ORIGINAL RESEARCH article

Front. Energy Res., 06 January 2023

Sec. Smart Grids

Volume 10 - 2022 | https://doi.org/10.3389/fenrg.2022.1054870

Real-time Volt-Var control of grid forming converters in DER-enriched distribution network

  • 1. Department of Electrical Engineering, Faculty of Science and Technology, UiT The Arctic University of Norway, Narvik, Norway

  • 2. Department of Electric Power Engineering, Faculty of Information Technology and Electrical Engineering, Narvik, Norway

  • 3. Center for Smart Grid, University of Exeter, Exeter, United Kingdom

Abstract

The growing installation of distributed energy resources (DERs) in a distribution network (DN) poses substantial issues related to voltage regulation. Due to constrained switching operation and slower response time, traditional voltage regulation devices cannot handle current voltage-related challenges. One alternative to solve these problems is to use smart converters to control the reactive power to regulate the voltage. Volt-Var control (VVC) is one of the simplest approaches for controlling the reactive power from smart converters. Among several converters, grid forming converters (GFCs) are more suitable in DER-enriched distribution networks. Since DER-enriched distribution networks have a higher fluctuation in voltage profile, real-time control is advantageous. Therefore, this work presents an advanced real-time reactive power control for handling voltage violations in a DN using GFC. The uniqueness of this method is that it controls the voltage magnitude of affected nodes by dispatching reactive power from smart converters in real-time. By running cyber-physical co-simulation (CPCS) between the Typhoon HIL 604 and OpenDSS, the Volt-Var control can be done in real time. The grid-forming converter is modelled in Typhoon HIL 604, which acts as a physical layer of the proposed cyber-physical system for real-time VVC. A CIGRE medium voltage distribution network is designed in OpenDSS and serves as one of the parts of the cyber layer. The CPCS between Typhoon HIL and OpenDSS and the control algorithm are both done by a programme written in Python. The execution of the control algorithm is performed in real time using the Supervisory Control and Data Acquisition (SCADA) developed in this study. The real-time simulation shows that the proposed real-time VVC is capable of handling voltage violations in real time in DER-enriched distribution networks.

1 Introduction

1.1 Motivation and incitement

To meet the target set by the European Energy Roadmap 2050 (), there will be a significant deployment of renewable energy resources (RES) based on distributed energy resources (DER) in the electrical system. By 2050, the proportions of wind and solar energy in the world’s energy mix are expected to increase from 0.33% to 0.82%, respectively, to 11.9% and 11.03% (). Due to the significant intermittency and dependence on the environmental condition of RESs, the continuous growth of the integration of such resources into power systems alters the operating conditions of both electricity transmission and distribution networks. This will have a significant impact on the existing control, management, and operation of the power system (). In fact, the high penetration of variable RES increases the uncertainty of the state of the system, increases the risk of contingencies (), and lowers the overall quality of the service (). Furthermore, the appearance of bidirectional power flows, reverse power flows, and terminal voltage rises () creates additional challenges to the control and management of distribution networks.

In addition, the digitalization of the distribution network is an emerging concern for effective control and management of the distribution network. The growing use of smart devices for real-time control and monitoring is accompanied by an increased implementation of the smart grid paradigm in distribution networks. Furthermore, the operation of the distribution system requires a more robust and adequate monitoring and control infrastructure as a result of the growing integration of converter-based renewable energy sources with cutting-edge ICT (information and communication technology). To address the approaching problems in the digitalization of the distribution network, it is critical to develop a comprehensive and implementable platform to test theoretical ideas, computational tools, methodologies, and new technologies in real time.

1.2 Literature review

Among many technical challenges due to the high integration of DER, voltage violation is a critical issue that must be solved to accommodate the high penetration of DER (). Additionally, the voltage violation problem is more sensitive because of the inherently resistive (high R/X) character of the distribution network. Due to limited capacity and poor operational response, conventional voltage-regulating devices (VRDs), such as load tap changing (OLTC) transformers, step voltage regulators, and switched capacitors/industry banks, could not be viable options in such situations (). They may not handle the voltage issue more accurately when DER power generation and load fluctuations are large. With the advancement in smart converter technology, smart converter reactive power regulation is one of the best methods to deal with voltage problems in distribution networks.

There are various approaches for controlling the reactive power in the scientific literature (; ; ; ; ; ; ; ; ). In most studies, reactive power control is achieved in centralised, distributed, and decentralised forms. The key problem with the centralised technique is the lack of communication and monitoring infrastructure in the distribution network. The distributed method incorporates both the concept of centralised control and the local control method in a coordinated fashion to implement the control action. This method somehow tries to coordinate the operation between the local control and the centralised control in a two-level control structure (). In the distributed control method, the centralised controller operates at a larger time step and the local controller acts at a smaller time step. On the other hand, the decentralised/local method uses local measurement, and, based on that, the optimal settings for the reactive dispatch are estimated. Due to the fast-responding nature of local controllers, local control based on real-time applications is gaining attraction among researchers. Moreover, local control methods require information about threshold settings for voltage and power for the controller to become more effective. These settings for Q(V), Q(P), and P(V) are defined in the . However, users can specify these values on the basis of the type and nature of the network under consideration before implementing the control action.

It is not a new field of study to use smart converters for reactive power control. In the past, much research has been done in the literature to implement Volt-Var control using the smart converter. A droop-based reactive power (Q) absorption approach was studied by (; introduced piece-wise linear droops to regulate the voltage using a smart inverter (). used Droop-based active power curtailment as well as empirical Q(P)rules to reduce reactive power at the same time. The absorption of reactive power and the reduction of active power of photovoltaics were coordinated using the sensitivity V/P and V/Q by . A nodal sensitivity-based approach is implemented in a distribution network to produce the best voltage performance index by . However, this research does not consider real-time validation and proposes solutions as anticipated offline solutions to the problem. Due to the rapid increase in the integration of DER in the distribution network, the future distribution network is subject to significant voltage fluctuations (). Therefore, researchers in the distribution system should consider switching from conventional offline mode to real-time mode. Moreover, with higher integration of DERs, conventional generators alone may not maintain the stability of the system due to lack of spinning reserve. Grid forming converters (GFC) are suitable to provide virtual inertia to maintain the system dynamics (). Hence, this paper proposes a novel implementation of real-time Volt-Var Control (VVC) on GFC on a cyber-physical co-simulation (CPCS) framework developed in this study.

