ORIGINAL RESEARCH article

Front. Energy Res., 21 February 2022

Sec. Smart Grids

Volume 10 - 2022 | https://doi.org/10.3389/fenrg.2022.840967

A Study of Protection Method for Hybrid Multiterminal UHVDC Lines Based on CEEMDAN–Teager Energy Operator

  • CX

    Chao Xing 1,2

  • LW

    Long Wang 2,3

  • GB

    Guihong Bi 3

  • SC

    Shilong Chen 3

  • JG

    Jingye Gao 2,3

  • YC

    Yanbo Che 1*

  • 1. Key Laboratory of Smart Grid of Education Ministry, Tianjin University, Tianjin, China

  • 2. Electric Power Research Institute of Yunnan Power Grid Co., Ltd., Kunming, China

  • 3. College of Electric Power Engineering, Kunming University of Science and Technology, Kunming, China

Abstract

In the research, a protection scheme for hybrid multiterminal UHVDC lines based on the CEEMDAN and Teager energy operator is proposed. The fault direction criterion is proposed according to the polarity difference of the sudden variable of the mode component of the current line on both sides of the T-zone after the fault of the EHV multiterminal hybrid DC system. When the fault is located on the left or right side of the T-zone, CEEMDAN is used to decompose the mode component of the fault transient current and obtain the intrinsic mode function (IMF component) at different local characteristic time scales. Then, the Teager energy operator is used to calculate the instantaneous energy of the current high-frequency IMF1 component. Finally, the faults inside and outside the line are judged by comparing the maximum value of current high-frequency IMF1 instantaneous energy with the setting value. When the fault is located in the T-zone, it is determined as a fault outside the line zone. The protection scheme of hybrid multiterminal UHVDC lines is given. The simulation model of the Kunliulong hybrid multiterminal UHVDC line system is built in a PSCAD/EMTDC simulation platform, and the proposed protection method is verified. A large number of simulation results show that the protection scheme has certain anti-transition resistance ability and high reliability.

Introduction

The hybrid multiterminal UHVDC system integrates the traditional grid commutated converter–based high voltage direct current (LCC-HVDC) and modular multilevel flexible DC transmission system (MMC-HVDC) with the advantages of large transmission capacity, low transmission losses, and low cost; the receiving end can supply weak AC systems and passive systems, and there is no phase change failure, flexible operation, etc. The long-distance, large-capacity transmission has a wide range of application prospects (; ; ).

The development of a hybrid multiterminal UHVDC system faces many technical challenges, and DC line protection is one of the important technical challenges (). At present, traditional DC transmission line main protection generally uses traveling wave protection, under voltage sensing protection, etc. The traveling wave protection has fast action speed but poor transition resistance and anti-interference ability, and it is easy to refuse to move in case of high-resistance ground fault (; ). There is an adaptability problem when applying the traditional DC line protection to the hybrid multiterminal UHVDC line protection. For the line protection of hybrid multiterminal UHVDC systems, domestic and foreign experts have conducted relevant studies. studied the T-zone protection of multiterminal hybrid DC transmission lines and constructed the T-zone protection criterion using the mode mutation of the current line and Hausdorff distance algorithm on both sides of the T-zone; calculated the analysis of traveling wave protection for flexible DC networks, but the analysis method is very computationally intensive; constructed the fault direction criterion based on the difference between the amplitude of the forward and reverse traveling waves at the near ends of the converter station on both sides. However, this method requires accurate detection of the first wave head of the traveling wave, and the transition resistance needs to be improved; used the attenuation of the low-frequency component of the fault transient current in the T-zone to construct a directional criterion for fault area discrimination in parallel-type multiterminal hybrid DC lines and discriminate the fault location, but in the wavelet transform, the decomposition gradient of the signal sampling frequency needs to be set in advance before the analysis so that it cannot fully reflect the information of the signal itself followed by the pre-selection of the wavelet change basis function, so the resulting error directly affects the correct analysis of the signal itself ().

