ORIGINAL RESEARCH article

Front. Built Environ., 04 October 2019

Sec. Bridge Engineering

Volume 5 - 2019 | https://doi.org/10.3389/fbuil.2019.00114

Field Testing of a Prestressed Concrete Bridge With High Performance and Locally Developed Ultra-High Performance Concrete Girders

  • 1. Department of Civil Engineering, College of Engineering, New Mexico State University, Las Cruces, NM, United States

  • 2. Stubbs Engineering Incorporated, Las Cruces, NM, United States

Abstract

Recent research has developed mixture proportions for ultra-high performance concrete (UHPC) using materials primary local to New Mexico, United States of America (USA). In 2017, a two-span bridge was constructed in Anthony, New Mexico, USA consisting of prestressed girders using the locally developed non-proprietary UHPC, for span one, and high performance concrete (HPC), for the second span. Field tests were conducted on the bridge ~9 months apart to investigate the performance and behavior of the UHPC and provide baseline data for future studies and condition evaluation of the bridge. The load tests consisted of various load configurations utilizing up to four trucks weighing 267 kN on average. The load paths were designed to maximize strains along the length of the bridge and investigate transverse load distributions between girders. The measured results provide a comparison of the behavior and performance of the UHPC and the HPC girders and were also compared to the American Association of State Highway and Transportation Officials (AASHTO) predicted behaviors. This study is one of the first that compares HPC and non-proprietary UHPC bridge performance subjected to the same environmental conditions and vehicular loading. The findings of the study will aid in the development of recommendations incorporating UHPC into design provisions as well as provide meaningful information of the short and long-term performance between the two materials including durability and load distribution.

Introduction

Ultra-high performance concrete (UHPC) is an increasingly utilized material that provides high compressive strengths and advanced durability properties. Typically including fiber reinforcement, UHPC provides significantly increased post-cracking strength and ductility, allowing for the reduction or elimination of conventional mild steel reinforcement in structural members. The advantages to structural design, offered by the advanced mechanical and durability properties of UHPC, include the potential for longer lifespans and corresponding reductions in lifecycle economic impacts. Additionally, UHPC allows for smaller, lighter structural members that require less structural detailing, and facilitate more rapid construction and reduced service-life maintenance (Ahlborn et al., ).

Proprietary UHPC mixture proportions are currently available in the United States of America (USA), however, the lack of standardized domestic design specifications and high material costs have limited the widespread use of UHPC. The USA Federal Highway Administration (FHWA) has fostered research to provide a greater understanding of UHPC material properties and promote the use of this advanced structural material (Graybeal, ). Research has been focused primarily on commercially available products, although, the use of non-proprietary mixture proportions in structural applications is being investigated in different states of the USA.

Non-proprietary UHPC mixture proportions utilizing unique mixing procedures, curing regimens, and materials typical of precast production and primarily local to New Mexico (NM) have been developed. The resulting material possesses the superior mechanical and durability properties characteristic of UHPC (Muro-Villanueva et al., ; Weldon et al., ). More recent research has focused on the experimental testing of full-scale structural components and implementation of the non-proprietary UHPC in a local precast-prestressed bridge (Taylor et al., ; Giesler et al., ; Manning et al., ; Giesler et al., ; Visage et al., ). Based on the results of an extensive research program, the design and construction of the first non-proprietary UHPC bridge in New Mexico were successfully completed in 2017. The bridge is a two-span structure and is fabricated with non-proprietary UHPC (145 MPa) girders for span 1, and conventional high performance concrete (HPC, 65.5 MPa) girders, typical of bridge construction in New Mexico, for span 2. The design and behavior of this non-proprietary UHPC are being validated through short-term and long-term strain monitoring of the bridge. This study reports on the first load tests conducted on the bridge following construction.

To evaluate the behavior of the two-span bridge, the superstructure was equipped with external strain gauges and load tested. In early 2017, a diagnostic load test under a slow moving truck load was completed and ~9 months later a diagnostic test under incremental, static truck loads was conducted on the bridge in 2018. The diagnostic test using a slow moving load, referred to as stage 1 loading, consisted of one truck moving at ~8 km/h across the bridge along six load paths. Each path was designed to maximize the response of a single girder and was used to gain an initial understanding of the bridge response and provided guidance for the tests under multiple truck loads. The diagnostic test using incremental static loads, referred to as stage 2 loading, involved the application of the maximum feasible load using up to four trucks statically along several load paths to maximize the response of the bridge. This paper presents the results of the stage 1 and stage 2 load tests conducted on the bridge and compares the responses between the UHPC and HPC spans. Additionally, the measured response of the bridge is compared to the design-based estimated behavior.

Background

UHPC is an advanced construction material that provides new opportunities for the future of highway infrastructure. This class of concrete has enhanced properties that address specific problems for highway bridge infrastructure, such as increased service life through improved durability and tensile ductility. Initial material development and structural testing of UHPC began more than two decades ago. The first UHPC traffic bridge was constructed in 2001 in the France's Drome region (Hajar et al., ). The first field deployment of UHPC in the USA was the construction of a prestressed concrete girder bridge in Wapello County, Iowa in 2006 (Graybeal, ). Since being introduced, more than 100 bridges (motorway and pedestrian) have incorporated UHPC in one or more components including shear keys, overlays, and joint connections (Graybeal, ; Brühwiler and Denarié, ; Voo et al., ; Yuan and Graybeal, ).