CPCS is one of the effective techniques for solving this complexity (). There is ongoing research on CPCS in a variety of industries, including the automotive, military, building science, and energy. As a consequence, several cosimulation systems are already available, each with a variety of features and degrees of use (). The cyber-physical framework can be implemented to study the effects of cyber attacks and their mitigation techniques (; Zhang et al., 2022a). Furthermore, Cyber-physical systems can also be implemented for long-term risk mitigation studies (; Zhang et al., 2022b), security vulnerability analysis (), optimal cyber defence strategy planning (). Even though cyber-physical co-simulation is expanding, a number of issues remain, particularly as a framework for modelling the distribution network is under development. The importance of co-simulation in achieving the best reactive power regulation is emphasised in (). CPCS frameworks combine digital and cybernetic systems with physical systems to improve the monitoring and management of the physical system (). proposes a real-time cyber-physical test bed for microgrid control, where the power system network is constructed in RSCAD and real-time co-simulation is performed using the real-time digital simulator (RTDS). In a real-time simulation test bed is also suggested that runs between OpalRT and Matlab Simulink. In this paper, the microgrid control algorithm and the impact of cyber incidents on microgrid performance are tested using a test bed. However, the modelling of distribution networks is limited to Matlab user only, which may not be a suitable system to model large distribution networks. The communication network was created using OPNET and the Real-Time Laboratory (RT-LAB) is studied by . offers a detailed analysis of the real-time co-simulation testbed.

Furthermore, the existing literature provides information on microgrids or small distribution networks for CPCS. Most CPCS frameworks in comparable domain listed in the literature () place more emphasis on power system models that are typically balanced in operation. However, the distribution network differs from the power system network in many factors, such as unbalanced operation, network topology, multiple load points, and many more. The distribution network solver taken into consideration in the co-simulation should be able to solve all forms of distribution networks (either single-phase or three-phase, balanced or unbalanced) in order to assess a realistic distribution network. Also, to solve the realistic distribution network, real-time operation for distribution networks must also be reliable and quick. OpenDSS is a highly potent technology developed specifically to address the distribution network problem (). A general framework for co-simulation between OpenDSS and Typhoon HIL is presented in , however, in this paper only a basic implementation without detailed modelling of the controller is presented.

1.3 Contribution and paper organization

To the authors’ best knowledge, the proposed CPCS framework between Typhoon HIL and OpenDSS for real-time Volt-Var control is the first of its kind. The proposed system can be applied to any kind of distribution network, either balanced or unbalanced, single-phase or three-phase. Therefore, the goal of this effort is to provide a CPCS framework that will be used to execute a real-time simulation between Typhoon HIL and OpenDSS together with the implementation of a real-time Volt-Var control on a proposed CPCS framework. In this context, the contributions of this work are as follows.

  • 1) In this study, a cyber-physical co-simulation framework for real-time Volt-Var control in grid forming converters (GFC) is developed. The proposed framework is implemented using real-time co-simulation between the distribution network solver OpenDSS and Typhoon HIL. The GFC controller is designed in the Typhoon HIL real-time simulator and the active and reactive power output obtained from the GFC is fed to the distribution network in OpenDSS during the real-time simulation to obtain the voltage profile of the network.

  • 2) In this study, real-time Volt-Var control is proposed in a distribution network to mitigate the uncertain voltage violations of the network. The voltage regulation due to real-time variation in DER generation and load is achieved by the proposed real-time Volt-Var controller in DER enriched distribution network.

  • 3) Real-time simulation studies are performed to show the efficacy of the proposed real-time Volt-Var controller in handling the real-time disturbances from DERs and loads.

The rest of this article is organised as follows. Section 2 details the Volt-Var control methods used in this work. Section 3 describes the detailed modelling of GFC. Section 4 explains the overall methodology implemented for real-time Volt-Var control. The system under consideration, test data and simulation studies is presented in Section 5. The main conclusions drawn from this article are provided in Section 6.

2 Volt-Var control

The voltage of the distribution network must adhere to standards to ensure proper operation of the network. Under typical operating circumstances, the voltage restrictions are derived from the power quality criteria, which are based on the EN 50160 standard () in Europe. According to the standard, the steady-state voltage limits, under normal operating conditions, excluding voltage interruptions, during each period of 1 week, shall be 95% of the mean RMS values of the supply voltage for 10 min within the range of ±10%. However, some networks can have reduced criteria to ±5%. To maintain the voltage profile () at the point of common coupling, converters can deliver both inductive and capacitive reactive power. The IEEE1547-2018 standard (pho, 2020) specifies the reactive power output requirements for voltage control applications using smart converters. According to IEEE1547-2018, DER units can provide inductive or capacitive reactive power up to 44% of the total rated capacity.

The reactive power required for the smart converter is given by Eq. 1. In Eq. 1, Q1, Q4, v1, v2, v3, v4, are considered fixed quantities in this study and are capacitive 0.44 pu, inductive 0.44, 0.92, 0.98, 1.02, and 1.08 pu, as shown in Figure 1. Q2 and Q3 are considered 0 pu during the normal voltage operation period, which is from 0.98 to 1.02 pu, as the controller does not intervene during those periods. For this analysis, it is assumed that all DERs in the network have the same Volt-Var settings.

FIGURE 1

In order to realise the reactive power control in smart converters, the fundamental concept of the power capability curve of the power converter needs to be precise. Figure 2 shows the capability curve and the relationship of converter size with the reactive power.

FIGURE 2

).

