to the grid exhibit the need for applying the multivariable control theory.

In order to coordinate the operation of VSCs and exploitation of their reactive power potential, this study presents a distributed control strategy instead of AVC (automatic voltage control)-based centralized control. The proposed droop-based active voltage regulation control enables VSCs continue to operate and regulate voltage at the point of common coupling (PCC) during a fault without causing overcurrent. The active voltage regulation control is achieved by detecting the PCC voltage and regulating the dynamic voltage actively with its output reactive power. Control strategy errors are inevitable in engineering applications which deteriorate system performance. The proposed control strategy is designed based on practical engineering data, and plant uncertainty and parameter disturbance are introduced into a robust stability margin analysis model based on a component connection method and structured singular value so that it improves the engineering application prospect. The main structure of this study is organized as follows:

The main circuit and control circuit topologies of grid-connected VSCs are shown in Section 2. Then, an active voltage control strategy for VSCs is proposed and discussed, so that converters operating in parallel can automatically share the output reactive power and ensure that the converter output does not exceed the limit as shown in Section 3. In Section 4, the system-level small-signal model of multi-VSCs is presented regarding to the plant uncertainty and parameter deviation for engineering application and design. Taking into account the perturbation effects such as system parameter variations that can occur in their physical plants, the control parameters’ influence on system stability is analyzed, and the stability margin is presented. The simulation model and case study are carried out in Section 5.

2 Grid-interfaced voltage source converter modeling

2.1 Voltage source converter topology

The main circuit structure and control strategy of the grid-connected VSCs are shown in Supplementary Figure S1.

For the main circuit of VSCs shown in Supplementary Figure S1, the mathematical model in the dq rotating coordinate is established according to KVL and KCL.

(UtdUtq)(UdUq)Lf(0ωω0)(IldIlq)=(Lfs+Rf+ron)(IldIlq),(1)
(IldIlq)(IdIq)Cf(0ωω0)(UdUq)=Cfs(UdUq),(2)

where utd and utq are dq-axis components of VSC output voltage. id and iq are the dq-axis components of the VSC output current. ud and uq are dq-axis components of the output voltage at PCC. ild and ilq represent the dq-axis components of the inductor current.

2.2 Voltage source converter control system

Supplementary Figure S2 gives a control block diagram for grid-connected VSCs based on their mathematical model with a compensator, and Gcl(s) is the inner loop transfer function.

Since the input reference Udref is a DC value, a PI compensator is designed as

Kvac(s)=kpvacs+kivacs,(3)

where kpvac and kivac are proportional coefficients and integral coefficients, respectively. Then, an open-loop transfer function of VSC operating in the voltage regulation mode is

lvac(s)=kpvacs+kivacs23Ud01τis+1(ω0Lg).(4)

With determined system parameters, cutoff frequency ωcvac and phase margin γvac in the open-loop transfer function of the control system should be designed to meet PCC voltage performance requirements. Therefore, kpvac and kivac are designed based on the parametric equation and determined by γvac and ωcvac. In order to ensure power inner loop gain is 1 or

1τijωcvac+11,(5)

where the cutoff frequency ωcvac gives the control bandwidth of voltage response and should be much smaller than the power inner loop bandwidth 1/τi. In a mathematical model derivation process of this section, filter capacitor influence and dynamic characteristics of PLL are neglected since it is impossible to get the exact value of the power grid-equivalent inductance Lg in an actual operation. Therefore, the phase margin γvac should be wide enough to ensure system stability. A simple way is to set kpvac0; then, kivac is determined by the given cutoff frequency ωcvac and sufficient phase margin.

3 Droop-based multi-voltage source converter control strategy

3.1 Control strategy theoretical analysis

The equivalent circuit of multiple VSC parallel operation is shown in Supplementary Figure S3, where E is the grid voltage and U0 is the voltage value at PCC. ZL is load impedance, Ui and Uj are the voltage of the ith and jth VSC, respectively, and Ii and Ij are the output current. Zoi is the equivalent internal impedance of the ith VSC, and Zvi represents the virtual impedance of this VSC. Z1 is the equivalent output impedance of the power grid.