Proprietary UHPC has been implemented in different applications throughout the world. However, the high cost of the materials, a lack of design code provisions, and low industry familiarization with the material have limited its use, particularly in the USA. With the intention of improving the economic impact and increase sustainability, Weldon et al. () developed and tested non-proprietary UHPC using materials local to New Mexico that has mechanical and durability properties similar to commercially available products. Furthermore, the use of familiar material constituents makes implementation into precast plants, ready-mix applications, and construction practices simpler.

Development of Local UHPC

Mixture Proportions

Allena () investigated the use of material constituents local to New Mexico for the development of UHPC. Mixture proportions included fine aggregate, Type I/II Portland cement, silica fume, high-range water-reducing admixture (HRWRA), and a dosage of steel fibers. To increase sustainability and reduce cost, Lyell () replaced a portion of silica fume with Class F fly ash. Final optimization was conducted by Weldon et al. () by increasing the size and quantity of the aggregates. The final mixture proportions used a fine aggregate with a 4.76 mm nominal top size. Greater economy was achieved by reducing labor costs associated with tedious sieving of fine aggregates without negative effects on the mechanical properties of the UHPC. High strength steel fibers were provided at 1.5% by volume. The UHPC had a design compressive strength of 146 MPa.

Laboratory Testing

Investigation of the flexural behavior of locally developed non-proprietary UHPC began with a parametric study in which small-scale specimens were tested in flexure (Manglekar et al., ; Visage et al., ). The results showed favorable potential for UHPC made with local materials and research moved to the implementation of UHPC in precast/prestressed applications. Flexural testing of large-scale prestressed beams by Giesler et al. (, ) was conducted to further verify the flexural behavior of non-proprietary UHPC and continue the development of structural design models. The scope of the research included modifications to the curing regimen and trial batching for implementing UHPC into precast plant production. Three prestressed concrete beam specimens were designed according to AASHTO () for flexure with modifications made for the improved material properties of UHPC including changes to the modulus of elasticity, compressive strength, and tensile strength. Flexural testing validated the designs. Manning et al. () designed two full-scale prestressed girders; one using conventional HPC typical of current New Mexico bridge design, and the second designed using the locally developed UHPC. Both sections were designed to provide equal capacities and thus, flexural investigations of the sections provided a direct comparison of the behavior and performance of the two types of concrete. The UHPC girder, with a reduced cross-section and reduced shear reinforcement, provided the same capacity, equal stiffness, and improved post-cracking behavior compared to the HPC girder.

Field Testing

Load testing is a proven field method to evaluate the structural capacity, construction quality, and effectiveness of new materials used for bridge construction. The American Association of State Highway and Transportation Officials (AASHTO) recommends load testing to evaluate the in-situ bridge response and behavior under loading (AASHTO, ). The goal of a load test is to evaluate a bridge's structural response without causing damage to the structure. The measured response can then be compared to theoretical behavior to improve design methods and procedures. Furthermore, load tests can provide information necessary to guide inspections, improve asset management, and identify best repair practices. Load testing is also an effective method for determining load ratings for bridges without plans (Aguilar et al., , ; Cuaron et al., ). Diagnostic load testing provides an initial measure of the load effects (i.e., moment, shear, deflection, load distribution) in the structure due to applied loads (Phares et al., ) and provides a means to identify critical components or load paths for further investigation. Proof load testing determines the magnitude and configuration of loads that cause structural components to approach their elastic limit (Cai et al., ), and typically the loads are applied statically using blocks, sandbags, etc. (Lantsoght et al., ). In some cases, the proof load test targets critical components rather than testing the full bridge.

Load testing has been used to evaluate and rate bridge response, investigate fatigue life (Alampalli and Lund, ) and to evaluate new construction materials and technologies (Hou and Lynch, ; Kleinhans et al., ). Load testing was used to load rate a bridge in New York, USA that replaced the bridge deck with a fiber reinforced polymer (FRP) deck, that was 80% lower in weight compared to the original concrete deck (Alampalli and Kunin, ). Load testing was also used to evaluate the capacity and performance of a bridge strengthened with FRP laminates. Load tests were conducted before and after the installation of the laminates to assess the effectiveness of the strengthening FRP system (Hag-Elsafi et al., ). Similarly, in New Mexico a bridge was retrofitted with carbon fiber-reinforced polymer (CFRP) laminates. Load tests were performed before and after retrofitting the bridge and again 9 years after the installation of the laminates to evaluate the immediate and long-term effectiveness of the CFRP retrofit of the bridge (Regalado et al., ). The load tests used in this research were used to validate the use of the non-proprietary UHPC using local materials in bridge design.

Description of Bridge 9706

It should be noted that research conducted by Manning et al. () helped to further improve methods of precast production of UHPC prestressed bridge girders in New Mexico and the analyses of specimens cast from UHPC. The research findings of Manning et al. () and Giesler et al. (, ) were instrumental in the development and design of the first bridge incorporating locally developed UHPC in New Mexico, Bridge 9706.