The CEEMDAN algorithm is a complete ensemble empirical mode decomposition with the adaptive noise algorithm, which is widely used in the field of mechanical fault diagnosis, and the algorithm achieves complete decomposition of the signal by adding zero-mean Gaussian white noise to the original signal; and used complete ensemble empirical mode decomposition with adaptive noise (CEEMDAN) to extract the fault characteristic signal of faulty rotating machinery; the decomposition method has better decomposition effect than the traditional method, does not need to select the basis function, and is subject to less interference; domestic experts have combined the CEEMDAN algorithm with other algorithms to apply in the fields of harmonic detection, ultrashort-term load prediction, etc. used the CEEMDAN algorithm and Teager energy operator for harmonic signal detection; combined the CEEMDAN algorithm, alignment entropy, and leakage integral echo state network (LIESN) method for load prediction; used the Teager energy operator to calculate the transient energy magnitude of transient voltage of DC lines to construct the longitudinal protection criterion to improve the reliability and quick action of the protection, () but the method directly uses the value of the outer voltage of the flat-wave reactor, and the protection may be misactivated when there is an error in the measurement.

This study combines two algorithms, the CEEMDAN algorithm and the Teager energy operator, for DC line fault diagnosis. The protection principle is simple and is constructed using the attenuation characteristics of boundary elements to high-frequency quantities of faults. Compared to the time domain–type protection, the method is a frequency domain–type protection, which improves the quick-action and high reliability of the UHV multiterminal hybrid DC line protection. The method uses CEEMDAN to completely decompose the fault transient current signal, accurately extract the high-frequency component of the fault current, calculate the fault high-frequency component amplitude using the simplicity and speed of the Teager energy operator algorithm, and thus determine the fault location.

In this study, we propose a protection scheme based on the CEEMDAN–Teager energy operator for hybrid multi–terminal UHVDC lines. There is an analysis of the attenuation characteristics of fault transient current signals at the rectifier side boundary and the inverter side boundary at the end of the line for ultrahigh voltage multiterminal hybrid DC transmission; the fault direction is discerned according to the polarity of the sudden change in the mode component of the fault current line on both sides of the T-zone; the maximum value of the instantaneous energy of the high-frequency component of the fault transient current is used to construct the in-zone and out-zone criterion to discern the fault inside and outside its zone. Finally, the PSCAD/EMTDC simulation platform is used to build the UHV multiterminal hybrid DC transmission model, and MATLAB is used to write the protection algorithm for verification. The extensive simulation results show that the proposed protection method has good reliability.

Introduction to the Topology of the Hybrid Multiterminal UHVDC System

The topology of the Kunliulong hybrid multiterminal UHVDC system is analyzed, which adopts the traditional type line-commutation converter (LCC) and full half-bridge modular multilevel converter (FHMMC) for the converter station (FHMMC) (; ), where the sending end of the converter station uses the LCC-type converter, the receiving end used the FHMMC-type converter, the system’s transmission lines are overhead lines, its voltage level of the system is ±800 kV, and line 1 length and line 2 length are marked according to the actual and the system’s topology and fault location, respectively, as shown in Figure 1.

FIGURE 1

Analysis of Boundary Frequency Characteristics of the Hybrid Multiterminal UHVDC System

The boundary of the conventional DC transmission system and flexible DC transmission system is symmetrical structure. The boundary of the rectifier side and the boundary of the inverter side at the end of the line of the Kunliulong hybrid multiterminal UHVDC system are asymmetrical, so the frequency characteristics of the boundary of the rectifier side and the frequency characteristics of the boundary of the inverter side at the end of the line need to be analyzed separately.

Frequency Characteristics of the Boundary of the Rectifier Side

The rectifier-side line boundary of the Kunliulong hybrid multiterminal UHVDC system comprises both the DC filter and smoothing reactor, and the rectifier-side line boundary of this system is shown in Figure 2 (; ; ; ).

FIGURE 2

The rectifier-side line transfer function of the Kunliulong hybrid multiterminal UHVDC system is defined as ; from the circuit theory, it can be introduced that is as follows:

The in the formula is the impedance of the DC filter; is the impedance of the smoothing reactor. Smoothing reactor parameters: ; DC filter parameters: ; ; ; ; ; and ; when they are brought into Eq. 1, we can get the amplitude frequency characteristics of transfer function of the rectifier side of the boundary shown in Figure 3.