In Supplementary Figure S3, ith VSC outputs active power Pi and reactive power Qi is

{Pi=UiEZicos(θiφi)E2Zicosθi,Qi=UiEZisin(θiφi)E2Zisinθi.(6)

Since Ziθi is much smaller than ZLθL, it is reasonable to conjecture sinφiφi and cosφi1. Then, Eq. 6 is rearranged as

{Pi=EZi[(UiE)cosθi+Uiφisinθi],Qi=EZi[(UiE)sinθiUiφicosθi].(7)

Also, output impedance is suppressed by introducing a current feedforward control loop Zoi for simplicity. When Zli is much smaller than Rviri, the output impedance Zi of the ith VSC is resistive, and then output impedance Zi is approximately equal to Rviri. Substituting Ziθi=Ri into Eq. 7, the output power characteristics of the ith VSC is

{Pi=ERi(UiE),Qi=UiERiφi,(8)

where Ui is the modulation output voltage amplitude of the ith VSC, which is controlled to track its reference value, and then the output active power is reciprocal to the virtual resistance for parallel operation VSCs. Supplementary Figure S4 gives the output power and voltage relationship curve of the ith and jth VSCs. The slope of each curve is determined by the VSC virtual impedance. When Ui equals to Uj and tune virtual impedance Zvi double as Zvj, the output active power Pi is half of Pj. The same procedure may be easily adapted to obtain control reactive power Qi half as Qj by virtual impedance. The theoretical analysis shows that the VSC output power relies on Zi by following the control law, and the droop characteristic is shaped naturally with Zv dominating the output impedance of VSCs.

3.2 Design control parameters

When paralleled VSCs operate in the active voltage regulation mode, the output characteristics of ith VSC is designed as shown in Supplementary Figure S4 and Eq. 8. The output voltage reference of VSCs in the PV station and wind farm is constrained by the grid code requirements as disturbances like overvoltage/undervoltage protection will shut VSC. So, the voltage constraint is

|ΔU|=|Umea_iUref_i|0.07UN(9)

Substituting the constraints into Eq. 8, then it is rearranged as

(Qmea_iQ0_i)/Zi0.07UN(10)

It can be deduced as

1/Zi|0.07UN(Qmea−iQ0−i)||0.07UNQmax|(11)

In parallel operation, to ensure that the VSC output voltage does not exceed its critical value, the inequality constraint and control sensitivity of Eq. 11 should be comprehensively considered.

4 Robust dynamic stability analysis

4.1 Uncertain system modeling

On-site plant uncertainty is introduced in the modeling process to guarantee the control effect and robustness in engineering application. The basic idea in modeling an uncertain system approach is introducing an independent control loop to represent plant uncertainty and separate stochastic perturbation from the nominal system where disturbance elements are bounded values, as shown in Supplementary Figure S5. The linear fractional transformation method is applied to model the multiple perturbation-embedded physical system, where u is the input, y is the output, and x is the state variable. Supplementary Figure S5A shows the generalized state–space model, and uncertainties are pulled out of the system and formulated in the matrix as shown in Supplementary Figure S5B. Then, the M- structure is established based on the state variable in Eq. 12. Subsequently, the M-Δ structure shown in Supplementary Figure S5B is established based on input u, u’ and output y, y’ as follows:

Gl=yΣuΣ=M22+M21×Δ(IM11Δ)1M12(12)

Therefore, (I-M11∆)−1 is the only term that causes system global instability, and the stability margin is decided by subsystem M11. Supplementary Figure S5D gives the detailed M11Δ structure which can be seen as an extraction of the transfer function matrix. Then, uncertain system modeling mainly focuses on M11 and SSV. The smallest structured Δ (measured in terms of the largest singular value s (Δ)) makes the matrix I−MΔ singular.