Bridge 9706 replaced a structurally deficient bridge in Anthony, New Mexico, USA. The bridge has an 18° skew and is comprised of two 7.62 m spans with a rail-to-rail width of 9.14 m (9.75 m out-to-out). The bridge supports two design lanes. The girders in the East span of the bridge were designed with UHPC and the girders in the West span were designed using HPC typically used for prestressed concrete in New Mexico. The UHPC channel girders are 317.5 mm in depth and the HPC channel girders are 381 mm in depth. The resulting span-to-depth ratios are 24:1 for the UHPC span and 20:1 for the HPC span. A stepped abutment was used to accommodate the different depths of the girders. The channel girders are placed directly next to one another and transversely fastened with a threaded rod through the stems at midspan. Embedded 305 mm long steel bearing seats rest on elastomeric bearing pads at the abutments and middle pier. Additionally, there is a 127 mm composite normal strength concrete (NSC) deck (see Figure 2A) and New Mexico Department of Transportation (NMDOT) metal-thrie bridge railings are attached to the edge girders. Overall, the bridge has a length of 15.24 m and carries NM-186 over an irrigation canal. A photo of the Bridge 9706 during construction, completion, and the bridge profile and interior and edge girder cross-sections are shown in Figures 1, 2, respectively. The girders were designed with twelve straight Grade 270, seven wire low relaxation prestressed strands with a diameter of 15.2 mm (area = 140 mm2 per strand). Each strand had a designed pre-stress force of 260.6 kN, for a total force of 3,128 kN per girder. The width of the exterior stem of the edge girder was increased to accommodate the bridge rail connection (see Figures 2D,E).

Figure 1

Figure 2

Instrumentation

Bridge 9706 was instrumented with 36 external strain transducers placed at midspan of both spans. For each span, 12 strain transducers were attached to the bottom of the stem and six were attached at mid-height of the stem. The instrumentation layout was the same for the stage 1 and stage 2 load tests. The girder and stem gauges are numbered from North to South and labeled using the notation: N/S—North stem/South stem, B/M—gauge location on bottom or at mid-height of the stem, and G#—girder number. The placement of strain gauges on each span is shown on the bridge cross-section in Figure 3.

Figure 3

Preparatory Calculations

Available Moments and Strains

The available strain capacities of the bridge girders were computed and used to monitor the measured strains during the load tests to prevent damage to the bridge. To obtain the available strains, the girder cracking moment was first calculated. The dead load moment was then subtracted to determine the available moment capacity the beam can resist before cracking. The available moment was divided by the product of the section modulus and the design modulus of elasticity to obtain the available strain. The available moment and strain equations are given in Equations (1) and (2).

where fcr is the modulus of rupture, Pe is the effective prestress determined from the AASHTO Load and Resistance Factor Design (LRFD) Specifications, Anc is the area of the non-composite section, and enc is the distance between the centroid of the non-composite section to the centroid of the strands. Sc, Snc, Mdc, and Mdnc are the composite and non-composite section moduli and the composite and non-composite dead load moments, respectively. The available strain capacity for the beam is computed as:

where Edesign is the concrete elastic modulus (either for UHPC or HPC). Equation (3) (Grabeal, ) and Equation (4) (ACI Committee, ) are used to calculate the modulus of elasticity for the UHPC and HPC, respectively:

where is the compressive strength of UHPC, is the compressive strength of HPC, and wc is the weight of the concrete (2,402 kg/m3). Table 1 summarizes the section properties, calculated moments, and strains for the UHPC and HPC girders, where k is the remaining prestress force percentage after all losses, fpi is the actual effective prestressed stress after all losses, Inc is the moment of inertia for the non-composite section, and the other parameters were previously defined.

Table 1

VariableUHPCHPC
EdgeInteriorEdgeInterior
k0.790.740.790.74
fpi (MPa)1469137914681378
Number of strands12.012.012.012.0
Area per strand (mm2)140140140140
Pe (kN)1,9741,9301,9461,594
Sc (mm3)1.8 × 1071.4 × 1072.4 × 1071.8 × 107
Snc (mm3)1.05 × 1077.9 × 1061.5 × 1071.14 × 107
Anc (mm2)2.3 × 1052.01 × 1052.6 × 1052.2 × 105
Inc (mm4)2.02 × 1091.62 × 1093.45 × 1092.78 × 109
Edesign (MPa)46,19246,19240,96840,968
enc (mm)51.5657591.7
girder (MPa)14514565.565.5
deck (MPa)27.527.527.527.5
fcr (MPa)5.95.93.93.9
Mdnc (kN-m)66.761.172.265
Mdc (kN-m)7.20.007.20.00
Mavailable (kN-m)308293383362
εavailable*370455389483

UHPC and HPC available moment and strain parameters.

*

Available strain using effective flange width of 1,220 mm.

Live Load Distribution Factor

To calculate the bending moments for the girders, the lateral distribution was calculated in accordance with the current design standard. The AASHTO LRFD Bridge Design Specifications were used for Bridge 9706. Table 4.6.2.2.1–1 in Articles 4.6.2.2.2 and 4.6.2.2.3 defines the superstructure types. Bridge 9706 was considered as type (h), precast concrete channel sections with shear keys and a cast-in-place concrete overlay, although the bridge has a composite deck instead of an overlay.