FIGURE 3

As can be seen from Figure 3, when ; when , ; when and , takes a great value; and when the frequency , . It can be seen that the rectifier side of the boundary has a significant attenuation characteristic on the high-frequency components of the fault transient fault current signal. When a fault occurs on the outside of the rectifier side, the high-frequency component of the fault current signal needs to go through the dual attenuation of the rectifier side of the boundary and line 1 to reach the installation protection A1. Therefore, the high-frequency component of the fault signal detected by protection A1 has small amplitude; when the fault occurs in line 1, the fault current signal high-frequency components only need to go through the attenuation of line 1 to reach the installation protection A1, so protection A1 detects a larger high-frequency component energy of the transient fault current. Therefore, based on the size of the high-frequency component energy of the fault current signal detected by protection A1, we can discriminate faults inside and outside on the left side of the T-zone.

Inverter-Side Boundary Frequency Characteristics at the End of the Line

The Kunliulong UHV multi-end hybrid DC transmission system is equipped with a smoothing reactor at the end of the transmission line, and there is ground capacitance to the ground, so it is proposed to use a section of overhead line ground capacitance and smoothing reactor at the end of the line to form the inverter side boundary at the end of the line, and the boundary components are shown in Figure 4.

FIGURE 4

The transfer function of the inverter side boundary at the end of the line is defined as , which can be introduced by the circuit theory as follows (; ; ; ): is a section of overhead line impedance to the ground, , is a section of the overhead line to ground capacitance, is the impedance of the smoothing reactor , and ; substituting into Eq. 2 yields the amplitude–frequency characteristics of the inverter-side boundary transfer function at the end of the line as shown in Figure 5.

FIGURE 5

From Figure 5, the transitory current transfer function at the inverter side boundary at the end of the line has high resistance to the high-frequency component of the fault transient current; when in the DC and low-frequency band , ; when 400 Hz < f < 1050 Hz, ; and when , . It can be seen that the inverter side of the boundary of the line end on the fault current high-frequency signal has a strong attenuation characteristics. When the fault occurs outside the inverter side area of the line section, the fault current signal high-frequency component after double attenuation of the line end inverter-side boundary and line 2 reaches the installation protection A2, and the high-frequency component energy of the fault current signal detected by protection A2 is less; when the fault occurs in line 2, fault current high-frequency signal only after the attenuation of line 2 can reach the installation protection A2, and the high-frequency component energy of the fault current signal detected by protection A2 is less. Based on the size of the high-frequency component energy of the fault current detected by protection A2, the fault can be discerned inside and outside the right side of the T-zone.

Principle of the CEEMDAN–Teager Energy Operator Algorithm

Basic Principle of the CEEMDAN Algorithm

The CEEMDAN algorithm is improved on the basis of EEMD, which effectively solves the modal mixing phenomenon of EMD and also avoids the problem of unequal number of IMFs after each EMD decomposition in EEMD and CEEMD so that the reconstructed signal is almost identical to the original signal. The algorithm, compared with wavelet decomposition, does not require the selection of basic functions and can achieve complete decomposition of the signal, which is suitable for the processing of nonlinear and nonstationary signals. The specific steps of the algorithm are as follows (

;

;

).

  • (1) is defined as the adaptive coefficient in solving , as the ith addition of zero-mean white noise, and and as the kth modal component obtained by the decomposition of EMD and CEEMDAN algorithms, respectively. The noise component is added to the original signal and then the EMD decomposition is performed, and the first IMF component is decomposed by adding noise for the ith time:

  • (2) The first-order residuals of CEEMDAN are calculated:

  • (3) After adding adaptive white noise to the residual shown in Eq. 3, EMD decomposition is performed to obtain the second-order IMF component :

  • (4) Steps (2) and (3) are repeated to obtain the kth residual signal and (k+1)st order IMF components as shown in Eqs 6, 7.

  • (5) Step (4) is repeated until the end of the residual signal is not available for EMD decomposition.

The CEEMDAN algorithm finally decomposes the k IMF components with a final residual of :

The original signal is as follows:

From Eq. 9, the CEEMDAN algorithm decomposes the original signal into a series of IMF components with instantaneous frequencies ranging from high to low and one residual to achieve complete decomposition of the signal by adding zero-mean white noise.

Teager Energy Operator

The Teager energy operator is a nonlinear difference operator, and compared with the traditional energy operator, instantaneous energy of the Teager energy operator is related to both amplitude and frequency, with obvious local characteristics, which can quickly perform DC line fault analysis.

The Teager energy operator for the nonlinear signal is defined as in the study by ):where and are the first-order derivative function and the second-order derivative function of the signal , respectively.

When the signal is discrete, the Teager energy operator is defined as

The relationship between and is as follows:

where T is the sampling period.