μΣ1min{σ¯|det(IMΔ)=0}(13)

According to the aforementioned theoretical analysis, plant parameter inaccuracies, system nonlinearities, control data acquisition, and communication delay are the main reasons of system uncertainties. It is proved that these uncertainties are dominated by system angular frequency. So, the uncertain system modeling process is intuitively simplified as adding perturbations to the nominal plant in a multiplicative way which regroups the plants as

G(s)=G(I+wΔ)(14)

When VSC operates at its normal state, matrix Δ is not bigger than 1. The amplitude is set close to engineering situations of 20% at low frequency and increases till 450% at high frequency as shown in Supplementary Figure S6. The chosen weight accounts for low-frequency uncertainties due to parametric uncertainty, as well as high-frequency neglected dynamic effects or resonant effects from nearby VSCs.

4.2 System small-signal modeling

The global system state–space model of VSCs operating in parallel is derived by applying the CCM method, as shown in Supplementary Figure S7. Subsystem modular is connected to each other with interconnection matrices, and then the whole state–space representation is given as

{x˙Σ=AΣxΣ+BΣuΣ,yΣ=CΣxΣ+DΣuΣ.(15)

As shown in state–space Eq. 15, the coefficient matrix A, B, C, and D are, respectively, given as

{AΣ=A+BL11(IDL11)1C,BΣ=BL11(IDL11)1DL12+BL12,CΣ=L21(IDL11)1C,DΣ=L21(IDL11)1DL12+L22.(16)

Interconnection matrices L indicate connections between inputs and outputs of the subsystems. The coefficient matrices A, B, C, and D are sparse block diagonal matrices obtained from the state–space matrices of single subsystems. The detailed information is given in Supplementary Material S1.

{A=diag{Ac2,ALCL1,ALCL2,Ag,APQ},B=diag{Bc2,BLCL1,BLCL2,Bg,BPQ},C=diag{Cc2,CLCL1,CLCL2,Cg,CPQ},D=diag{Dc2,DLCL1,DLCL2,Dg,DPQ}.(17)

5 Simulation and experimental verification

5.1 Simulation model and parameters

The simulation model of Supplementary Figure S1 is built in the MATLAB/Simulink platform to verify feasibility and effectiveness of the proposed droop-based active voltage regulation control for VSCs. VSC#1 and VSC#2 work in parallel operation and coordinate with each other to control the PCC voltage. The simulation model parameters are shown in Supplementary Tables S1,S2.

5.2 Stability margin analysis

According to the uncertainty representation shown in Supplementary Figure S6, the SSV analysis is applied to evaluate system stability. Parameters listed in Supplementary Tables S1,S2 are aligned with the case studied in Section 2. The system’s robust stability margin is shown in Supplementary Figure S8. The µ-factor of control parameter virtual impedance scanning varies from 0.5 to 2 p.u. The output power short circuit ratio (SCR) varies from 1.5 to 10, and the low-pass filter (LPF) shear frequency varies from 20 to 200 rad/s as shown in Supplementary Figure S8. VSC robust stability increases along with virtual impedance and an increase in SCR. However, an increase in output power and shear frequency reduces the stability margin.

5.3 Case study

A simulation model is developed based on topology given in Supplementary Figure S3, where VSC#1 and VSC#2 are connected in parallel with the grid at PCC. Resistance–inductance load in Supplementary Table S1 is designed to simulate voltage disturbance at PCC. Both VSC#1 and VSC#2 are controlled by the proposed droop-based active voltage regulation control mode. VSC#1 operates in an active voltage regulation control mode at 0.2 s, and its virtual impedance set to 5 kΩ. VSC#2 operates in an active voltage regulation control mode at 0.3 s, and its virtual impedance set to 5 kΩ. At 0.4 s, a load connects in and disconnects at 0.6 s. Voltage fluctuation and reactive power and current response characteristics of VSC#1 and VSC#2 are observed. The virtual impedance value of VSC#2 at 0.7 s is adjusted, and VSC#2 at 0.8 s exits the operation and verifies the change of reactive power distribution among VSCs.