Tables 4.6.2.2.2b–1 and 4.6.2.2.2d–1 provide the live load distribution factors for moment in interior and edge beams, respectively, based on the type (h) equations for interior beams and the lever rule calculation for edge beams.

A summary of the calculated AASHTO live load distribution factors for UHPC and HPC girders are presented in Table 2.

Table 2

UHPCHPC
Lanes loadedOneTwoThreeOneTwoThree
Edge0.600.500.430.600.500.43
Interior0.3400.3330.3270.3410.3350.329

AASHTO live load distribution factors for UHPC and HPC.

Expected Strains

For comparison to the available moment and strain capacities calculated from Equations (1) and (2), the total expected midspan moment was first calculated for the test truck applied in the stage 1 load test. The total moment was then multiplied by the design-based distribution factor from AASHTO and the “upper bound” distribution factor that represents the worst-case scenario for live load distribution between the girders (i.e., a distribution factor of one). These two factors provide the range of expected girder moments possible for the stage 1 and stage 2 test loads. The expected strains for UHPC and HPC girders were computed using Equation (5) and strain values are presented in Table 3.

where DFint. and DFedge are the distribution factors for an interior and edge girder, respectively.

Table 3

Truck loadingεexpected(με)
AASHTO DFDF = 1
UHPCHPCUHPCHPC
Interior single truck11195326279
Edge single truck133112221187
Interior double truck side-by-side174150326280
Edge double truck side-by-side133112221187
Interior triple truck side-by-side171147326280
Edge triple truck side-by-side133112221187
Interior single truck back-to-back127109373320
Edge single truck back-to-back152128253214
Interior double truck back-to-back199171373320
Edge double truck back-to-back152128253214

Expected strain.

Stage 1 Load Testing

A moving diagnostic load test (stage 1) was first conducted to gain an understanding of the in-situ bridge behavior prior to the load test with larger truck loads (stage 2). The magnitude of the total truck load applied on the bridge during the stage 1 load test was less than the stage 2 target load due to the uncertainties in the bridge response. Load was applied in the stage 1 load test in similar paths used in the stage 2 load test for the single truck paths configurations; however, truck loads and paths were not applied to maximize the loading but to gather information on the behavior, load distribution between adjacent girders, and to compare the initial structural response between the UHPC and HPC spans. Six single truck load paths were conducted as part of the stage 1 load test. A single truck was applied as a slow-moving load along the transverse paths shown in Figure 4.

Figure 4

On March 30, 2017, the stage 1 load test was performed on Bridge 9706. Figure 5 shows a photo of a single truck on the bridge. Two load trucks, weighing 275 kN on average, were used during the stage 1 load test. Table 4 shows the axle weights of the trucks used for the stage 1 load test.

Figure 5

Table 4

Truck numberAxle weight (kN)Total weight (kN)
Front singleRear tandem
170209279
263208271

Stage 1 load test: truck weights.

Maximum Strain for UHPC and HPC Spans

The maximum strain for each load path and the corresponding strain transducer and location on the UHPC span and HPC span is shown in Table 5. The maximum measured strain for each load path on each span is indicated in bold. The strains measured during the stage 1 load test and bridge behavior are discussed later.

Table 5

Gauge locationPath 1Path 2Path 3Path 4Path 5Path 6
UHPC STRAIN SINGLE TRUCK LOAD (με)
NBG1814719843
SBG18962281797
NBG28161291976
SBG2676342291310
NBG3666548321514
SBG3616664512826
NBG4545560543225
SBG4454866695648
SBG5212347636062
SBG6131228446471
SBG75514254686
SBG8225183285
HPC STRAIN SINGLE TRUCK LOAD (με)
NBG1743812622
SBG17650191466
NBG27860281777
SBG2707245291515
NBG3676844301613
SBG3566163503024
NBG4566165553526
SBG4505375736054
SBG5253057727473
SBG691228437077
SBG72513224378
SBG8237102578

Maximum stage 1 load test strains of UHPC and HPC.

Strain Comparison Between UHPC and HPC Spans

Comparing the strains between the UHPC span and the HPC span for the stage 1 load test, the following was observed:

  • The largest measured strains in the UHPC span, were 89 and 86 με for paths 1 and 6, respectively (see Table 5). For the HPC span, the largest measured strains were 78 and 78 με during path 1 and path 6, respectively.

  • The edge girders for both the UHPC and HPC spans experienced more tensile strains for paths 1 and 6 since the truck wheel loads were positioned over the edge girders. When the truck load was moved toward the interior girders, the tensile strains showed better distribution between adjacent girders, typically resulting in lower strains.

  • Strains measured in the UHPC span were higher than strains in the HPC span. The maximum strains for the UHPC span occurred in either girder 1 or 7. The maximum strains for the HPC span occurred in either girder 2 or 7. The HPC girders have a larger cross-sectional area compared to the UHPC girders. Although the UHPC and HPC girders were designed to have the same capacity, UHPC girders measured higher values of strain. Although the modulus of elasticity of the UHPC is greater than that of HPC, the section modulus is smaller. The section and elastic moduli ratio between the UHPC and HPC are 0.7 and 1.2, respectively.

