Abstract
This study provides a theoretical and practical assessment of the potential benefits of live data streams, as used in digital twins, relating to a building’s running cost and carbon emissions. This is a significant issue, as there is a rise in the demand of digital twins and smart buildings in industry, and the energy savings that could be achieved should be assessed, as it relates to building automation and function. The study considers theoretical assessments based on existing standards and practical assessments on university buildings in London, United Kingdom and New Haven, Connecticut, United States, and is particularly focused on how data-driven controls can improve the energy efficiency of the buildings considered. Using data from the building’s building management systems and energy monitoring software, operational building data analysis was carried out on buildings in London and New Haven. Informed by the studies of both buildings, an assessment against ISO 52120-1:2021 was carried out for the existing building in New Haven, and a planned new university complex in New Haven. The comparative study between the London and New Haven building found that 29% of noteworthy cases identified for the London building were also observed in New Haven. The most significant energy saving opportunities, such as signs of overcooling and not adhering to scheduled shutdowns, were found to be present in both buildings. From a baseline state of low building automation, three states of increasing Building Automation and Control capability were defined as “must have”, “should have”, and “could have”. The mean expected energy savings for these were 5%, 7%, and 9% respectively. The implications of this study are that energy savings can be achieved in existing and planned education buildings, and that opportunities can be identified using enhanced building automation described in ISO 52120-1:2021. It also highlights the challenges with using ISO 52120 to fully quantify the energy savings due to enhanced automation and live data streams, especially for buildings with laboratory areas, which are not covered by ISO 52120, and which typically make up a much higher proportion of a building’s energy footprint than office areas.
1 Introduction
Digital twins in the built environment are seen to be at an early stage in their development (Schweigkofler et al., 2022; ), and their use is increasing rapidly (). This will be associated with a rapid increase in live data streams and the associated processing and storage of data (Wright and Davidson, 2020). This could lead to benefits for the environment, building occupants, and building managers (; Shahzad et al., 2022; ), with the potential for improved energy efficiency identified as a key benefit (). However, there are indications that 90% of sensor data from the internet of things and 80% of all digital data is never used (McGovern, 2020; Rogers and Kirwan, 2019; ). This is a large cost, when considering that total global carbon emissions from data transmission and storage are estimated at 97 million tonnes of CO2e per year (Obringer et al., 2021). At the time of writing, this is greater than the total estimated carbon footprint of Chile. In light of this, guiding principles for developing digital twins in the built environment such as the Gemini principles () exist. These provide a framework for developing digital twins that provide a clear purport and public good.
The assessment of energy-saving potential for live data streams should also be considered in the wider context of active and passive energy-saving measures. This includes effective use of atriums to minimise thermal energy consumption (Vujošević and Krstić-Furundžić, 2017; ; Wang et al., 2017), with Vujošević and Krstić-Furundžić finding that buildings with a glass atrium could reduce heating demands by 30% in other areas of the building (Vujošević and Krstić-Furundžić, 2017). Ventilation design to enable gravity assisted ventilation can also be used to maximise passive cooling and ventilation (Nakielska and Pawłowski, 2017; ). Other effective passive energy saving measures include the use of night cooling (Solgi et al., 2018), thermal inertia (; Rugani et al., 2021), and ground energy (; Panão and Gonçalves, 2011). Existing active energy saving measures include thermal storage systems (), heat recovery (Vakiloroaya et al., 2014) and predictive control (Xue et al., 2023).
Existing studies have assessed the utility of live data streams in buildings, for example, Maltese et al. (2021) have shown how live data in office buildings can be used to reduce running costs and improve occupant productivity and space utilisation. Schweigkofler et al. have also shown how live data streams are used in digital twin to engage occupants with facilities and energy management for a school building (Schweigkofler et al., 2022). Existing literature has shown ISO 52120 as a method for assessing gains from enhanced building automation, including modelling of the Building Automation and Control Systems classes in the standard (), assessing benefits from improved automation in heating (Morkunaite et al., 2022) and designing an automated control system for improved thermal performance (Montalbán Pozas et al., 2023). The present study builds on the existing literature to assess the benefits of live data streams through ISO 52120 assessments for existing buildings and a planned new development, informed by operational data.
Considering the potential benefits of live data streams mentioned, and the costs of harvesting, storing, and analysing this data, an assessment of quantitative potential digital twin benefits is needed (). The work presented provides a case study to contribute towards addressing this need by calculating the potential benefits of live data streams in digital twins and feeds back learning from operational data from existing buildings into the design stage for new building projects. First, operational data from two university buildings, one of which is situated in London, UK and another in New Haven, Connecticut, USA is assessed. The London building is University College London (UCL) East One Pool Street (UCL 2018a), and the New Haven building is Yale University’s Becton Engineering and Applied Science Center (BCT) (Yale University, 2021). One Pool Street and the BCT are shown in Figures 1, 2 respectively.
FIGURE 1
FIGURE 2
Based on an analysis of the operational data and building control manuals, the BCT and a planned new development for the Yale School of Engineering and Applied Science (SEAS) on Hillhouse Avenue (Yale University, 2023) were assessed against the ISO 52120-1:2021 standard (), to provide an indication of energy savings that could be achieved using greater levels of Building Automation and Control (BAC). Using the ISO 52120 standard covers the use of active energy saving measures, including demand driven heating and cooling, and passive techniques including use of free cooling. This assessment gave rise to a series of possible development pathways for the new SEAS development on Hillhouse Avenue. These are provided in this paper as “must have”, “should have”, and “could have” pathways, with the potential utility of each pathway considered.