At 0.4 s, the voltage at PCC drops to 0.8 p.u when the load is connected as shown in Supplementary Figure S9. VSC#1 and VSC#2 detect PCC voltage falling and generate reactive power according to their virtual impedance as shown in Supplementary Figure S10. The dynamic response of VSC output current is shown in Supplementary Figures S11,S12. After about four circles of current-loop time constants, the system reaches a steady state. The PCC voltage returns to 0.99 p.u. Due to VSC#2 virtual impedance adjustment, the reactive power distribution between VSCs changes at 0.7 s, which corresponds to the virtual impedance ratio. The output reactive power of VSC#1 and VSC#2 is 10 kVar and 20 kVar, respectively, where Q1:Q2 = 2:1 and R1:R2 = 1:2. It is consistent with the conclusion of the theoretical analysis in Supplementary Figure S4.

When VSC#2 exits at 0.8 s, VSC#1 operates normally and outputs reactive power. The output current characteristics of VSC#1 are shown in Supplementary Figure S12. VSC#1 works normally without an inrush current. The control system ensures autonomous operation of the VSCs, and the power can be automatically distributed as shown in Supplementary Figure S13, according to the control law.

6 Conclusion

An active voltage regulation control strategy is proposed based on the grid-connected VSC working principle, and droop control characteristics are proposed to improve the stability in a large-scale RES-integrated power system. The proposed control strategy and control parameter design process are designed regarding to the plant uncertainty and parameter deviation for engineering applications which guarantee the control effect and robustness in PV stations and wind farms. The active voltage regulation and automatic response to the PCC voltage disturbance features improved the flexibility of VSCs in PV stations and wind farms significantly. The feasibility and effectiveness of the proposed active voltage regulation strategy are verified by logical deduction and practical simulation based on a generalized small-signal model.

Data availability statement

The original contributions presented in the study are included in the article/Supplementary Material; further inquiries can be directed to the corresponding author.

Author contributions

ZZ: conceptualization, methodology, data curation, simulation test, and writing. XS: supervision and conceptualization. JY: investigation and data curation. PZ: simulation and resources. HC: simulation test and resources. GL: resources.

Funding

This work is cofunded by the National Natural Science Foundation of China (52167022), Natural Science Foundation of Qinghai (2022-ZJ-935Q), and Youth Foundation of Qinghai University (2021-QGY-4).

Acknowledgments

The authors thank State Grid Qinghai Electric Power Company for providing an on-site experimental data test platform in PV stations and wind farms. We also thank Bowen Cao, Lize Liu, and Chaofan Zhao for their help with drawings in the article.

Conflict of interest

Authors JY, PZ, HC, and GL were employed by State Grid Qinghai Electric Power Company.

The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Publisher’s note

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors, and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.

Supplementary material

The Supplementary Material for this article can be found online at: https://www.frontiersin.org/articles/10.3389/fenrg.2022.1005593/full#supplementary-material

References

Ge, R., Dong, Y., and Lu, Y. C. (2007). Analysis of large-scale blackout in UCTE power grid and lessons to be drawn to power grid operation in China. Power Syst. Technol. 3, 1–6.

Google Scholar

Han, Y., Zhang, K., Li, H., Coelho, E. A. A., and Guerrero, J. M. (2018). MAS-Based distributed coordinated control and optimization in microgrid and microgrid clusters: A comprehensive overview. IEEE Trans. Power Electron. 33 (8), 6488–6508. doi:10.1109/tpel.2017.2761438

CrossRef Full Text | Google Scholar

Le, J., Zhao, L. G., Liao, X. B., Zhou, Q., and Liang, H. (2020). LANG HongkeStability analysis of grid-connected inverter system containing virtual synchronous generator under time delay and parameter uncertainty. J. Electr. Eng. Technol. 16, 1779–1792. doi:10.1007/s42835-021-00710-y

CrossRef Full Text | Google Scholar

Li, S. L., Wang, W. S., and Wang, R. M. (2016). High-voltage ride-through control strategy and experiment of doubly-fed wind turbines. Automation Electr. Power Syst. 40 (16), 76–82.