  • Figure 6 shows the strain behavior across the bridge width for load paths 1 (North side) and 6 (South side). More strain transducers were placed on girders 1–4, therefore, additional data points are shown for these girders. The results illustrate the symmetric behavior of the bridge as expected for a newly constructed bridge.

Figure 6

Comparison of Measured and Expected Strains

The maximum measured stage 1 load test strains and the expected strains are tabulated in Table 6. The percent difference between the two strain values is also shown. Overall, the measured strains for the UHPC and HPC spans were lower than the predicted behavior, indicating the designed-based load distribution factors to be conservative for the UHPC and HPC bridge girders. The percent difference between the measured and expected strains for the UHPC girders is slightly larger than the HPC girders indicating better load distribution in the UHPC bridge.

Table 6

Truck loadingStrain (με)
UHPCHPC
Interior singleExpected11195
Measured8678
Difference23%18%
Edge singleExpected133112
Measured8978
Difference33%30%

Stage 1 load test: expected vs. measured strain.

Stage 2 Load Testing

Based on the results from the stage 1 load test, the bridge showed no signs of cracking nor did it exceed the available strain. The measured strains were 24 and 19% of the available strains for edge and interior UHPC girders, respectively. The measured strains were 20 and 16% of the available strains for interior and edge HPC girders, respectively. Consequently, the stage 2 load test was planned and conducted with the goal of applying the largest load possible to the bridge without exceeding the available moment to investigate the bridge behavior at larger loads. The bridge behavior under the stage 2 truck loading was monitored carefully via strain measurements. For the stage 2 load test, the test vehicles were loaded to the maximum weight and positioned along the paths producing the largest girder strains (critical paths). As the applied loads increased during the stage 2 load test, the measured strains were monitored carefully to ensure they did not exceed the expected or available strains. Single truck, double truck side-by-side, triple truck side-by-side, single truck back-to-back, and double truck back-to-back (i.e., four trucks) loadings were done as part of the stage 2 load test. The loading was applied by moving the trucks incrementally to specified locations along the span. Figures 7A–C, show pictures of the bridge being loaded with the single truck back-to-back, double truck back-to-back, and triple truck side-by-side load paths during the stage 2 load test. Figures 8A,B show the configurations of the double truck side-by-side and triple truck side-by-side paths for the stage 2 load test. Figure 9A shows the bridge profile with the back-to-back truck loadings, which are applied in similar path configurations as illustrated in Figure 4 (single truck back-to-back) and Figure 8A (double truck back-to-back). The back-to-back load path configurations were incrementally loaded, placing the center of the two rear tandem axels at the abutments, quarter-points, mid-points, and pier along the length of the bridge. Figures 9B,C show the top view of the bridge being loaded with single and double truck back-to-back load path configurations, respectively. It is noted that multiple load paths were used, however, only one example path is shown. For the stage 2 load test, dump trucks were maximized in weight and applied in different configurations to maximize the moment along the length of the bridge. The truck configurations included single truck, single truck back-to-back, double truck back-to-back (four trucks), and triple truck side-by-side. The double truck back-to-back and triple truck side-by-side configurations maximized the number of trucks that could be applied based on the dimensions of the bridge and were used to apply the largest load feasible. The truck moments applied to the bridge during the stage 1 and stage 2 load tests were about 15 and 20% higher than the non-factored standard truck live load moment (HL93), respectively.

Figure 7

Figure 8

Figure 9

From January 29 through January 31, 2018, the stage 2 load test was performed on Bridge 9706, 9 months after the stage 1 load test. Four load trucks, weighing on average 283 kN, were used for the test. Table 7 shows the axle weights of the trucks used for the stage 2 load test. The stage 2 load test consisted of a preliminary load test in which a few slow-moving and incremental truck load paths were used to calibrate the strain transducers and ensure the behavior of the bridge had no significant changes since the time of the stage 1 load test. Then, the stage 2 load test was conducted loading the trucks onto the bridge following the designed paths to maximize the total load applied to each span.

Table 7

Test dateTruck numberAxel weight (kN)Total weight (kN)
Front singleRear tandem
Jan 29th170214284
270216286
365217282
476213289
Jan 30th170213283
268213281
364213278
475210285
Jan 31st170211281
268213281

Stage 2 load test: truck load weights.

Maximum Strains

Table 8 provides the maximum measured strains for each load path configuration on the UHPC span and HPC span. The maximum measured strain for each load path configuration on each span is indicated in bold. The strains measured during the stage 2 load test and bridge behavior are discussed later.

Table 8

Gauge locationSingle truckDouble truck side-by-sideTriple truck side-by-sideSingle truck back-to-backDouble truck back-to-back
UHPC SPAN STRAINS (με)
NBG13217820146
SBG15279219148
NBG25348819154
SBG24407320127
NBG36528620150
SBG312759327143
NBG416889830141
SBG43010310248136
SBG5521091047588
SBG68410312210067
SBG79912612812040
SBG89011910710514
HPC SPAN STRAINS (με)
NBG18306912115
SBG18377910113
NBG28549317135
SBG212699717140
NBG3106811020130
SBG32110911133143
NBG4201059433124
SBG43812711756138
SBG57112912793117
SBG69512212010980
SBG79312010010151
SBG8971059812033

Maximum stage 2 load test strains for UHPC and HPC.