Extraction of High-Frequency Transient Energy of Fault Current Based on the CEEMDAN–Teager Energy Operator

The CEEMDAN algorithm can achieve complete decomposition of the fault current signal, and the IMF components are arranged in the order from highest to lowest frequency band, that is, 2 has the highest frequency band. When the frequency of is greater than the attenuation frequency of the boundary, the occurrence of out-of-zone fault, the component through the double attenuation of the line boundary and the line to reach the protection device installation, and the protection device to detect the fault transient current component of the energy is smaller; on the contrary, the discovery of the in-zone fault, the component only through the line attenuation to reach the protection installation, and the energy of the high-frequency component of the fault transient current detected by the protection device is larger.

Therefore, the DC transmission line protection can be constructed based on the energy magnitude of the high-frequency component of the fault transient current.

The steps to extract the high-frequency transient energy of the fault transient current based on the CEEMDAN-Teager energy operator are as follows:

  • (1) The fault current signal is obtained and decoupled using phase mode transformation, and the fault current line mode component is obtained.

  • (2) The mode components of the fault current line obtained in step (1) are decomposed using CEEMDAN to obtain the kth IMF components.

  • (3) The instantaneous energy of the high-frequency component of the fault transient current is calculated using the Teager energy operator.

  • (4) The rectified value and maximum value of the instantaneous energy of the high-frequency component of the fault transient current are compared to discriminate the fault location. When the maximum value of the transient energy of the high-frequency component of the fault transient current is greater than the value of the rectification, the fault is judged to be within the zone; conversely, the fault is judged to be outside the zone.

Hybrid Multiterminal UHVDC Line Protection Scheme

Protection Triggering Criterion

When the DC line fault occurs, the voltage amplitude of the line on both sides of the T-zone changes (), the amplitude of the transient voltage can be used as the triggering criterion; in order to improve the protection sensitivity, the side of line with large voltage fluctuation on both sides of the T-zone is selected as the triggering criterion; the triggering criterion is as follows:

where , represent line voltage change line 1 and line 2, respectively; a for line mode voltage of normal operation is required in order to prevent frequent false starts of protection; when for three consecutive points is greater than the start value, protection is triggered.

Protection Direction Criterion

When a fault occurs in the DC line, it is necessary to judge the direction of the fault, and the DC current has definite size and direction (; ). For the Kunliulong hybrid multiterminal UHVDC system, under working condition, DC current always flows from Kunbei converter station to Liubei converter station and Longmen converter station, and the specified current reference direction is the bus pointing to the line, as shown in Figure 1.

When the fault occurs on the left side of the T area, the Kunbei-side LCC converter station, the Liubei-side converter station MMC1, and the Longmen-side converter station MMC2 all inject short-circuit current into the short-circuit point; at this time, for protection A1, fault current direction is positive, and protection A1 detects the current increase; for protection A2, the fault current is opposite to the reference direction, so the fault current direction detected by protection A2 is negative, and the current detected by protection A2 becomes smaller; Similarly, when the fault occurs in the right side of the T-zone, protection A1 detects a decrease in current and protection A2 detects an increase in current; when the fault occurs in the T-zone, both protection A1 and protection A2 detect a decrease in current. When the fault occurs in the T-zone, both protection A1 and protection A2 detect a decrease in current.

Analysis of the fault occurred at simulation , , and , respectively, that is, simulation of the fault occurred at the left side of the T-zone, the right side of the T-zone, and within the T-zone; mode component mutation amount of the fault current line detected by protection A1 and protection A2 is shown in Figure 6.

FIGURE 6

As can be seen in Figure 6, when the left side of the T-zone is fault, protection A1 detects the mode component mutation of the fault current line in line 1 and is positive, protection A2 detects the mode component mutation of the fault current line in line 2 and is negative; when the right side of the T-zone is fault, protection A1 detects the mode component mutation of the fault current line in line 1 and is negative, protection A2 detects the mode component mutation of the fault current line in line 2 and is positive; when the T-zone is fault, protection A1 detects the mode component mutation of fault current line in line 1 and is negative, protection A2 detects the mode component mutation amount of fault current line in line 2 and is negative; Therefore, the construction fault direction criterion is as follows:where indicates the integral of the change in the mode component of the current line at the end of line 1 calculated by protection A1 over the time window.