In algorithm 1, the overall process of Volt-Var control (VVC) mode in a converter is represented. For all converters in the network, Volt-Var is implemented at the same time. To bring the system under similar consideration, the Volt-Var settings for all converters are considered the same. In algorithm 1, n is the total number of buses. m is the total number of buses with DER integration. k is the total number of load buses. The active and reactive power consumption of the load on the bus k at a particular moment in the simulation time t is represented by and . Similarly, and represent the active and reactive power of DER on the bus m at the simulation instant t. The values of the active power and reactive power of the loads and the active power generation of the DERs are taken from the measurement data. This initialisation process is performed using the Typhoon HIL signal processing toolchain and is programmed in Python. After retrieving the required signals, the loads and active power generation of DERs are changed in the distribution system model in OpenDSS by co-simulation between the Typhoon HIL and OpenDSS. With the assigned values, the power flow in the distribution network is calculated using co-simulation. After successful completion of the power flow, the required information (voltage of the bus) is extracted. From the information available from the extracted data, Volt-Var is implemented on each DER in the network. The implication of Volt-Var control is that it provides the required reactive power for the DER to mitigate voltage violations. The VVC is implemented in all converters to obtain the reactive power reference. The reactive power reference is then sent to the controller in the real-time simulator. The process is repeated until the user manually stops the simulation. The general methodology that describes the real-time Volt-Var control and the detailed process of exchanging the required information is explained in Section 4.

Algorithm 1

  • Require:t ≥ 0, n ≥ 0, m ≥ 0, k ≥ 0, ,

  • Ensure:t = 0, m = 0, Vn(0) ≥ 0, ,

  • 1  while True do

  • 2  Initialisation

  • 3  Run power flow with initial values using cyber-physical co-simulation

  • 4  Get the measurement signals for monitoring the voltage profile

  • 5   whilemn−1 do Implement VVC

  • 6   ifVm(t) > v2 and Vm(t) ≤ v3then

  • 7   

  • 8   else ifVm(t) ≤ v1then

  • 9   

  • 10   else ifVm(t) > v1 and Vm(t) ≤ v2then

  • 11   

  • 12   else ifVm(t) > v3 and Vm(t) ≤ v4then

  • 13   

  • 14   else ifVm(t) > v4then

  • 15   

  • 16   end if

  • 17   end while

  • 18  SetPandQreference to the converters in physical system

  • 19  Run power flow using cyber-physical co-simulation

  • 20  Obtain voltage after VVC

  • 21   t = t+1

  • 22  end while

An algorithm for real-time Volt-Var control.

The block diagram representation of the real-time VVC is presented in Figure 3. Typhoon HIL control centre, the Volt-Var control centre, and the Typhoon HIL and OpenDSS co-simulation are the main components for obtaining the real-time Volt-Var control using the propsed method. The Typhoon HIL control centre consists of various Python-based programmes to execute the co-simulation between the OpenDSS and the real-time simulator. The control centre also communicates with the Volt-Var control centre using the Python-based programme. The Volt-Var control centre communicates with OpenDSS to implement Algorithm 1 from the information obtained from the Typhoon HIL control centre and OpenDSS.

FIGURE 3

3 Detailed modelling of grid forming converters

DERs like wind power plants and solar photovoltaics, are not directly connected to the grid (). Generally, converters are used to connect them to the grid. An appropriate control design is an important aspect to connect the DERs efficiently. The control algorithms are anticipated to establish active power and reactive power from the DERs based on the scope of interconnection. The literature has several control measures that have been suggested (). The degree of integration of RESs into the network should also be taken into account when choosing the appropriate control mechanisms. Synchronous generators in the network can manage unstable power dynamics when there are fewer DERS interconnected. However, these generators are not able to manage such system dynamics and maintain system stability in converter-dominated systems, as converter-based DERs lack damping or spinning inertia (). Researchers are becoming more interested in the idea of virtual synchronous machines (VSMs) (Zhong and Weiss, 2010) as a potential solution to this problem. Physically, VSMs are power electronics converters that can provide the grid with virtual inertia and damping (). This work uses the grid-forming synchronverter (Zhong and Weiss, 2010; Zhong, 2016) created as a voltage source for real-time reactive power regulation. The grid forming converter has the ability to maintain angle and voltage at the coupling point. Are therefore thought to be appropriate for DER-enriched distribution networks .

Control of the synchronverter to regulate active and reactive power is governed by a mathematical model of the synchronous generator (Zhong et al., 2015). As the main focus of this paper is to implement the real-time control using the developed CPCS framework, this paper implements the control similar to (Zhong et al., 2015). Assume that the stator windings are placed in slots around the uniform air gap in a synchronous generator and that the stator winding has a self-inductance of L, mutual inductance of M, and resistance Rs characterise the stator winding. The electromagnetic flux (Φ) produced by the stator winding and the current (i) flowing through the winding can be represented by Eq. 2.

The phase shift between the phases differs by . So, the phase shift vector and is represented by Eq. 3. θ is the rotor angle corresponding to phase a.

The phase terminal voltage of the generator is given by the Kirchhoff voltage law and can be represented by Eq. 4where, Ls = L+M and is the back emf. The back emf is given by Eq. 5.

The relative location of the electrical rotor axis and the magnetic field axis in a synchronous generator is fixed under normal operating conditions. However, any disturbance causes the rotor to decelerate or accelerate, reducing or increasing the rotor angle θ. The swing equation () describes a relative motion of the rotor for synchronously rotating air gap. The swing equation is given by Eq. 6.Where J is the moment of inertia of all the rotating parts, D is the damping factor, Tm is the mechanical torque, and Te is the electromagnetic torque. The electromagnetic torque is given by Eq. 7.where ⟨⋅, ⋅⟩ denotes the inner product in . The converter’s active and reactive power is obtained using Eq. 8.

The controller block diagram is placed within the overall methodology block diagram 4. Inside the block diagram, the controller is represented by the mathematical model described above. The controller takes Pref and Qref as input and provides Pe and Qe as electrical outputs. I is the current that flows into the grid from the synchronverter. I is given by Eq. (2). Pref and Qref are obtained from the controlling and monitoring system developed in SCADA of the proposed cyber-physical testbed for real-time Volt-Var control. Pe and Qe are sent back to the converters in the distribution network through the SCADA. A detailed description of the signal flow to and from the controller is described in Section 4.

4 Proposed real-time Volt-Var control

For monitoring and controlling the distribution networks, a number of crucial components are needed to implement the real-time application (). One of the most fundamental needs is a tool to calculate three-phase unbalanced power flow. Other factors include the control system and its implications for supervisory control and data acquisition (SCADA). Remotely controlled equipment infrastructure, improved real-time metering, and communication infrastructure are also essential. Some of the requirements are developed in the cybernetic layer and some of them in the physical layer. The cyber-physical co-simulation (CPCS) framework for real-time Volt-Var control is made up of two layers 1) the cybernetic layer and 2) the physical layer. The cybernetic layer consists of monitoring and controlling components, software to interface with the physical layer, and software to communicate with the distribution system simulator (OpenDSS in this instance). For simplicity, all the software of the cybernetic layer is executed on the host PC. All controllable hardware, both virtual and actual, is part of the physical layer.