2 Methods
This study assessing the utility of live data streams is based on a data harvesting and analysis project at One Pool Street. This section describes the methods used in this study, and the following studies at Yale University. These include the operational data assessment at BCT, ISO 52120 assessment at BCT, and the ISO 52120 assessments for the planned development on Hillhouse Avenue. The method used intentionally covers operational data for existing buildings and a theoretical assessment of a planned new development. This is to provide a real-world picture of building automation and controls as well as assessing which technologies work best in practice to feedback to new buildings at the design stage.
2.1 UCL East One Pool Street harvesting and analysis of live data streams
One Pool Street operational data is made available through campus wide instances of Schneider Ecostruxure Building Operation (Schneider, 2022) and Schneider EcoStruxure Power Monitoring Expert (Schneider Electric 2024b). A data harvesting solution was implemented using MQTT (MQTT, 2022), with data storage carried out in InfluxDB (), and data visualisation achieved in Grafana (Grafana Labs, 2024). Harvested operational data included room temperature, CO2 concentration, thermal energy consumption, electricity consumption, Heating, Ventilation, and Air Conditioning (HVAC) operating parameters, and occupancy (from passive infrared sensors). The list of parameters harvested for this study is provided in Tables 3, 4.
Grafana data visualisations are analysed manually to identify cases that could save energy or improve operations. For example, spaces were being actively cooled to 21°C in summer months, even though it is university policy for spaces not to be cooled below 25°C. This case will be discussed in more detail in
Section 3.1. Potential cases that affect occupant comfort were also identified. These include chiller outages that caused room temperatures above 29°C in occupied rooms, and up to 34°C in a room that houses a computer cluster. The cases observed were used to support engagement with building stakeholders, and formed the basis for the assessments made for existing and planned university buildings at Yale University described in
Sections 2.3,
2.4. The opportunities identified that offered the largest potential energy savings were:
• Increasing the cooling setpoint from 21°C to 25°C to bring this in line with the UCL heating and cooling policy (UCL 2018b).
• Turning off ventilation over shutdown periods and weekends.
• Reducing the return temperature from the building’s hot water circuit to the district heating system in line with the design values to maintain the intended temperature difference across the hot water circuit.
This study aims to compare these cases with improvements suggested in ISO 52120 () (see Sections 2.3, 2.4), to identify alignment for the buildings considered.
The key building parameters as it pertains to energy consumption for UCL East One Pool Street are provided in Table 1.
TABLE 1
| Parameter | Value |
|---|---|
| Measured annual energy consumption (November 2023 – October 2024). This includes electricity and low temperature hot water provided by district heating (chilled water is provided by an electrical chiller on site) | 5,050 MWh |
| Total floor area | 20,000 m2 |
| Energy use intensity | 253 kWh/m2/year |
| Main heating source | District heating |
| Shape coefficient | 0.36 |
Energy performance parameters for UCL East One Pool Street.
2.2 Becton Engineering Center operational data analysis
The study of live data at the BCT seeks to understand whether the same cases arise in this university building in New Haven, USA, as were present in the UCL East One Pool Street case study. Trend data from Johnson Controls Metasys (), Fault Detection and Diagnostics data from Clockworks analytics (), and energy data from the Facilities Energy Usage Explorer (Yale University, 2024) were used to assess each of the 40 cases identified in the One Pool Street case study, and an assessment was made as to whether they existed at the BCT. Data for comparison was not available for all cases. For example, Yale University does not have the same building shutdown at Easter that exists at UCL. The understanding of the building systems and the trends in the harvested operational data fed directly into the ISO 52120 assessments described in Sections 2.3, 2.4.
The key building parameters as it pertains to energy consumption for the Becton Engineering Center are provided in Table 2.
TABLE 2
| Parameter | Value |
|---|---|
| Measured annual energy consumption (November 2023 – October 2024). This includes electricity, steam, and chilled water provided by a central power plant | 13,500 MWh |
| Total floor area | 13,500 m2 |
| Energy use intensity | 1,000 kWh/m2/year |
| Main heating source | District heating |
| Shape coefficient | 0.17 |
Energy performance parameters for the Becton Engineering Center.
A description of the of data harvested at One Pool Street and the BCT is provided in Tables 3, 4 respectively.
TABLE 3
| Data type | Sensor or system used | Sensor location | Zoning |
|---|---|---|---|
| Temperature | Schneider Smart X room sensor (Schneider Electric, 2020) | Wall | Multiple sensors per room |
| CO2 concentration | Schneider Smart X room sensor (Schneider Electric, 2020) | Wall | Multiple sensors per room |
| Occupancy (Binary output) | Passive infrared | ceiling | Room level |
| Thermal energy consumption | Kamstrup Multical 403 heat meter () | District heating system inlet | Building level |
| Building level electricity consumption | Schneider Electric Micrologic 6.0 X control unit (Schneider Electric 2024c) | Incoming power from the electricity grid | Building level |
| Thermal energy consumption | Kamstrup Multical 403 heat meter () | Secondary low temperature hot water pumps for the podium and residential towers | Zone level |
| Equipment level electricity consumption | Schneider Electric Micrologic 6.0 X control unit (Schneider Electric 2024c) | Low voltage distribution boards | Equipment level |
| Chilled and hot water network temperatures | STP500 pipe temperature sensor (Schneider Electric 2024a) | Throughout chilled and hot water distribution network | Equipment level |
| HVAC system pressures | EP Series Differential Pressure sensor (Schneider, 2024) | HVAC ducts | Zone level |
| HVAC system temperatures | STP500 pipe temperature sensor (Schneider Electric 2024a) | HVAC ducts | Zone level |
| HVAC system valve positions | Danfoss AB-QM control valves | Air handling units, fan coil units, variable air volumes | Zone level |
| HVAC equipment on/off state | Danfoss AB-QM control valves | Air handling units, fan coil units, variable air volumes | Zone level |
Detailed description of sensor data for UCL East One Pool Street.