K2 denotes the integral over the time window of the change in the mode component of the current line at the first end of line 2 calculated by protection A2. The calculation formula of k1 and k2 is as follows:

where “x” is taken as 1 or 2, , are mode change amount of the current line at the end of line 1 and the first end of line 2, is the initial moment of the fault, is the sampling interval, and indicates the length of the time data window.

In- and Out-of-Zone Fault Criterion

After achieving fault direction discrimination, it is also necessary to determine whether the fault occurs in the protection range. When the fault is located in the left side of the T-zone, protection A1 is required to determine the location of the fault; if the fault is located in line 1, protection A1 acts. If the fault is located outside the rectifier side area, protection A1 does not act; when discriminating the fault located in the right side of the T-zone, protection A2 is required to determine the location of the fault, when the fault is located in line 2, protection A2 acts; when the fault is located outside the inverter side area at the end of the line, protection A2 does not act; when the fault is located in the T-zone, this type of fault belongs to the line outside the fault area; hence, protection A1 and protection A2 do not act.

In- and Out-of-Zone Fault Criterion for the Left Side of the T-Zone

Section 2.1 analysis results show that the rectifier side boundary has strong attenuation characteristics for the high-frequency component of the fault current. When the fault is located in the left side of the T-zone, the rectifier-side boundary is used to discern the fault location for the attenuation characteristics of the high-frequency component of the fault transient current. When the fault is located in line 1, the high-frequency signal of the fault current only needs to go through the line attenuation, so the high-frequency component transient energy of the fault current signal is larger; when the fault is located outside the rectifier-side zone, the high-frequency signal of the fault current needs to go through the double attenuation of the rectifier-side boundary and line 1, and the high-frequency component transient energy of the fault current signal is smaller. In order to improve the sensitivity of the protection, the maximum value of the high-frequency component transient energy of the fault current signal is extracted to construct the protection criterion, so the construction of the left side of the T-zone inside and outside the zone fault criterion is as follows:where is the maximum value of the instantaneous energy of the high-frequency component of the fault current calculated by protection A1, and is the rectification value of protection A1. In order to reliably distinguish between the left side of the T-zone inside and outside the zone fault, the value should be selected in accordance with the most serious fault situation X. The principle of the rectification is that high-resistance ground fault occurs at the head-end of line 1 to avoid metallic ground fault outside the rectifier side area. Therefore is as follows:where is a reliable coefficient, take 1.5, and is the maximum value of the instantaneous energy of the high-frequency component of the fault current when a metal ground fault occurs on the outside of the rectifier-side smoothing reactor. Through simulation experiments, it is calculated that is . When the fault is located in the left side of the T-zone, using Eq. 16 can accurately discern the fault in the left side of the T-zone; when the fault is located outside the left side of the T-zone, protection A1 does not act; and when the fault is located in the left side of the T-zone, protection A1 acts.

Internal and External Faults in the Right-Hand Area of the T-Zone

Section 2.2 analysis results show that the inverter side boundary at the end of the line also has a strong attenuation effect on the high-frequency signal of the fault current. Similarly, the attenuation characteristics of the high-frequency component of the fault current from the inverter side boundary at the end of the line are used to discriminate between internal and external faults in the right-hand side of the T-zone. Fault judgment inside and outside the right side of the T-zone is as follows:where is the maximum value of the transient energy of the high-frequency component of fault transient current calculated by protection A2, and is the rectification value of the protection A2. In order to reliably distinguish between the right side of the T-zone inside and outside the zone fault, should be selected in accordance with the most serious fault situation. The principle of the rectification is that high-resistance ground fault occurs at the head-end of line 1 to avoid metallic ground fault outside the rectifier side area. Therefore is calculated as follows:where is the reliability factor, taken as 1.5; and is the maximum value of the instantaneous energy of the high-frequency component of the fault when a metal ground fault occurs on the outside of the inverter-side flat-wave reactor. Through simulation experiments, it is calculated that is . When the fault is located in the right side of the T-zone, Eq. 18 can be used to discern the fault in the right side of the T-zone. When the position is located within the right side of the T-zone, protection A2 is operated, and when the fault is located outside the right side of the T-zone, protection A2 is not operated.