Strain Comparisons Between UHPC and HPC Spans

Comparing the strains between the UHPC span and the HPC span for the stage 2 load test, the following was observed:

  • For a single truck load, the maximum strain for the UHPC span was 99 με, which was higher than the strain measured for the HPC span, 95 με. Similarly, the strain measured for double truck side-by-side loading for the UHPC span was 126 με and for the HPC span was 129 με.

  • For triple truck side-by-side loading, the largest measured strain for the UHPC span was 128 με. For the HPC span, the largest measured strain was 127 με. During this loading, the strains were more evenly distributed across all girders.

  • The maximum measured strain for single truck back-to-back loading for the UHPC span was 120 με, and for the HPC span was 120 με.

  • For the double truck back-to-back load path, the largest measured strains for the UHPC span was 154 με. For the HPC span, the largest measured strain was 143 με.

  • The maximum strains usually occurred in the UHPC and HPC interior girders. Results show that as the bridge becomes more uniformly loaded, measured strains between the HPC and UHPC spans are more similar.

Comparison of Measured and Expected Strain

The maximum measured stage 2 load test strains and the expected strains are presented in Table 9. The percent difference between the two strains is also shown. Overall, the measured strains for the UHPC and HPC spans were lower than the predicted behavior, indicating that the designed-based load distribution factors are conservative for both the UHPC and HPC bridge girders. Again, in general, the UHPC predicted strains are greater in comparison to the measured strains than those for the HPC span. This indicates better load distributions for the UHPC span compared to HPC span.

Table 9

Girder/load path configurationStrain (με)
UHPCHPC
Interior/single truckExpected11195
Measured9995
Difference11%0%
Edge/single truckExpected133112
Measured9097
Difference32%13%
Interior/double truck side-by-sideExpected174150
Measured126129
Difference28%14%
Edge/double truck side-by-sideExpected133112
Measured119105
Difference11%6%
Interior/triple truck side-by-sideexpected171147
Measured128127
Difference25%14%
Edge/triple truck side-by-sideExpected133112
Measured10798
Difference20%13%
Interior/single truck back-to-backExpected127109
Measured120109
Difference6%0%
Edge/single truck back-to-backExpected152128
Measured105120
Difference31%6%
Interior/double truck back-to-backExpected199171
Measured154143
Difference23%16%
Edge/double truck back-to-backExpected152128
Measured148115
Difference3%10%

Stage 2 load test: expected vs. measured strain.

Conclusions

The stage 1 load test of Bridge 9706 was comprised of six single truck load paths (slow-moving). The stage 2 load test was conducted ~9 months after the stage 1 load test, focusing on the behavior of the new concrete material, to provide a baseline for the bridge behavior, and compare the behaviors of the two different spans. The stage 2 load test was comprised of incremental single truck, double truck side-by-side, triple truck side-by-side, and both single and double truck back-to-back load paths. Overall, the maximum measured strains for UHPC and HPC for both the stage 1 load test and stage 2 load test were similar. A few observations and conclusions from the load tests can be made:

  • The stage 1 and stage 2 load test results showed that the UHPC span experienced larger strains than the HPC span when loaded with a single truck. The combined effect of a smaller section modulus and an increased modulus of elasticity results in slightly larger expected strains in the UHPC span.

  • The stiffness (EI) of the UHPC girders was calculated to be 34% smaller than HPC for both edge and interior beams. However, the measured strains were similar between the two materials. This also may indicate that the estimated E may be overly conservative for the UHPC.

  • During the stage 1 and stage 2 load tests, the maximum measured strains for the UHPC and HPC spans did not exceed the expected strains. It is noted that the expected strains presented in this paper are based on the actual truck weights and positioned as measured during the tests. Prior to testing, the expected strains were based on estimated loads and the designed load paths (which were also not exceeded).

  • As more trucks were added during the stage 2 load test, more girders were engaged demonstrating better load distribution across the bridge. The distribution was achieved through the composite deck and shear keys between girders.

  • To ensure that no damage was done to the bridge during the load tests, the measured and expected strains were shown to not exceed the available strains that were calculated based on the AASHTO specifications for both tests. The maximum percentage of the available strains exhausted for the UHPC span was 40 and 34% for edge and interior girders, respectively. The maximum percentage of available strains exhausted for the HPC span was 31 and 30% for edge and interior girders, respectively.

  • The UHPC span experienced better live load distribution compared to the HPC span, validating the expected behavior based on the distribution factor presented in Table 2.

  • The use of load testing provides measured data to understand the behavior of the different concrete materials used in the bridge. Furthermore, the data can be compared to verify design procedures that incorporated the material properties of UHPC design and provide additional information for the introduction of UHPC into design codes. Based on the results from these load tests, non-proprietary UHPC can be effectively used in bridge construction with the following advantages: less material, equal or higher capacity with smaller girder cross-section, and more economical compared to proprietary products. The results also demonstrated that the introduction of UHPC into precast production was successful and the construction quality of the bridge was good.

  • The information collected from load tests provides essential information for the long-term performance study of the use of UHPC. Over the design-life of the bridge, the two spans can be observed to compare the difference in performance, particularly focusing on the durability and maintenance required. Additionally, future load tests can be utilized to monitor the long-term behavior of this new concrete material by comparing changes in behavior to the baseline data. As changes are observed, the data collected can also be used to guide inspections and denote key areas that require more detailed inspections.