TABLE 4
| Data type | Sensor or system used | Sensor location | Zoning |
|---|---|---|---|
| Temperature | Johnson Controls NS-BTB7002-0 temperature sensor | Wall | Room level |
| CO2 concentration | Johnson Controls NS-BCN7004-0 CO2 sensor | Wall | Room level |
| Occupancy (Binary output) | Dry contact passive infrared occupancy sensor | Ceiling | Room level |
| Building level thermal energy consumption | Yale energy explorer (Yale University, 2024) | Plant room | Building level |
| Building level electricity consumption | Yale energy explorer (Yale University, 2024) | Plant room | Building level |
| Chilled and hot water network temperatures | Johnson Controls TE-63xS Series Strap-Mount Temperature Sensors | Throughout chilled and hot water distribution network | Equipment level |
| HVAC system pressures | Johnson Controls DPT2641-005D-1 pressure transducer | HVAC ducts | Zone level |
| HVAC system temperatures | Johnson Controls NS-BTB7002-0 temperature sensor | HVAC ducts | Zone level |
| HVAC system valve positions | Belimo pressure independent control valves | Air handling units, fan coil units, variable air volumes | Zone level |
| HVAC equipment on/off state | Belimo pressure independent control valves | Air handling units, fan coil units, variable air volumes | Zone level |
Detailed description of sensor data for the BCT.
2.3 Becton Engineering Center data-driven control assessment
In addition to the studies on operational data, an assessment against the ISO 52120-1:2021 standard (), that covers the contribution of building automation to the energy performance of buildings, was carried out for the BCT. The standard describes detailed requirements for using sensor data to drive automated building control and provides quantitative metrics that these data-driven controls have on the energy performance of buildings. The Siemens EPC-Tool web interface was used to carry out the assessment against ISO 52120 (Siemens, 2022). The building control manuals for the BCT were used to complete the assessment, as well as the results from the BCT operational data analysis described in section 2.3. The building classification is carried out for an office building, since the spaces in the BCT that are not laboratory spaces are office spaces, and there is no distinction in ISO 52120 for laboratory spaces. The overall BAC classification was used, since this allowed for the most granular level of input, covering 45 functions across heating, hot water, cooling, ventilation/air conditioning, lighting, blinds, and technical building management. The requirements to meet each classification are minimum requirements, meaning that if one control element is rated as “D”, then the BAC class of that building is D.
2.4 Hillhouse Avenue data-driven control assessment
Based on the BCT ISO 52120 assessment, and available proposal documents from the architects and engineers for the new development at Hillhouse Avenue, an ISO 52120 assessment was made for the new development. The classification process is as described for the BCT in
section 2.3. For the Hillhouse Avenue assessment, the requirements to move to a BAC class C, B, and A from a “do nothing” state were identified. The requirements to meet class C are defined as “must have”, to meet class B are defined as “should have”, and to meet class A are defined as “could have” requirements. Energy modelling results from design proposals were used to estimate energy savings for each state, considering that the savings defined in ISO 52120 would only be for the office portion of the new development. The assumptions made in assessing the expected energy consumption for each state were:
• A gross floor area of 30,000 m2.
• 40% of the planned new development is laboratory space, and the rest is office space.
• An Energy Use Intensity (EUI) of 315.5–378.6 kWh/m2/yr as calculated using energy modelling.
• An increased energy consumption factor of laboratory spaces of 5-10 times compared to an office space ().
• The EUI and increased energy consumption factor of laboratory spaces are normally distributed.
• The EUI calculated in energy modelling assumes a standard class BAC and therefore corresponds to BAC class C.
• Since the planned new development is fully electrified, BAC factors for thermal energy correspond to the electricity used for Domestic Hot Water (DHW), cooling, heating, and humidification, whereas BAC factors for electrical energy are applied to HVAC systems such as pumps and fans, and equipment that uses electricity. As shown in Figure 3, this means that thermal BAC factors were applied to 54% of energy consumption, and electrical BAC factors were applied to 46% of energy consumption.
FIGURE 3
These assumptions show that the new building is similar in function to existing buildings, especially considering the distribution of lab and office space is similar to the Becton Engineering Center. It is the largest of the buildings considered, with the BCT having a gross floor area of approximately 13,500 m2 and One Pool Street 20,000 m2. Using the assumptions listed in this section, the total expected building energy consumption for the planned new development were calculated for the inputs that would result in the minimum, mean, and maximum expected energy savings from improved use data-driven control. The analysis of operational building data (see section 2.1 and 2.2) was used to classify the BAC level for the planned new development.
2.4.1 Energy savings calculation
ISO 52120 overall BACS factors were used in the present study. The formula for calculating total energy consumption for thermal and electrical energy is shown in Equations 1, 2 ().