Criterion of Fault Pole Selection

When judging the fault within the left side of the T-zone or within the right side of the T-zone, in order to make the protection act accurately on the fault pole and ensure normal operation of the non-fault pole, the fault pole discrimination is required, and the fault pole criterion is defined as follows:

P is the pole selection factor, and the calculation formula is as follows:

where and are the positive and negative current change, respectively; and is the number of current sampling within 4 ms; when the fault initiating element is activated, the sampling starts.

Protection Flow

The protection device starts when the start-up criterion of any of the protection installations on both sides of the T-zone is satisfied. The current data of the 2-ms time window of the line on both sides of the T-zone are taken and decoupled after phase mode transformation and then polarity of the mode component change of the fault current line is calculated, and fault direction discrimination is carried out. When discriminated as the left side of the T-zone fault, protection A1 calculates the maximum value of the instantaneous energy of the high-frequency component of the current line mode at the end of the fault line 1 and judges the fault inside and outside the left side of the T-zone; when discriminated as the right side of the T-zone fault, protection A2 calculates the maximum value of the instantaneous energy of the high-frequency component of the fault current line mode at the first end of the line 2 and discriminates the fault inside and outside the right side of the T-zone; when discerning a fault within the T-zone, A1 and A2 judge the fault to be outside the line zone, where protection A1 and protection A2 are not operating. The current data of fault line 4 ms for fault pole judgment are calculated, the final fault pole protection device action. The protection flow is shown in Figure 7.

FIGURE 7

Simulation Verification

On the PSCAD/EMTDC simulation platform, the Kunliulong hybrid multiterminal UHVDC system model shown in Figure 1 is built. The Kun-North side adopts the traditional grid phase–shifting type converter with constant DC current and minimum trigger angle control; the Liu-North converter station adopts a hybrid full-bridge and half-bridge modular multiterminal flat converter with constant active power and reactive power control. Longmen converter station uses a full-bridge and half-bridge hybrid modular multiterminal flat converter. Control mode uses fixed DC voltage and reactive power control. Line 1 and line 2 are overhead lines, line model using Frequency Dependent (Phase) Model Options model, the length of 908 km and 542 km, respectively. System parameters are shown in Table 1. The main parameters of the system are shown in Table 1.

TABLE 1

Converter stationKunbei converter stationLiubei converter stationLongmen converter station
Rated power8,000 MW3,000 MW5,000 MW
Rated voltage800 kV800 kV800 kV
Rated current5 kA1.875 kA3.125 kA
Flat-wave reactor300 mH150 mH150 mH

Main parameters of the simulation system.

In Figure 1, , are the faults occurring on the outside of the positive and negative Kun-north side of the flat-wave reactor, respectively, which is outside the left zone of the line T-zone; are first end, midpoint, and end fault of positive line 1; are the first end, midpoint, and end failure of negative line 1. Line 1 faults are intrazone faults on the left side of the T-zone; are first end, midpoint, and end failure of positive line 2, are the first end, midpoint, and end fault of negative line 2; line 2 fault is an intrazone fault on the right side of the T-zone; , , respectively, for the positive and negative Longmen side of the flat-wave reactor outside the fault, the fault for the right side of the T-zone outside the fault; , are faults occurring on the outside of the positive and negative Longmen-side flat-wave reactors respectively, which are faults outside the right side of the T-zone; , are faults occurring on the outside of the positive and negative Liubei-side flat-wave reactors, respectively, which are faults within the T-zone.

According to the protection scheme proposed in Principle of the CEEMDAN–Teager Energy Operator Algorithm, the protection algorithm is written in MATLAB, and the simulation data are imported. This study uses the CEEMDAN algorithm to decompose the first IMF component after the fault transient current; it can be achieved when the center frequency is greater than the boundary decay frequency. Considering the CEEMDAN decomposition principle and Shannon’s theorem to engineering practical impact factors, this study involves simulation sampling frequency using 20 kHz, and the data window length is 4 ms (; ; ; ).

The intra-area fault in the left area of the T-zone is taken as an example. If the center point of line 1 is metallic ground, the moment of fault occurrence is 1 s, the fault duration is 0.1 s, and the amount of line voltage change on both sides of the T-zone is shown in Figure 8.

FIGURE 8

It can be seen from Figure 8 that when the midpoint of line 1 metal ground fault and line 1 and line 2 voltage are down to reach the protection of the start value, the protection process is started. According to the protection process to discriminate the fault direction, line 1 and line 2 current line mode change amount is as shown in Figure 9.