The cybernetic layer is the central core of the CPCS framework for real-time Volt-Var control. The host PC contains the cybernetic layer. Additionally, the host PC has the software required to administer and model the real-time digital simulator. The main purpose of the proposed CPCS framework for Volt-Var control is to simulate an entire distribution network and implement real-time Volt-Var control. As a result, the proposed CPCS framework is equipped with measuring and monitoring devices to obtain the necessary parameters, such as voltage magnitudes in the network. To create variation in DER generation and load demand in real-time, different sliders are placed in SCADA. The change in SCADA is represented in the distribution network by a signal processing system designed within the programme. After the co-simulation, the network experiences a change in the operating condition. With a change in the network operating condition, the SCADA monitoring system triggers the Volt-Var controller to obtain the reactive power references for the GFC. The voltage profile resulting after the application of Volt-Var Control can be observed in real-time. A monitoring and control system created in Typhoon HIL SCADA may be used to dynamically adjust the active power production and loads. A graphical user interface (GUI) is the monitoring and control system of a CPCS framework for real-time Volt-Var Control, and it enables real-time visualisation and control of the simulation. The GUI is specifically designed to show the signals produced by the measurement devices linked to the test system during real-time simulation. The GUI also shows the current condition of the bus voltages visually or digitally. This study uses the Typhoon HIL SCADA system to construct the GUI. Using the Python API, the HIL SCADA communicates with both the cybernetic and physical layers. The true simulation happens at the physical layer. The physical layer in this investigation was HIL 604 from Typhoon HIL Inc. The HIL 604 has eight processing cores, two digital I/O channels, and two analogue I/O channels. It also has two Advanced RISC Machine (ARM) cores.

The general process of implementing the real-time Volt-Var control is shown in Figure 4. Firstly, the test distribution system is modelled in OpenDSS. DERs are placed on the distribution network in the OpenDSS model. The OpenDSS modules are executed via Python API. A Python programme is written inside the Typhoon HIL SCADAIL to interface with OpenDSS. In a Typhoon HIL schematic editor, the grid-forming converter is modelled according to the mathematical model as described in Section 3. The communication interface between the SCADA and the Typhoon HIL real-time simulator is developed using signal processing components available in Typhoon HIL and the Python API of Typhoon HIL. The SCADA system continuously monitors the node voltage of the network and, using the information of the voltage, the Volt-Var controller is designed in the cyber layer. The detailed algorithm for the Volt-Var control for all connected GFCs is presented in Section 2. The reference active and reactive power after the application of the Volt-Var controller is then sent to the GFC. The GFC controller is designed in such a way as to track the reference active and reactive power. The electrical power output of the GFC is then fed to the distribution system. The model can interact with the SCADA and the Typhoon HIL real-time simulator using the signal processing blocks developed in the Typhoon HIL SCADA. The SCADA also consists of a Python programme to get the signals from OpenDSS, process the signal, and display them in real-time. SCADA is equipped with different sliders (to change the load and generation) to send the real-time signal to the OpenDSS. The signals exchanged between the cyber and physical layers are Pref, Qref, Pe, Qe, Vgrid. The exchange of information is done with the help of the signal processing block available in the typhoon HIL and a programme written in Python. The real-time simulation is executed at a fixed time step (1.00 s), which is the maximum allowable execution time of Typhoon HIL. After each time step, the process is repeated until the user stops the simulation.

FIGURE 4

5 Real-time simulation studies

This section demonstrates the proposed real-time simulation analysis of the proposed real-time Volt-Var control. The study was performed in the Digital Energy Systems Laboratory (DIgEnSys-Lab). The DIgEnSys-Lab features physical equipment for real-time monitoring and control (for more information, see https://fglongattlab.fglongatt.org). The following subsections go through each component of the simulation research. In this research, Typhoon HIL 604, OpenDSS and Python are used for cyber-physical co-simulation (CPCS) for real-time Volt-Var control.

5.1 Test system

European MV distribution network can be used for DER integration studies (). Therefore, in this study, the European MV distribution network developed by the CIGRE Task Force C6.04 in “Benchmark Systems for Network Integration of Renewable and Distribution Energy Resources” () is considered. The network is symmetric and balanced. The test system is shown in Figure 5. The network can be operated in radial or meshed topology by turning on or off the switches S1, S2, and S3. However, in this analysis, all switches are considered closed. To study the effectiveness of real-time Volt-Var control in GFC in this case and to represent the dominance of GFC, the wind power plant on bus B7 considered in the original study is replaced by a DER source. In this study, PVs are considered as DERs.

FIGURE 5

).

Table 1 shows the PV ratings considered in this study. In this study, the size of the photovoltaics and the load are modified according to the hosting capacity and the calculation of the spare load capacity performed for the same distribution network. For simplicity, constant impedance loads are considered in this analysis. The main aim of this study is to incorporate the proposed cyber-physical co-simulation framework for control application, even though constant power loads have destabilising effects on volt-volt control methods, the effect is not considered in this study. Tables 2, 3 are the values of residential and commercial loads considered in this study. Network information is taken as in the original CIGRE test network.

TABLE 1

NodeType of DERPmax (kW)
B3PV690
B4PV690
B5PV680
B6PV680
B7PV740
B8PV740
B9PV740
B10PV740
B11PV740

MV distribution network benchmark application: parameters of PV units ().

TABLE 2

NodeSmax (kVA)powerfactor
B1740.98
B32640.97
B48120.97
B58950.97
B65320.97
B87600.97
B106530.97
B113150.97
B12141730.98
B141990.97

MV distribution network benchmark application: Parameters of residential load.

TABLE 3

NodeSmax (kVA)powerfactor
B120.700.95
B31.300.85
B70.400.85
B93.300.85
B100.400.85
B1225.200.95
B130.200.85
B141.900.85

MV distribution network benchmark application: Parameters of commercial load.