Equation 1 – Formula used to calculate thermal energy consumption with improved building automation control ()
Where:
is the total calculated thermal energy consumption for the building related to the new BAC efficiency class
is the total thermal energy consumption for the building for the reference BAC efficiency class
is the thermal BAC efficiency factor for the new BAC class
is the thermal BAC efficiency factor for the reference BAC class.
Equation 2 - formula used to calculate electrical energy consumption with improved building automation control ()
is the total calculated electrical energy consumption for the building related to the new BAC efficiency class
is the total electrical energy consumption for the building for the reference BAC efficiency class
is the electrical BAC efficiency factor for the new BAC class
is the electrical BAC efficiency factor for the reference BAC class.
The BAC efficiency factors for thermal energy are 1.51 for class D, one for class C, 0.80 for class B, and 0.70 for class A.
The BAC efficiency factors for electrical energy are 1.10 for class D, one for class C, 0.93 for class B, and 0.87 for class A.
3 Results
Results for the operational data assessment are shown in Section 3.1, and results for the ISO 52120 assessments, and the associated energy implications are shown in Sections 3.2–3.4.
3.1 Becton Engineering Center operational data analysis and comparison to One Pool Street
The results from the comparison of operational data between One Pool Street and the BCT are shown in Figure 4.
FIGURE 4
As mentioned in section, the reason that data for comparison was not available for all cases observed at One Pool Street was because of a difference in data harvesting architecture available at the BCT, for example, the lack of electrical submetering for equipment. In both buildings, it was observed that equipment was left running over the Christmas shutdown period. There were however differences in how this came about. At One Pool Street, there was no process for shutting down equipment over Christmas, so it was not turned off. At Yale University, all buildings are shut down over Christmas by default, and staff members can notify facilities if their specific area will be occupied or in use, in which case equipment is left running for that area.
At both sites, there was a large increase in cooling energy used over summer months, with zone temperatures below the defined setpoints for both university buildings.
The setpoint defined by UCL’s cooling policy (UCL 2018b) is 25°C, and the mean recommended cooling setpoint defined by Yale University is 75°F (23.9°C). The zone temperatures observed in both buildings, along with the recommended setpoints can be seen in Figures 5, 6, which show the outdoor and indoor air temperature for One Pool Street, and the BCT respectively.
FIGURE 5
FIGURE 6
In the One Pool Street case (see Figure 5), the low cooling setpoint of 21°C resulted in complaints from occupants who were used to warm weather, whereas discussions with staff at Yale indicated that occupants desired colder zone temperatures.
3.2 Becton Engineering Center ISO 52120-1:2022 assessment
The results of the ISO 52120 assessment, based on the learning from the operational data assessment at the BCT, surveying the building’s facilities, and the contents of the manual. The results are shown in Figure 7.
FIGURE 7
As shown in Figure 7, only 18% of the functions were assessed as BAC class D. Since the requirements in ISO52120 are minimum requirements, this means that the overall rating for the BCT is currently a D, but the BAC class could be improved by upgrading a small portion of BAC functions. Figure 8 shows a breakdown of classifications by the ISO 52120 they fall under.
FIGURE 8
Figure 8 shows that the highest number of D rated functions are in cooling and ventilation/air conditioning. Within cooling, two of the D rated functions were because the temperature control of the cold-water distribution network and chillers was based on a constant temperature control. Upgrading these to a control that compensates for outside temperature would upgrade these classifications.
3.3 Hillhouse Avenue ISO 52120-1:2022 assessment
The learnings from the assessment of building automation and controls were carried through to an assessment of the design proposals for Hillhouse Avenue. This provided sufficient confidence that the level of building automation control would be at least as good as it is in the BCT. Therefore, as a worst-case scenario, BAC classes were assumed to be the same as at the BCT. Additionally, the proposals explained that occupancy control would be used for all systems, which meant that BAC ratings for functions 1.1, 3.1, and 5.1 improved to an A rating, and 4.1 improved to a B rating. Heat pumps, and heat recovery will be used in the new development, where these were not used in the BCT. The BAC classes for these technologies were assigned in line with the classes observed at the BCT. This means that functions 1.7 (Heat generator control (heat pump)) (class C), 2.1 (Control of Domestic hot water storage temperature with integrated electric heating or electric heat pump) (class C), 2.2 (Control of Domestic hot water storage temperature using heating water generation, 4.6 (Heat recovery control (icing protection)) (class D), and 4.7 (Heat recovery control (prevention of overheating)) (class D) were included in the Hillhouse ISO 52120 assessment.
From the baseline state, improved states of building automation and control were defined for the new development. These were defined as “must have”, “should have”, and “could have” states, and correspond to BAC classifications C, B, and A respectively. Table 5 provides a summary of the improved states.
TABLE 5
| State | BAC classification | Notes |
|---|---|---|
| Baseline | D | Baseline state |
| Must have | C | The main benefits of the “must have” improvements are a likely increase in the mean flow temperature of the cooling circuit, minimising the chance and amount of simultaneous heating and cooling, and optimising the use of freely heating and cooling, available from the outdoor environment and pre-conditioned air () |
| Should have | B | The “should have” improvements provide better temperature control in the local and district heating and cooling supply circuits, prioritise more efficient cooling sources depending on demand, and minimise energy demand by co-ordinating control across all heat sources. Additional benefits are obtained by making use of free cooling and co-ordinating lighting to available daylight to minimise energy used in lighting () |
| Could have | A | The “could have” improvements enable shorter heating and cooling operation time, energy saving based on daylight intensity, total elimination of simultaneous heating and cooling, optimised use of free cooling and heating and control that matches demand as close as possible () |
Summary of improvements for “must have”, “should have”, and “could have” states.