Statements

Data availability statement

The data models, or code generated or used during the study are available from the corresponding author by request and upon approval from the New Mexico Department of Transportation.

Author contributions

All authors have contributed to the testing, data analysis, and writing of this paper.

Funding

This project was partially funded by NMDOT PROJECT NO. NM09MSC-01.

Acknowledgments

This research was funded in part by the New Mexico Department of Transportation (NMDOT), Project No. NM09MSC-01, Project Manager Virgil Valdez. Special thanks to the NMDOT District 1 personnel: Earl Franks and Benito Trevino and to the NMDOT load truck drivers that assisted with the load tests: Ernest Lascaun, J. D Moronez, Chris Maribal, Andrew McLaughlin, Charles Blanton, and Kenny McCoy. Additionally, the authors would like to acknowledge the support of the Saudi Arabia Ministry of Higher Education for providing student support. Any and all opinions, findings, conclusions, and/or recommendations expressed herein are those of the authors and do not necessarily reflect the views of the individuals or organizations listed above.

Conflict of interest

The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  • 1

    AASHTO (2000). Manual for Condition Evaluation of Bridges, 1994. Washington, DC: American Association of State Highway & Transportation Officials.

  • 2

    AASHTO (2012). American Association of State and Highway Transportation Officials (AASHTO) Load Resistance Factor Design (LRFD) Bridge Design Specifications. Washington, DC: American Association of State and Highway Transportation Officials.

  • 3

    ACI Committee (2011). Building Code Requirements for Structural Concrete (ACI 318-11) and Commentary. Farmington Hills, MI: American Concrete Institute.

  • 4

    AguilarC. V.JáureguiD. V.NewtsonC. M.WeldonB. D.CortezT. M. (2015). Load rating a prestressed concrete double T-beam bridge without plans by field testing. Transp. Res. Record J. Transp. Res. Board2522, 9099. 10.3141/2522-09

  • 5

    AguilarC. V.JáureguiD. V.WeldonB. D.NewtsonC. M. (2018). Rating of Prestressed Concrete Adjacent Beam Bridges Without Plans. Farmington Hills, MI: Special Publication, 323, 51.

  • 6

    AhlbornT. M.HarrisD. K.MissonD. L.PeuseE. J. (2011). Strength and durability characterization of ultra-high performance concrete under variable curing conditions, in Presented at 90th Annual Meeting of the Transportation Research Board (Washington, DC).

  • 7

    AlampalliS.KuninJ. (2003). Load testing of an FRP bridge deck on a truss bridge. Appl. Compos. Mater.10, 85102. 10.1023/A:1022885728627

  • 8

    AlampalliS.LundR. (2006). Estimating fatigue life of bridge components using measured strains. J. Bridge Eng.11, 725736. 10.1061/(ASCE)1084-0702(2006)11:6(725)

  • 9

    AllenaS. (2010). Ultra high strength concrete using local materials (Ph.D. dissertation), New Mexico State University, Las Cruces, NM, United States.

  • 10

    BrühwilerE.DenariéE. (2013). Rehabilitation and strengthening of concrete structures using ultra-high performance fibre reinforced concrete. Struct. Eng. Int.23, 450457. 10.2749/101686613X13627347100437

  • 11

    CaiH.AbudayyehO.Abdel-QaderI.AttanayakeU.BarberaJ.AlmaitaE. (2012). Bridge deck load testing using sensors and optical survey equipment. Adv. Civil Eng.2012:493983. 10.1155/2012/493983

  • 12

    CuaronA. M.JáureguiD. V.WeldonB. D. (2017). “Invited Student Paper- A Procedure for Load Rating Reinforced Concrete Slab Bridges without Plans (No. 17–01754), in Transportation Board 96th Annual Meeting (Washington, DC).

  • 13

    GieslerA. J.ApplegateS.WeldonB. (2016). Implementing, nonproprietary, ultra-high performance concrete in a precasting plant. PCI J.61, 6880.

  • 14

    GieslerA. J.McGinnisM. J.WeldonB. D. (2018). Flexural behavior and analysis of prestressed ultra-high-performance concrete beams made from locally available materials. PCI J.63, 6680.

  • 15

    GrabealB. A. (2006). Material Property Characterization of Ultra High Performance Concrete. FHWA-HRT-06-103, Turner-Fairbank Highway Research Center, McLean, VA.

  • 16

    GraybealB. A. (2008). UHPC in the US highway transportation system, in Proceedings of the Second International Symposium on Ultra High Performance Concrete (Kassel), 1117.

  • 17

    GraybealB. A. (2010). Behavior of Field-Cast Ultra-High Performance Concrete Bridge Deck Connections Under Cyclic and Static Structural Loading (No. FHWA-HRT-11-023). McLean, VA: Federal Highway Administration.

  • 18

    Hag-ElsafiO.AlampalliS.KuninJ. (2004). In-service evaluation of a reinforced concrete T- beam bridge FRP strengthening system. Compos. Struct.64, 179188. 10.1016/j.compstruct.2003.08.002

  • 19

    HajarZ.LecointreD.SimonA.PetitjeanJ. (2004). Design and construction of the world first ultra-high performance concrete road bridges, in Proceedings of the International Symposium on UHPC (Kassel), 3948.