The controller parameters considered in this study are given in Table 4.

TABLE 4

ParameterValueUnits
Moment of inertia (J)0.1kg/m2
Mechanical friction (D)1Nms
Reactive power droop (Kv)0.0001
Grid frequency (ω)314rad/sec
Filter resistance (R)0.1Ω
Filter inductance (L)10.1859mH
Filter capacitance (C)24μF
Mfif of synchronous generator0.5Vs

Parameters of controller of grid forming converter (Zhong et al., 2015).

5.2 Real-time simulation results and discussion

A case study is considered to check the effectiveness of the proposed real-time Volt-Var Control (VVC) in the distribution network. In this case study, active power generation from PVs and some residential loads is dynamically changed during the real-time simulation of the SCADA panel developed in this study. The power from PV and the load can be changed in real time by changing the value of the slider widget in THIL SCADA, developed for this specific purpose. The real-time simulation is executed at an execution time of 1.00 s. The proposed VVC and all signal processing are completed within the time frame of each iteration.

The change in active power from the PVs and the loads from the SCADA modify the operating condition of the distribution network by CPCS between OpenDSS and Typhoon HIL. The loads and active power of PV are randomly changed during the real-time simulation in this study. These values are stored in a database during a real-time simulation. After each execution time, the corresponding voltage profile of the distribution network is monitored through the monitoring system developed using advanced model-based system engineering tool chains of Typhoon HIL. Inside a Typhoon HIL, a Python-based programme activates the VVC and provides the reactive power references to manage uncertain voltage violations. This reactive power reference is passed to the grid-forming converter modelled inside the real-time simulator. The active and reactive power output of the converter is fed back to PV in the distribution network. This process is repeated until the end of the simulation. To consider the limitations of the Typhoon HIL configuration available in the laboratory, only four smart converters are designed in Typhoon HIL. For the rest of the PV in the network, the active power reference and the reactive power reference are fed directly to the PV in the distribution network. The real implementation of the power converters developed in THIL are PV1, PV3, PV6, and PV9 connected to B3, B5, B9, and B7, respectively. However, the active power reference is changed for all the PVs connected to the network to change the system’s dynamics. Figure 6 shows the active power reference and the active power generated by the converter. Active power references are obtained by randomly changing the sliders in SCADA.

FIGURE 6

Similarly, to make the real-time simulation more realistic, some of the residential loads in the distribution network are dynamically changed. Residential loads in B4, B5, B8, B10, and B12 are only changed in this study, and the rest of the loads are considered constant. However, it is possible to change all loads during a real-time simulation. The change in loads is exchanged with the distribution network model by a similar process as explained for the change in the active power reference of PVs. The load profile of residential loads in B4, B5, B8, B10, and B12 is shown in Figure 7. The load profile is obtained by changing the values randomly in real-time from the SCADA.

FIGURE 7

The distribution network experiences changes in the voltage profile of the network with the change in the active power of the PVs and loads. In Figure 8B, it is observed that there are some instances where voltage violations are observed. This voltage profile is obtained by offline co-simulation with the values stored during real-time simulation to make a comparative analysis.

FIGURE 8

However, during real-time Volt-Var control, as soon as voltage violations are observed in the network, the real-time Volt-Var controller dispatches the required reactive power to mitigate these voltage violations. With this reactive power from the converter, voltage violations are supposed to be mitigated. The voltage profile obtained during the real-time simulation is depicted in Figure 8A. It is observed that there are no voltage violations during the real-time simulation. This analysis shows the effectiveness of the real-time Volt-Var controller to mitigate voltage violations. The real-time Volt-Var controller is able to mitigate voltage violation issues that were observed with the same PV and load profile on the network.

The reference reactive power and the output reactive power from the PV1, PV3, PV6, and PV9 converters are shown in Figure 9. Reactive power references are sent from the real-time Volt-Var controller based on the voltage of the network at that instant. The GFC controller tracks the reactive power reference. This electrical power is fed to the PV in the distribution network. According to the standard, the positive reactive power is considered as a capacitive reactive power support and the negative reactive power as inductive. Voltage violations below the prescribed limit are supported by capacitive reactive power, while voltage violations above the prescribed limit are supported by inductive reactive power. The reactive power reference profile is obtained from the Volt-Var setting as described in Section 2.

FIGURE 9

5.3 Computational analysis

The computational efficiency of the cyber-physical co-simulation framework is highly dependent on the executable model in the physical layer. This also differs according to the application of the cyber-physical system. The authors in () analyse the computational part of the real-time transient behaviour of a single full-bridge inverter with FPGA hardware resources in a cyber-physical system of a modern distribution grid. Only a few component analyses are presented, for example, the number of logical function blocks (33% of available resources), the number of input output blocks (29% of available resources), the number of digital signal processing blocks (4% of available resources), and a computational time of 0.126 μS. The detailed description of the computational analysis also differs from that of the real-time simulator considered for the developed CPCS. Table 5 shows the detailed computational analysis of the proposed CPCS.

TABLE 5

Name of componentNumber of componentsPercentage of available resources
Standard processing core utilization1 out of 333%
Signal generator utilization12 out of 12100%
Matrix memory utilization0.5%
Simulation step time1μs
Scaled discretization step1μs
Time slot utilization of core66.25%
Time slot utilization of other functional units42.5%
Signal processing IO variables utilization24 out of 41943040.00057%
Signal processing Probes utilization51 out of 10244.98%
Total utilization of the internal memory54 out of 254 kB21.24%

Computational analysis of proposed CPCS.

6 Discussion and conclusion

In this study, a fundamental framework for real-time Volt-Var control is designed in a DER-enriched distribution network to address voltage violations caused by increased penetration of DERs. This study also shows how effectively the suggested framework for real-time cyber-physical co-simulation (CPCS) can handle voltage violations in DER-enriched distribution networks. The suggested method is more adaptable for implementation on any sort of distribution network since the distribution network was modelled on an open source distribution network solver called OpenDSS. The controller for the grid-forming converter modelled in Typhoon HIL tracks the active power reference from the SCADA and the reactive power reference from the Volt Var controller. Reactive power references are computed in real-time by the Volt Var controller to mitigate voltage violations. In the Typhoon HIL, an SCADA is created to perform CPCS and real-time Volt Var control. Taking into account the alteration in the generation profiles of DERs and the consumption profiles of loads, a scenario of voltage violations was developed. The effectiveness of the real-time VVC suggested to mitigate voltage violations is shown by real-time simulations. This study broadens the multidimensional horizon for real-time simulation studies on a CPCS between Typhoon HIL and OpenDSS. The framework developed in this study can be implemented on any type of distribution network, whether single-phase or multi-phase, balanced or unbalanced.