3.4 Energy implications of suggested BAC improvements
ISO 52120 () provides efficiency factors. As described in section 2.4, these were used to estimate the energy consumption reductions that are expected if the recommendations described in section 3.3 are implemented. Figures 9, 10 show the expected total energy consumption and the expected energy savings for each state respectively.
FIGURE 9
FIGURE 10
The results shown in Figures 9, 10 should be viewed with consideration for the assumptions listed in section 2.4, which provide the baseline for the savings and uncertainties shown.
4 Discussion
The comparative study of operational data between the London and New Haven university buildings focussed on 28 cases that were chosen from live data streams. Of these 28 cases, nine were also observed in the New Haven building. This shows that ∼70% of cases were not transferrable between the two buildings. However, the two cases that were deemed to have the highest potential energy savings in the London building were also observed in New Haven. The significant differences in cases across the two buildings highlights the need for skilled facilities managers who understand the building they are managing and can take actions tailored to it. However, sharing key similarities also shows the benefits of data-driven methods as tools to aid managers in operating, maintaining, and improving buildings that are optimised for energy efficiency and occupant comfort.
As mentioned in Section 2.1, the greatest energy saving opportunities identified from operational data at UCL East One Pool Street were to increase the cooling setpoint, turn off ventilation when it is not needed, and reduce the hot water exit temperature. Considering the ventilation, the improvements suggested in ISO 52120 would help to address this opportunity, since the higher BAC classifications improve a building’s ability to tailor equipment operation to occupancy. Similarly, ISO 52120 functions 1.3 and 3.4 control the flow temperature of the hot water and cold water distribution networks respectively. This means that the hot water exit temperature from the system could be optimised using higher levels of building automation and control. The cooling setpoint adjustment, however, requires an understanding of local policies, which would not be addressed by improving BAC functionality alone. In One Pool Street, the overcooling was caused by having a setpoint of 21°C for the entire year, with no modification for winter and summer months. With regards to this, understanding the impacts of adjusting the setpoint on occupant comfort is also important. As seen in the present case, for example, the low setpoint at UCL caused occupants to complain that they are cold in addition to using more energy, whereas occupants at Yale University indicated that they enjoyed the lower cooling setpoint. Overcooling is a wider issue observed in the literature, a study into overcooling in commercial buildings in the US, for example, found that overcooling alone represents an 8% energy loss on average across the country ().
The results from the ISO 52120 assessments have shown that some energy savings can be made from enhanced building automation, with 5% energy savings across the entire new development project achievable for the most basic improvements, and 9% for the most complete building automation enhancements. This shows that where it is cost effective to make improvements to building automation, these should be implemented. This in turn shows the necessity of future work to assess the costs of the enhanced automation proposed in ISO 52120.
Comparing the results from this study to existing studies that assess the impact of improved automation, the achieved results are conservative, with results showing savings of up to 31.6% (Yin and Mohamed, 2023) of energy used for electric heating, and savings from smart control of lighting between 40%-70% (Mahdavi et al., 2008; Roisin et al., 2008; Yun et al., 2012). This conservativeness shows gives confidence in the savings presented in this study being lower than what would be achieved for the proposed new Hillhouse Avenue development. It is likely that the cause of this conservativeness is the exception of laboratory areas (see Section 5).
Whilst ISO 52120 () provides an excellent tool for assessing the technological capability of a BAC system, and defining the technologies that should be installed in a building, it lacks detail in how this technology should be implemented. The ASHRAE 36 guideline, High-Performance Sequences of Operation for HVAC Systems () provides an excellent resource for this, and should be used in conjunction with the recommendations found in this study to maximise savings in energy consumption.
5 Limitations
As can be seen in Section 3.1, there was not scope in this paper to provide a detailed description of every improvement opportunity identified at One Pool Street and the BCT. The results summary was included however, as the assessment helped to provide a solid understanding of BCT controls to carry out ISO 52120 assessments, and to be able to understand similarities and differences in the utility of live data streams across different geographies and cultures. Future work should provide a detailed assessment of each case found, and provide a benefit assessment based on operational data, to allow for comparison against the energy savings calculated using an ISO 52120 assessment provided in this paper. It should be noted that the building management system sensors used to obtain operational data typically have lower accuracies than newly calibrated stand-alone temperature sensors ().
An important limitation is the uncertainty associated with energy savings from ISO 52120 assessments for the Hillhouse Avenue project. The greatest source of this is the lack of detailed understanding of the energy consumption of the lab spaces at the BCT and Hillhouse Avenue. Since ISO 52120 does not provide guidance on laboratory applications, it was assumed that no energy savings from improved controls could be made for laboratory spaces, and it was estimated that these made up the greatest proportion of the building’s energy consumption (between 77% and 87%). Therefore, future work should seek to address laboratory use to understand the savings that could be obtained using the control strategies described in this report, and to develop a control strategy tailored to minimising energy consumption in laboratories.
It should be noted that the baseline assessment for the planned development at Hillhouse Avenue (Section 3.3) is a worst-case assessment. This was done intentionally, to ensure that no potential improvement opportunities could be missed. However, it is likely that a lot of the functionality listed in the “Must”, “Should”, and “Could” states would be incorporated into the building, but have not been included in plans at such an early stage. Future work should be done to understand which features would be included in the building without any intervention, and what the value of the remaining improvements would be.