Google Scholar

Lu, X., Wang, J., Guerrero, M., and Zhao, D. (2018). Virtual-impedance-based fault current limiters for inverter dominated AC microgrids. IEEE Trans. Smart Grid 9 (3), 1599–1612. doi:10.1109/tsg.2016.2594811

CrossRef Full Text | Google Scholar

Lu, Z. K. (2020). Research on integrated control strategy of photovoltaic VSG under power grid voltage drop. Xi'an Univ. Technol.

Google Scholar

Ma, S. K., Hua, G., Liu, L., Yang, G., and Pal, B. C. (2018). Grid-synchronization stability improvement of large scale wind farm during severe grid fault. IEEE Trans. Power Syst. 33 (1), 216–226. doi:10.1109/tpwrs.2017.2700050

CrossRef Full Text | Google Scholar

Mahdian Dehkordi, N., Sadati, N., and Hamzeh, M. (2017). Distributed robust finite-time secondary voltage and frequency control of islanded microgrids. IEEE Trans. Power Syst. 32 (5), 3648–3659. doi:10.1109/tpwrs.2016.2634085

CrossRef Full Text | Google Scholar

Mahdian Dehkordi, N., Sadati, N., and Hamzeh, M. (2017). Fully distributed cooperative secondary frequency and voltage control of islanded microgrids. IEEE Trans. Energy Convers. 32 (2), 675–685. doi:10.1109/tec.2016.2638858

CrossRef Full Text | Google Scholar

Natarajan, V., and Weiss, G. (2017). Synchronverters with better stability due to virtual inductors, virtual capacitors, and anti wind-up. IEEE Trans. Ind. Electron. 64 (7), 5994–6004. doi:10.1109/tie.2017.2674611

CrossRef Full Text | Google Scholar

Rodriguez, P., Citro, C., Candela, I., Rocabert, J., and Luna, A. (2018). Flexible grid connection and islanding of SPC-based PV power converters. IEEE Trans. Ind. Appl. 54 (3), 2690–2702. doi:10.1109/tia.2018.2800683

CrossRef Full Text | Google Scholar

Su, X. L., Chen, L. J., Jun, Y., Li, Z., Zhou, P., and Chen, H. (2021). On-site engineering test of active support control for the PV station and wind farm in the AC-DC hybrid power grid under extreme fault conditions. Complexity 2021, 1–13. doi:10.1155/2021/9636383

CrossRef Full Text | Google Scholar

Su, X. L., Zhao, Z. K., Si, Y., and Guo, Y. Q. (2020). Adaptive robust SMC-based AGC auxiliary service control for ESS-integrated PV/wind station. Complexity 2020, 1–10. doi:10.1155/2020/8879045

CrossRef Full Text | Google Scholar

Sumsurooah, S., Odavic, M., and Boroyevich, D., Modelling and robust stability analysis of uncertain systems, Proceedings of the 2013 Grand Challenges on Modeling and Simulation Conference. 2013.

Google Scholar

Sumsurooah, S., Odavic, M., and Bozhko, S. (2018). $\mu$ approach to robust stability domains in the space of parametric uncertainties for a power system with ideal CPL. IEEE Trans. Power Electron. 33 (1), 833–844. doi:10.1109/tpel.2017.2668900

CrossRef Full Text | Google Scholar

Sun, H. B., Guo, Q. L., and Pan, Z. G. (2015). Energy internet: concept、architecture and frontier outlook. Automation Electr. Power Syst. 39 (19), 1–8.

Google Scholar

Wang, B., Yang, D. Y., and Cai, G. W. (2020). Review of research on power system inertia related issues in the context of high penetration of renewable power generation. Power Syst. Technol. 44 (8), 2998–3007.