The model-based system engineering tool chains of Typhoon HIL are used in this work to process signals and exchange information between the cyber and physical layers. However, the application of C37.118 or IEC61850 communication protocol is left for future work.

Statements

Data availability statement

The original contributions presented in the study are included in the article/Supplementary Material, further inquiries can be directed to the corresponding author.

Author contributions

RW, PS, and FG-L contributed to the conception and design of the study. RW and FG-L developed the methodology and software validation. RW performed the simulation studies. RW wrote the first draft of the manuscript. PS, CS, MA, and FG-L review the manuscript. All authors contributed to the revision of the manuscript, read and approved the submitted version.

Acknowledgments

The authors are very grateful to the Arctic Centre for Sustainable Energy (ARC) (project number 740108), The Arctic University of Norway, Norway, for providing an opportunity for Raju to visit and work at DIgEnSys-Lab. The authors thank UiT The Arctic University of Norway for covering the publishing cost. The authors also acknowledge the technical support provided by the Typhoon HIL and OpenDSS teams.

Conflict of interest

The authors declare that the research was conducted in the absence of any commercial or financial relationship that could be construed as a potential conflict of interest.

Publisher’s note

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.

Abbreviations

  • DER

    Distributed energy resources

  • RES

    Renewable Energy Sources

  • DN

    Distribution Networks

  • GFC

    Grid Forming Converters

  • DSO

    Distribution System Operators

  • PV

    Photovoltaics

  • VRD

    Voltage regulating devices

  • OLTC

    On-load Tap Changing

  • VVC

    Volt-Var Control

  • LV

    Low voltage

  • CPCS

    Cyber-physical co-simulation

  • J

    Moment of inertia

  • D

    Mechanical friction

  • kv

    Reactive power droop

  • ω

    Grid frequency in rad/sec

  • Vk(t)

    Voltage phasor of bus k at time t

  • Active power generation of DER at bus m at time t

  • Reactive power generation of DER at bus m at time t

  • Active load demand of bus k at time t

  • Reactive load demand of bus k at time t

  • n

    Notation for bus

  • k

    Notation for load bus

  • m

    Notation for bus with DER integration

  • t

    Simulation time instant

Nomenclature

  • DER

    Distributed energy resources

  • RES

    Renewable Energy Sources

  • DN

    Distribution Networks

  • GFC

    Grid Forming Converters

  • DSO

    Distribution System Operators

  • PV

    Photovoltaics

  • VRD

    Voltage regulating devices

  • OLTC

    On-load Tap Changing

  • VVC

    Volt-Var Control

  • LV

    Low voltage

  • CPCS

    Cyber-physical co-simulation

  • J

    Moment of inertia

  • D

    Mechanical friction

  • kv

    Reactive power droop

  • ω

    Grid frequency in rad/sec

  • Vk(t)

    Voltage phasor of bus k at time t

  • Active power generation of DER at bus m at time t

  • Reactive power generation of DER at bus m at time t

  • Active load demand of bus k at time t

  • Reactive load demand of bus k at time t

  • n

    Notation for bus

  • k

    Notation for load bus

  • m

    Notation for bus with DER integration

  • t

    Simulation time instant

References

  • 1

    AcostaM. N.Gonzalez-LongattF.AndradeM. A.Rueda TorresJ. (2021). “Optimal reactive power control of smart inverters: Vestfold and telemark regional network,” in Proceeding of the 2021 IEEE Madrid PowerTech, Madrid, Spain, July 2021 (IEEE), 16. 10.1109/PowerTech46648.2021.9494911

  • 2

    Amendment to IEEE Std 1547-2018 (2020). “IEEE standard for interconnection and interoperability of distributed energy resources with associated Electric Power Systems Interfaces--Amendment 1: To Provide More Flexibility for Adoption of Abnormal Operating Performance Category III,” in IEEE Std 1547a-2020 (Amendment to IEEE Std 1547-2018), April 15, 2020 (IEEE), 116. 10.1109/IEEESTD.2020.9069495

  • 3

    AnastasiadisA. G.KondylisG. P.VokasG. A. (2019). Effect of augmented distributed generation in distribution networks. Energy Rep.6, 177187. 10.1016/j.egyr.2019.10.036

  • 4

    AnsariS.ChandelA.TariqM. (2021). A comprehensive review on power converters control and control strategies of ac/dc microgrid. IEEE Access9, 1799818015. 10.1109/ACCESS.2020.3020035

  • 5

    AwalM. A.YuH.LukicS.HusainI. (2020). Droop and oscillator based grid-forming converter controls: A comparative performance analysis. Front. Energy Res.8, 168. 10.3389/fenrg.2020.00168

  • 6

    Azuara-GrandeL. S.Gonzalez-LongattF.TricaricoG.WagleR.ArnaltesS.GranizoR. (2022). “Real-time implementation of two grid-forming power converter controls to emulate synchronous generators,” in Proceeding of the 2022 IEEE Biennial Congress of Argentina (ARGENCON), San Juan, Argentina, September 2022 (IEEE), 16. 10.1109/ARGENCON55245.2022.9940076

  • 7

    BarsaliS.,et al. (2014). Benchmark systems for network integration of renewable and distributed energy resources. International Council on Large Electric Systems Paris France.

  • 8

    BollenM. H.DasR.DjokicS.CiufoP.MeyerJ.RönnbergS. K.et al (2017). Power quality concerns in implementing smart distribution-grid applications. IEEE Trans. Smart Grid8, 391399. 10.1109/TSG.2016.2596788

  • 9

    BorlaseS. (2017). Smart grids: Infrastructure, technology, and solutions. CRC Press.