6 Conclusion
This study has provided some progress towards addressing the need for tools and real case study examples to assess the benefits of digital twins in the built environment, by quantifying the potential benefits of live data streams in existing and future buildings. The results showed that the mean reduced energy consumption for a planned new university building in New Haven, Connecticut were 5%, 7%, and 9% for three increasing levels of improved building automation control. A comparative study between university buildings in London and New Haven found that 71% of noteworthy cases identified for the London building were not observed in New Haven, but signs of overcooling and not adhering to scheduled shutdowns were observed in both buildings.
Additional work is needed to assess the costs of implementing the data acquisition and data-driven control strategies described in this study and to assess additional benefits of live data streams, including dynamically updating building models. Future work should also consider the impact of data-driven buildings on laboratory buildings, especially as potential energy savings could be greater than for offices.
Statements
Data availability statement
The datasets presented in this article are not readily available because the raw data for this study is privately held and owned by Yale University and University College London. Requests for data sharing can be directed to the corresponding author and may be granted subject to approval by the data holders. Requests to access the datasets should be directed to William.Markiewicz.21@ucl.ac.uk.
Author contributions
WM: Writing–original draft, Writing–review and editing. VW: Writing–review and editing. JD: Writing–review and editing. DW: Writing–review and editing. CE: Writing–review and editing.
Funding
The author(s) declare that financial support was received for the research, authorship, and/or publication of this article. This research has been funded by the Engineering and Physical Sciences Research Council under Grant EP/S021671/1 and Ove Arup and Partners Limited.
Acknowledgments
This study would not have been possible without Julie Paquette, Mike Ghilani, and Ed Lipsett from the Yale Office of Facilities. They provided access to the data needed to carry out this research, and their experience with the building controls at the Becton Engineering Centre was invaluable in supporting the ISO 52120 assessments and analysing operational data from the building. The authors are also very grateful to David Kelley, Senior Director of Capital Program Development and Delivery at Yale, especially for his help in defining requirements for collecting operational data and for his help in analysing the result from this. The authors are also very grateful to Darren Wright, director of Arup’s built environment team, especially for his guidance in collecting and interpreting operational data from UCL East One Pool Street.
Conflict of interest
The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.
Generative AI statement
The author(s) declare that no Generative AI was used in the creation of this manuscript.
Publisher’s note
All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.
References
1
Active Archive (2018). Active archive and the state of the industry 2018. Available at: https://activearchive.com/wp-content/uploads/2018/04/Active-Archive-and-the-State-of-the-Industry-2018_Final.pdf.
2
AlbesianoM. (2023). BACS: energy performance and technical-economic analysis of HVAC technologies. Politecnico di Torino: Laurea. Available at: https://webthesis.biblio.polito.it/26443/.
3
AldawoudA. (2013). The influence of the atrium geometry on the building energy performance. Energy Build.57 (February), 1–5. 10.1016/j.enbuild.2012.10.038
4
ASHRAE (2021). Guideline 36-2021 -- high-performance Sequences of operation for HVAC systems. Available at: https://store.accuristech.com/ashrae/standards/guideline-36-2021-high-performance-sequences-of-operation-for-hvac-systems?product_id=2229690.
5
BaeY.BhattacharyaS.CuiB.LeeS.LiY.ZhangL.et al (2021). Sensor impacts on building and HVAC controls: a critical review for building energy performance. Adv. Appl. Energy4 (November), 100068. 10.1016/j.adapen.2021.100068
6
BojeC.GuerrieroA.KubickiS.RezguiY. (2020). Towards a semantic construction digital twin: directions for future research. Automation Constr.114 (June), 103179. 10.1016/j.autcon.2020.103179
7
BoltonA.EnzerM.SchoolingJ. (2019). The Gemini principles: guiding values for the national digital twin and information management framework. Cambridge, United Kingdom: Centre for Digital Built Britain. Available at: https://www.cdbb.cam.ac.uk/DFTG/GeminiPrinciples.
8
Clockworks Analytics (2024). Clockworks analytics. Clockworks Anal.Available at: https://clockworksanalytics.com/.
9
DemianP.YeomansS.Murgula-SanchezD. (2018). Network FOuNTAIN A cdbb network: for onTologies and Information maNagement in digital built britain: final report. Text. Available at: https://www.cdbb.cam.ac.uk/CDBBResearchBridgehead/Networks/2018Network_FOuNTAIN.
10
DengM.MenassaC. C.KamatV. R. (2021). From bim to digital twins: a systematic review of the evolution of intelligent building representations in the AEC-FM industry. J. Inf. Technol. Constr. (ITcon)26 (5), 58–83. 10.36680/j.itcon.2021.005
11
DerribleS.ReederM. (2015). The cost of over-cooling commercial buildings in the United States. Energy Build.108 (December), 304–306. 10.1016/j.enbuild.2015.09.022
12
D’OrazioM.Di PernaC.Di GiuseppeE. (2014). A field study of thermal inertia of roofs and its influence on indoor comfort. J. Build. Phys.38 (1), 50–65. SAGE Publications Ltd STM. 10.1177/1744259113480134
13
EPA (2008). Laboratories for the 21st century: an introduction to low-energy design. Available at: https://www.nrel.gov/docs/fy08osti/29413.pdf.
14
Gil-BaezM.Barrios-PaduraÁ.Molina-HuelvaM.ChacarteguiR. (2017). Natural ventilation systems in 21st-century for near zero energy school buildings. Energy137 (October), 1186–1200. 10.1016/j.energy.2017.05.188
15
GondalI. A. (2021). Prospects of shallow geothermal systems in HVAC for NZEB. Energy Built Environ.2 (4), 425–435. 10.1016/j.enbenv.2020.09.007
16
Grafana Labs (2024). Grafana: the open observability platform. Grafana Labs. Available at: https://grafana.com/.