  • 20

    HouT. C.LynchJ. P. (2006). Rapid-to-deploy wireless monitoring systems for static and dynamic load testing of bridges: validation on the grove street bridge, in Nonintrusive Inspection, Structures Monitoring, and Smart Systems for Homeland Security, Vol. 6178, eds DiazA. A.WuH. F.DoctorS. R.Bar-CohenY. (San Diego, CA: International Society for Optics and Photonics), 61780D.

  • 21

    KleinhansD. D.MyersJ. J.NanniA. (2007). Assessment of load transfer and load distribution in bridges utilizing FRP panels. J. Compos. Constr.11, 545552. 10.1061/(ASCE)1090-0268(2007)11:5(545)

  • 22

    LantsoghtE. O.van der VeenC.de BoerA.HordijkD. A. (2017). State-of-the-art on load testing of concrete bridges. Eng. Struct.150, 231241. 10.1016/j.engstruct.2017.07.050

  • 23

    LyellE. K. (2011). Optimization of Ultra High Performance Concrete Mixture Proportions Using Locally Available Materials. MS thesis, New Mexico State University, Las Cruces, NM.

  • 24

    ManglekarH. C.VisageE. T.RayT.WeldonB. D. (2016). Experimental and analytical investigations of a locally developed ultrahigh-performance fiber-reinforced concrete. J. Mater. Civil Eng.29:04016202. 10.1061/(ASCE)MT.1943-5533.0001732

  • 25

    ManningM. P.WeldonB. D.McGinnisM. J.JáureguiD. V.NewtsonC. M. (2016). Behavior comparison of prestressed channel girders from high-performance and ultrahigh-performance concrete. Transp. Res. Record J. Transp. Res. Board2577, 6068. 10.3141/2577-08

  • 26

    Muro-VillanuevaJ.NewtsonC. M.AllenaS.WeldonB. D.JaureguiD. V. (2012). Freezing and thawing durability of ultra high strength concrete, in International Congress on Durability of Concrete (Trondheim).

  • 27

    PharesB. M.WipfT. J.GreimannL. F.LeeY. (2005). Health Monitoring of Bridge Structures and Components Using Smart Structure Technology, Vol. 2. Washington DC: Wisconsin Highway Research Program.

  • 28

    RegaladoA.CarpenterB. A.JáureguiD. V.WeldonB. D. (2017). Performance evaluation of a reinforced concrete slab bridge retrofitted with carbon fiber reinforcement polymer laminate system. Transp. Res. Record J. Transp. Res. Board2642, 6876. 10.3141/2642-09

  • 29

    TaylorC. W.WeldonB. D.JáureguiD. V.NewtsonC. M. (2013). Case studies using ultrahigh-performance concrete for prestressed girder bridge design. Pract. Period. Struct. Design Constr, 18, 261267. 10.1061/(ASCE)SC.1943-5576.0000167

  • 30

    VisageE. T.WeldonB. D.JaureguiD. V.NewtsonC. M. (2019). Flexural performance of ultrahigh-performance concrete developed using local materials. J. Mater. Civil Eng.31:04019050. 10.1061/(ASCE)MT.1943-5533.0002683

  • 31

    VooY. L.FosterS. J.VooC. C. (2014). Ultrahigh-performance concrete segmental bridge technology: toward sustainable bridge construction. J. Bridge Eng.20:B5014001. 10.1061/(ASCE)BE.1943-5592.0000704

  • 32

    WeldonB.JaureguiD.NewtsonC.MontoyaK.TaylorC.AllenaS.et al. (2012). Feasibility Analysis of Ultra High Performance Concrete for Prestressed Concrete Bridge Applications – Phase II. NMDOT Report No. NM09MSC-01, New Mexico State University, Las Cruces, NM.

  • 33

    YuanJ.GraybealB. (2016). Full-scale testing of shear key details for precast concrete box-beam bridges. J. Bridge Eng.21:04016043. 10.1061/(ASCE)BE.1943-5592.0000906

Summary

Keywords

diagnostic load test, ultra-high performance concrete, high performance concrete, strain measurement, load distribution

Citation

Alahmari TS, Kennedy CS, Cuaron AM, Weldon BD and Jáuregui DV (2019) Field Testing of a Prestressed Concrete Bridge With High Performance and Locally Developed Ultra-High Performance Concrete Girders. Front. Built Environ. 5:114. doi: 10.3389/fbuil.2019.00114

Received

16 February 2019

Accepted

19 September 2019

Published

04 October 2019

Volume

5 - 2019

Edited by

Joan Ramon Casas, Universitat Politecnica de Catalunya, Spain

Reviewed by

Devin K. Harris, University of Virginia, United States; Fernando Rebouças Stucchi, University of São Paulo, Brazil

Updates

Copyright

*Correspondence: Turki S. Alahmari

This article was submitted to Bridge Engineering, a section of the journal Frontiers in Built Environment

Disclaimer

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.

Outline

Figures

Cite article

Copy to clipboard


Export citation file


Share article

Article metrics