  • 10

    CaoG.GuW.GuC.ShengW.PanJ.andLijing SunR. L.et al (2019). Real-time cyber-physical system co-simulation testbed for microgrids control. IET Cyber-Physical Syst. Theory & Appl.4 (7), 3845. 10.1049/iet-cps.2018.5040

  • 11

    CeylanO.PaudyalS.PisicaI. (2021). Nodal sensitivity-based smart inverter control for voltage regulation in distribution feeder. IEEE J. Photovoltaics11, 11051113. 10.1109/jphotov.2021.3070416

  • 12

    ChenS.LiuP.LiZ. (2020). Low carbon transition pathway of power sector with high penetration of renewable energy. Renew. Sustain. Energy Rev.130, 109985. 10.1016/j.rser.2020.109985

  • 13

    CintugluM. H.MohammedO. A.AkkayaK.UluagacA. S. (2016). A survey on smart grid cyber-physical system testbeds. IEEE Commun. Surv. Tutorials19, 446464. 10.1109/comst.2016.2627399

  • 14

    DaiQ.ShiL. (2020). “A game-theoretic analysis of cyber attack-mitigation in centralized feeder automation system,” in Proceeding of the 2020 IEEE Power & Energy Society General Meeting (PESGM), Montreal, QC, Canada, August 2020 (IEEE), 15. 10.1109/PESGM41954.2020.9281583

  • 15

    DaiQ.ShiL.NiY. (2019). Risk assessment for cyberattack in active distribution systems considering the role of feeder automation. IEEE Trans. Power Syst.34, 32303240. 10.1109/TPWRS.2019.2899983

  • 16

    DNV GL (2020). Energy Transition Outlook 2020 - a global and regional forecast to 2050. Dnv Gl Energy Transition Outlook, 306.

  • 17

    GaoB.ShiL. (2020). Modeling an attack-mitigation dynamic game-theoretic scheme for security vulnerability analysis in a cyber-physical power system. IEEE Access8, 3032230331. 10.1109/ACCESS.2020.2973030

  • 18

    GaoD. W.MuljadiE.TianT.MillerM. (2017). Software comparison for renewable energy deployment in a distribution network. Tech. rep., Golden, CO (United States): National Renewable Energy Lab.

  • 19

    GhoshS.RahmanS.PipattanasompornM. (2016). Distribution voltage regulation through active power curtailment with pv inverters and solar generation forecasts. IEEE Trans. Sustain. Energy8, 1322. 10.1109/tste.2016.2577559

  • 20

    GraingerJ. J.StevensonW. D. (1994). Power systems: Analysis and design. McGraw-Hill.

  • 21

    GuoS.ShiL. (2020). “Robust optimal dispatch of power grid considering wind/pv power uncertainties,” in Proceeding of the 2020 IEEE 4th Conference on Energy Internet and Energy System Integration (EI2), Wuhan, China, October 2020 (IEEE), 14011406. 10.1109/EI250167.2020.9346740

  • 22

    HouJ.LeiS.YinW.PengC.HouY. (2020). “Optimal cyber defense strategy of high-voltage dc systems for frequency deviation mitigation,” in Proceeding of the 2020 IEEE International Conference on Communications, Control, and Computing Technologies for Smart Grids (SmartGridComm), Tempe, AZ, USA, November 2020 (IEEE), 15. 10.1109/SmartGridComm47815.2020.9302983

  • 23

    HuP.JiangK.JiX.TanD.LiuD.CaoK.et al (2022). A novel grid-forming strategy for voltage-source controlled PV under nearly 100% renewable electricity. Front. Energy Res.10. 10.3389/fenrg.2022.915763

  • 24

    KabiriR.HolmesD.McGrathB. (2014). “The influence of pv inverter reactive power injection on grid voltage regulation,” in Proceeding of the 2014 IEEE 5th International Symposium on Power Electronics for Distributed Generation Systems (PEDG), Galway, Ireland, June 2014 (IEEE), 18.

  • 25

    KimW.SongS.JangG. (2020). Droop control strategy of utility-scale photovoltaic systems using adaptive dead band. Appl. Sci.10, 8032. 10.3390/app10228032

  • 26

    KuT.LinC.ChenC.HsuC.HsiehW.HsiehS. (2015). “Coordination control of pv inverters for load transfer operation of distribution feeders with high penetration of pv installation,” in Proceeding of the 2015 IEEE/IAS 51st Industrial & Commercial Power Systems Technical Conference (I&CPS), Calgary, AB, Canada, May 2015 (IEEE), 18.

  • 27

    LangsdorfS. (2011). Eu energy policy: From the ecsc to the energy roadmap 2050. Brussels, Belgium: Green European Foundation.

  • 28

    LiP.JiJ.JiH.JianJ.DingF.WuJ.et al (2020). Mpc-based local voltage control strategy of dgs in active distribution networks. IEEE Trans. Sustain. Energy11, 29112921. 10.1109/tste.2020.2981486

  • 29

    LiuM. B.CanizaresC. A.HuangW. (2009). Reactive power and voltage control in distribution systems with limited switching operations. IEEE Trans. Power Syst.24, 889899. 10.1109/TPWRS.2009.2016362

  • 30

    LiuW.ChenS.HouY.YangZ. (2022). Trilevel mixed integer optimization for day-ahead spinning reserve management of electric vehicle aggregator with uncertainty. IEEE Trans. Smart Grid13, 613625. 10.1109/TSG.2021.3113720

  • 31

    MahmudN.ZahediA. (2016). Review of control strategies for voltage regulation of the smart distribution network with high penetration of renewable distributed generation. Renew. Sustain. Energy Rev.64, 582595. 10.1016/j.rser.2016.06.030

  • 32

    MihalP.SchvarcbacherM.RossiB.PitnerT. (2022). Smart grids co-simulations: Survey & research directions. Sustain. Comput. Inf. Syst.35, 100726. 10.1016/j.suscom.2022.100726

  • 33

    MokhtariG.GhoshA.NourbakhshG.LedwichG. (2013). Smart robust resources control in lv network to deal with voltage rise issue. IEEE Trans. Sustain. Energy4, 10431050. 10.1109/TSTE.2013.2265100

  • 34

    Molina-GarcíaÁ.MastromauroR. A.García-SánchezT.PuglieseS.LiserreM.StasiS. (2016). Reactive power flow control for pv inverters voltage support in lv distribution networks. IEEE Trans. Smart Grid8, 447456. 10.1109/tsg.2016.2625314

  • 35

    StandardB. (2007). Voltage characteristics of electricity supplied by public distribution networks. BS EN.