17
HalmetojaE. (2022). “The role of digital twins and their application for the built environment,” in Industry 4.0 for the built environment: methodologies, technologies and skills. Editors BolpagniM.GavinaR.RibeiroD. (Cham: Springer International Publishing), 415–442. 10.1007/978-3-030-82430-3_18
18
Hernández-MoralG.Mulero-PalenciaS.Serna-GonzálezV. I.Rodríguez-AlonsoC.Sanz-JimenoR.MarinakisV.et al (2021). 14. Big data value chain: multiple perspectives for the built environment. Multidiscip. Digit. Publ. Inst., 4624. 10.3390/en14154624
19
InfluxData (2022). InfluxDB | real-time insights at any scale. InfluxData. Available at: https://www.influxdata.com/home/.
20
ISO (2021). ISO 52120-1:2021’. ISO 52120-1:2021 energy Performance of buildings — Contribution of building automation. Geneva, Switzerland: International Standards Organisation. Available at: https://www.iso.org/standard/65883.html.
21
Johnson Controls (2024). Metasys software and servers. Available at: https://www.johnsoncontrols.com/building-automation-and-controls/building-automation-systems-bas/metasys-software-and-servers.
22
Kamstrup (2023). MULTICAL® 403 | the most flexible ultrasonic heat meter available. Available at: https://www.kamstrup.com/en-en/heat-solutions/meters-devices/meters/multical-403.
23
KetzlerB.NaserentinV.LatinoF.ZangelidisC.ThuvanderL.LoggA. (2020). Digital twins for cities: a state of the art review. Built Environ.46 (4), 547–573. 10.2148/benv.46.4.547
24
KimN.-K.ShimM.-H.WonD. (2018). Building energy management strategy using an HVAC system and energy storage system. Multidiscip. Digit. Publ. Inst.11, 2690. 10.3390/en11102690
25
MahdaviA.MohammadiA.KabirE.LambevaL. (2008). 1. Occupants operation of lighting and shading systems in office buildingsJ. Build. Perform. Simul., 57–65. 10.1080/19401490801906502
26
MalteseS.AltieriD.BrancaG.MarvinD. (2021). BIM+IoT for office spaces optimisation. Lugano, 1–4. Available at: https://repository.supsi.ch/13071.
27
McGovernG. (2020). World wide waste. Silver Beach. Available at: https://gerrymcgovern.com/world-wide-waste/.
28
Montalbán PozasB.Bustos García de CastroP.Lucas BonillaM.Serrano CandelaF. (2023). A methodology for designing an automated system to improve the thermal performance of a large building in operation. Buildings13 (8). 1938. 10.3390/buildings13081938
29
MorkunaiteL.PupeikisD.JurelionisA.FokaidesP. A.PapadopoulosA. (2022). An analytical model for the impact of building control and automation upgrade on space heating energy efficiency. Multidiscip. Digit. Publ. Inst., 12, 1074. 10.3390/buildings12081074
30
MQTT (2022). MQTT - the standard for IoT messaging. Available at: https://mqtt.org/.
31
NakielskaM.PawłowskiK. (2017). “Enhancement of gravity ventilation in buildings,” in Proccedings of 10th international conference ‘environmental engineering’. Vilnius gediminas technical university, Lithuania: VGTU technika. 10.3846/enviro.2017.269
32
ObringerR.RachunokB.Maia-SilvaD.ArbabzadehM.NateghiR.MadaniK. (2021). The overlooked environmental footprint of increasing internet use. Resour. Conservation Recycl.167 (April), 105389. 10.1016/j.resconrec.2020.105389
33
PanãoM. J. O.GonçalvesH. (2011). Methodological development of sesonal cooling energy needs by introducing ground-cooling systems. Available at: https://www.semanticscholar.org/paper/Methodological-development-of-sesonal-cooling-needs-Pan%C3%A3o-Gon%C3%A7alves/6fb3e202e11f30c48e4eea16d32cd880760d0f8c.
34
RogersJ.KirwanB. (2019). The post-occupancy digital twin: a quantitative report on data standardisation and dynamic building performance evaluation. Capst. Rep. May. 10.21427/a37g-ha11
35
RoisinB.BodartM.DeneyerA.D’HerdtP. (2008). Lighting energy savings in offices using different control systems and their real consumption. Energy Build.40 (4), 514–523. 10.1016/j.enbuild.2007.04.006
36
RuganiR.BigazziM.FantozziF.MarengoM.PiccoM.SalvadoriG. (2021). Impact of building thermal inertia in different climates using energy dynamic simulation through a simplified description model. Build. Simul. Conf. Proc.17. 2578–2585. 10.26868/25222708.2021.30515
37
Schneider (2022). EcoStruxureTM building operation. Available at: https://www.se.com/uk/en/product-range/62111-ecostruxure-building-operation/.
38
SchneiderE. (2024). EcoStruxure power monitoring Expert | schneider electric USA. Available at: https://www.se.com/us/en/product-range/65404-ecostruxure-power-monitoring-expert/.
39
Schneider Electric (2020). SmartX sensors. Available at: https://ecostruxure-building-help.se.com/bms/topics/show.castle?id=11538&locale=en-US&productversion=2.0.