Google Scholar

Wang, X. F., and Blaabjerg, F. (2019). Harmonic stability in power electronic-based power systems: Concept, modeling, and analysis. IEEE Trans. Smart Grid 10 (3), 2858–2870. doi:10.1109/tsg.2018.2812712

CrossRef Full Text | Google Scholar

Wei, C., Zhao, Y., Zheng, Y., Xie, L., and Smedley, K. (2021). Analysis and design of a non-isolated high step-down converter with coupled inductor and ZVS operation. IEEE Trans. Ind. Electron. 69, 9007–9018. doi:10.1109/tie.2021.3114721

CrossRef Full Text | Google Scholar

Wei, C., Xu, J., Chen, Q., Song, C., and Qiao, W. (2022). Full-order sliding-mode current control of permanent magnet synchronous generator with disturbance rejection, Proceedings of the IEEE Journal of Emerging and Selected Topics in Industrial Electronics, IEEE, 20 July 2022.

CrossRef Full Text | Google Scholar

Xiao, D., Chen, H., Wei, C., and Bai, X. (2021), Statistical measure for risk-seeking stochastic wind power offering strategies in electricity markets, Proceedings of the Journal of Modern Power Systems and Clean Energy, SGEPRI, 08 December 2021.

Google Scholar

You, R., Barahona, B., Chai, J., Cutululis, N. A., and Wu, X. (2017). Improvement of grid frequency dynamic characteristic with novel wind turbine based on electromagnetic coupler. Renew. Energy 113, 813–821. doi:10.1016/j.renene.2017.06.038

CrossRef Full Text | Google Scholar

Yuan, H., Yuan, X. M., and Hu, J. B. (2017). Modeling of grid-connected VSCs for power system small-signal stability analysis in DC-link voltage control timescale. IEEE Trans. Power Syst. 32 (5), 3981–3991. doi:10.1109/tpwrs.2017.2653939

CrossRef Full Text | Google Scholar

Zhang, L., Harnefors, L., and Nee, H. P. (2010). Power synchronization control of grid-connected voltage source converters. IEEE Trans. Power Syst. 25 (2), 809–820. doi:10.1109/tpwrs.2009.2032231

CrossRef Full Text | Google Scholar

Zhong, Q. C., Nguyen, P. L., Ma, Z., and Wang, S. (2014). Self-synchronized synchronverters: Inverters without a dedicated synchronization unit. IEEE Trans. Power Electron. 29 (2), 617–630. doi:10.1109/tpel.2013.2258684

CrossRef Full Text | Google Scholar

Zhong, Q. C., and Weiss, G. (2011). Synchronverters: Inverters that mimic synchronous generators. IEEE Trans. Ind. Electron. 58 (4), 1259–1267. doi:10.1109/tie.2010.2048839

CrossRef Full Text | Google Scholar

Zhuo, Z. Y., Zhang, N., and Xie, X. R. (2021). Key technologies and development challenges of power system with high proportion of renewable energy. Automation Electr. Power Syst. 45 (9), 171–191.

Google Scholar

Keywords: active voltage regulation, voltage source converters, plant uncertainty, robust stability, renewable energy sources

Citation: Zhao Z, Su X, Yang J, Zhou P, Chen H and Lu G (2022) Droop-based active voltage regulation control and robust stability analysis for VSCs in the large-scale RES-integrated power system. Front. Energy Res. 10:1005593. doi: 10.3389/fenrg.2022.1005593

Received: 28 July 2022; Accepted: 07 September 2022;
Published: 23 September 2022.

Edited by:

Dongliang Xiao, South China University of Technology, China

Reviewed by:

Bo Liu, Kansas State University, United States
Jin-Oh Lee, Korea Electrotechnology Research Institute, South Korea

Copyright © 2022 Zhao, Su, Yang, Zhou, Chen and Lu. This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.

*Correspondence: Xiaoling Su, suxiaoling@qhu.edu.cn

Download