  • 36

    SunC.-C.HongJ.LiuC.-C. (2015). “A co-simulation environment for integrated cyber and power systems,” in Proceeding of the 2015 IEEE International Conference on Smart Grid Communications (SmartGridComm), Miami, FL, USA, November 2015 (IEEE), 133138. 10.1109/SmartGridComm.2015.7436289

  • 37

    TangZ.HillD. J.LiuT. (2020). Distributed coordinated reactive power control for voltage regulation in distribution networks. IEEE Trans. Smart Grid12, 312323. 10.1109/tsg.2020.3018633

  • 38

    TzanisN.AndriopoulosN.ProiskosG.BirbasM.BirbasA.HousosE. (2018). “Computationally efficient representation of energy grid-cyber physical system,” in Proceeding of the 2018 IEEE Industrial Cyber-Physical Systems (ICPS), St. Petersburg, Russia, May 2018 (IEEE), 679683. 10.1109/ICPHYS.2018.8390789

  • 39

    van der MeerA.PalenskyP.HeussenK.Morales BondyD.GehrkeO.SteinbrinkiC.et al (2017). “Cyber-physical energy systems modeling, test specification, and co-simulation based testing,” in Proceeding of the 2017 Workshop on Modeling and Simulation of Cyber-Physical Energy Systems (MSCPES), Pittsburgh, PA, USA, April 2017 (IEEE), 19. 10.1109/MSCPES.2017.8064528

  • 40

    Van WesenbeeckM.De HaanS.VarelaP.VisscherK. (2009). “Grid tied converter with virtual kinetic storage,” in Proceeding of the 2009 IEEE Bucharest PowerTech, Bucharest, Romania, June 2009 (IEEE), 17.

  • 41

    VenkataramananV.SrivastavaA.HahnA. (2016). “Real-time co-simulation testbed for microgrid cyber-physical analysis,” in Proceeding of the 2016 Workshop on Modeling and Simulation of Cyber-Physical Energy Systems (MSCPES), Vienna, Austria, April 2016 (IEEE), 16. 10.1109/MSCPES.2016.7480220

  • 42

    WagleR.SharmaP.SharmaC.GjengedalT.PradhanC. (2021). Bio-inspired hybrid bfoa-pso algorithm-based reactive power controller in a standalone wind-diesel power system. Int. Trans. Electr. Energy Syst.31, e12778. 10.1002/2050-7038.12778

  • 43

    WagleR.TricaricoG.SharmaP.SharmaC.ReudaJ. L.Gonzalez-LongattF. (2022). “Cyber-physical Co-simulation testbed for real-time reactive power control in smart distribution network,” in Proceeding of the 2022 IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA), November 2022.

  • 44

    WangL.YanR.SahaT. K. (2019). Voltage regulation challenges with unbalanced pv integration in low voltage distribution systems and the corresponding solution. Appl. Energy256, 113927. 10.1016/j.apenergy.2019.113927

  • 45

    WangZ.QiD.MeiJ.LiZ.WanK.ZhangJ. (2021). Real-time controller hardware-in-the-loop co-simulation testbed for cooperative control strategy for cyber-physical power system. Glob. Energy Interconnect.4, 214224. 10.1016/j.gloei.2021.05.004

  • 46

    WenX.WuT.JiangH.PengJ.WangH. (2022). Mpc-based control strategy of pv grid connected inverter for damping power oscillations. Front. Energy Res.10. 10.3389/fenrg.2022.968910

  • 47

    ZhangZ.OchoaL. F.ValverdeG. (2017). A novel voltage sensitivity approach for the decentralized control of dg plants. IEEE Trans. Power Syst.33, 15661576. 10.1109/tpwrs.2017.2732443

  • 48

    ZhangZ.HuangS.ChenY.LiB.MeiS. (2022a). Cyber-physical coordinated risk mitigation in smart grids based on attack-defense game. IEEE Trans. Power Syst.37, 530542. 10.1109/TPWRS.2021.3091616

  • 49

    ZhangZ.HuangS.ChenY.LiB.MeiS. (2022b). Diversified software deployment for long-term risk mitigation in cyber-physical power systems. IEEE Trans. Power Syst.37, 377387. 10.1109/TPWRS.2021.3086681

  • 50

    ZhongQ.-C.MaZ.MingW.-L.KonstantopoulosG. C. (2015). Grid-friendly wind power systems based on the synchronverter technology. Energy Convers. Manag.89, 719726. 10.1016/j.enconman.2014.10.027

  • 51

    ZhongQ.-C. (2016). Virtual synchronous machines: A unified interface for grid integration. IEEE Power Electron. Mag.3, 1827. 10.1109/mpel.2016.2614906

  • 52

    ZhongQ.-C.WeissG. (2010). Synchronverters: Inverters that mimic synchronous generators. IEEE Trans. industrial Electron.58, 12591267. 10.1109/tie.2010.2048839

Summary

Keywords

cyber-physical co-simulation, distribution network (DN), real-time control (RTC), grid forming converters, Typhoon HIL

Citation

Wagle R, Sharma P, Sharma C, Amin M and Gonzalez-Longatt F (2023) Real-time Volt-Var control of grid forming converters in DER-enriched distribution network. Front. Energy Res. 10:1054870. doi: 10.3389/fenrg.2022.1054870

Received

27 September 2022

Accepted

21 December 2022

Published

06 January 2023

Volume

10 - 2022

Edited by

Yuzhang Lin, University of Massachusetts Lowell, United States

Reviewed by

Srete Nikolovski, Josip Juraj Strossmayer University of Osijek, Croatia

Vijay Babu Pamshetti, Chaitanya Bharathi Institute of Technology, India

Roy Mccann, University of Arkansas, United States

Updates

Copyright

*Correspondence: Pawan Sharma,

This article was submitted to Smart Grids, a section of the journal Frontiers in Energy Research

Disclaimer

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.

Outline

Figures

Cite article

Copy to clipboard


Export citation file


Share article

Article metrics