40
Schneider Electric (2024a). EPP302 - EP series differential pressure/air velocity transducer, panel mounting, 0-10 in. WC/0-2500 Pa | schneider electric UK. Available at: https://www.se.com/uk/en/product/EPP302/ep-series-differential-pressure-air-velocity-transducer-panel-mounting-010-in-wc-02500-pa/.
41
Schneider Electric (2024b). LV847288 - micrologic 6.0 X control unit, for masterpact MTZ circuit breakers, fixed, LSIG protections | schneider electric UK. Available at: https://www.se.com/uk/en/product/LV847288/micrologic-6-0-x-control-unit-for-masterpact-mtz-circuit-breakers-fixed-lsig-protections/.
42
Schneider Electric (2024c). STP500-50 - Immersion temp sensor schneider electric UK. Available at: https://www.se.com/uk/en/product/STP500-50/immersion-temp-sensor/.
43
SchweigkoflerA.BraholliO.AkroS.SiegeleD.PennaP.MarcherC.et al (2022). Digital twin as energy management tool through IoT and BIM data integration. 10.34641/clima.2022.46
44
ShahzadM.ShafiqM. T.DouglasD.KassemM. (2022). Digital twins in built environments: an investigation of the characteristics, applications, and challenges buildings. Multidiscip. Digit. Publ. Inst., 12. 120. 10.3390/buildings12020120
45
Siemens (2022). EPC-Tool. Available at: https://epc.bt.siemens.com/EPC/.
46
SolgiE.HamedaniZ.FernandoR.SkatesH.OrjiN. E. (2018). A literature review of night ventilation strategies in buildings. Energy Build.173 (August), 337–352. 10.1016/j.enbuild.2018.05.052
47
UCL (2018a). Campus facilities. UCL East. Available at: https://www.ucl.ac.uk/ucl-east/campus-facilities.
48
UCL (2018b). UCL heating, cooling and ventilation policy. Sustain. UCL. Available at: https://www.ucl.ac.uk/sustainable/about-us/governance-and-policies/ucl-heating-cooling-and-ventilation-policy.
49
VakiloroayaV.SamaliB.FakharA.PishghadamK. (2014). A review of different strategies for HVAC energy saving. Energy Convers. Manag.77 (January), 738–754. 10.1016/j.enconman.2013.10.023
50
VujoševićM.Krstić-FurundžićA. (2017). The influence of atrium on energy performance of hotel building. Energy Build.156 (December), 140–150. 10.1016/j.enbuild.2017.09.068
51
WangL.HuangQ.ZhangQ.XuH.YuenR. K. K. (2017). Role of atrium geometry in building energy consumption: the case of a fully air-conditioned enclosed atrium in cold climates, China. Energy Build.151 (September), 228–241. 10.1016/j.enbuild.2017.06.064
52
WrightL.DavidsonS. (2020). ‘How to tell the difference between a model and a digital twin’. Adv. Model. Simul. Eng. Sci.7: (1). 13. 10.1186/S40323-020-00147-4
53
XueY.DongB.ZhangZ.GaoX. (2023). “Deep learning-based model predictive control for energy saving and consumption reduction in HVAC systems,” in 2023 9th international conference on computer and communications (ICCC), 2233–2238. 10.1109/ICCC59590.2023.10507499
54
Yale University (2021). Becton engineering and applied science center (BCT) | office of facilities. Available at: https://facilities.yale.edu/service-schedule/becton-engineering-and-applied-science-center-bct.
55
Yale University (2023). Yale to make historic investment in engineering, lower Hillhouse Avenue. YaleNews. Available at: https://news.yale.edu/2023/02/23/yale-make-historic-investment-engineering-lower-hillhouse-avenue.
56
Yale University (2024). Facilities energy usage explorer. Available at: https://java.facilities.yale.edu/energy/.
57
YinH.MohamedH. (2023). Towards smart electric heaters for homes in-line with EN-ISO 52120 standard. Build. Simul.18. 3050–3058. 10.26868/25222708.2023.1155
58
YunG. Y.KimH.KimJ. T. (2012). Effects of occupancy and lighting use patterns on lighting energy consumption. Energy Build.46 (March), 152–158. 10.1016/j.enbuild.2011.10.034
Summary
Keywords
live data streams, ISO 52120, data-driven control, built environment, building automation and control, smart building, data harvesting, net zero
Citation
Markiewicz W, Wilczynski V, Dorsey J, Wilson D and Elwell C (2025) Assessing the utility of live data streams across existing and planned university buildings. Front. Energy Effic. 3:1539689. doi: 10.3389/fenef.2025.1539689
Received
04 December 2024
Accepted
31 January 2025
Published
24 February 2025
Volume
3 - 2025
Edited by
Tomasz Cholewa, Lublin University of Technology, Poland
Reviewed by
Graziano Salvalai, Polytechnic University of Milan, Italy
Łukasz Amanowicz, Poznań University of Technology, Poland
Damian Muniak, Cracow University of Technology, Poland
Updates
Copyright
© 2025 Markiewicz, Wilczynski, Dorsey, Wilson and Elwell.
This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.
*Correspondence: William Markiewicz, william.markiewicz.21@ucl.ac.uk
ORCID: William Markiewicz, orcid.org/0000-0002-1084-7884; Julie Dorsey, orcid.org/0000-0003-2495-4979; Duncan Wilson, orcid.org/0000-0001-6041-8044; Clifford Elwell, orcid.org/0000-0003-1058-1091
Disclaimer
All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.