FIGURE 9

From Figure 9, it can be seen that when the line 1 of the midpoint of a metallic ground fault protection A1 detecting the mode change amount of the current line at the end of line 1 is positive, protection A2 detecting the mode change amount of the current line at the first end of line 2 is negative. According to Eq. 18, it can be determined that the fault occurred on the left side of the T-zone. According to the protection process, the location can be determined. The mode components of the fault transient current line for CEEMDAN decomposition can be obtained for each order IMF component as shown in Figure 10, and the FFT transform of each order IMF component to find its spectrum, as shown in Figure 11.

FIGURE 10

FIGURE 11

As seen in Figures 10, 11, the mode signal of the fault transient current line is decomposed by CEEMDAN to obtain IMF1∼IMF5, which is FFT-transformed to find the center frequency of IMF1 as 5.3 kHz, and the center frequency is greater than the boundary decay frequency, and the energy spectrum of IMF1 is calculated by using the Teager energy operator, and the energy spectrum of IMF1 is shown in Figure 12.

FIGURE 12

From Figure 12, we can see that the maximum value of the instantaneous amplitude of the IMF1 component is ; this value satisfies the T internal fault criterion of the left side of T-zone and is judged to be an internal fault in the left zone of the T-zone, that is, line 1 is faulty. According to the protection process, we need to determine the pole line of the fault, that is, the fault pole selection; according to Eq. 21, the pole selection factor P is calculated as 3.2431; according to Eq. 20, the fault occurred in the positive pole is determined. In summary, the fault occurred in the positive T-zone left zone, that is, the positive line 1 fault, and protection A1 issued operation instructions.

In order to verify the impact of different fault locations and different transition resistances on the protection, (; ) this study selected , , and where the fault occurred; the transition resistance is in the value range of , and the simulation results are shown in Tables 2, 3.

TABLE 2

Location of the faultTransition resistance value/ΩK1K2Direction of failureT1T2PJudgment results of A1Judgment results of A2
fout1067−52Left side of the T-zone1.647*1031.6624Outside the left side of the positive T-zone
10049−37Left side of the T-zone7.12*1021.6949Outside the left side of the positive T-zone
20037−27Left side of the T-zone3.10*1021.7224Outside the left side of the positive T-zone
30030−21Left side of the T-zone1.95*1021.7481Outside the left side of the positive T-zone
50021−14Left side of the T-zone1.52*1021.799Outside the left side of the positive T-zone
finI10256−187Left side of the T-zone2.42*1051.7315Inside the left side of the positive T-zone
100121−89Left side of the T-zone4.12*1041.6946Inside the left side of the positive T-zone
20078−57Left side of the T-zone1.34*1041.69Inside the left side of the positive T-zone
30058−42Left side of the T-zone5.88*1031.6917Inside the left side of the positive T-zone
50037−26Left side of the T-zone2.27*1031.6923Inside the left side of the positive T-zone
finI20459−236Left side of the T-zone3.15*1053.2431Inside the left side of the positive T-zone
100308−159Left side of the T-zone1.31*1053.2563Inside the left side of the positive T-zone
200232−119Left side of the T-zone6.98*1043.2548Inside the left side of the positive T-zone
300186−95Left side of the T-zone4.45*1043.2468Inside the left side of the positive T-zone
500133−67Left side of the T-zone2.11*1043.2305Inside the left side of the positive T-zone
finI301,591−671Left side of the T-zone9.07*1054.7264Inside the left side of the positive T-zone
100810−316Left side of the T-zone3.84*1054.6185Inside the left side of the positive T-zone
200539−202Left side of the T-zone2.1*1054.651Inside the left side of the positive T-zone
300402−147Left side of the T-zone1.32*1054.6757Inside the left side of the positive T-zone
500266−94Left side of the T-zone6.68*1044.75Inside the left side of the positive T-zone
finII10−7961751Right side of the T-zone9.8*1054.7264Inside the right side of the positive T-zone
100−391885Right side of the T-zone4.06*1054.6185Inside the left side of the positive T-zone
200−256593Right side of the T-zone2.22*1054.6504Inside the left side of the positive T-zone
300−190445Right side of the T-zone1.36*1054.6757Inside the left side of the positive T-zone
500−125297Right side of the T-zone6.97*1044.75Inside the left side of the positive T-zone
finII20−322660Right side of the T-zone8.44*1054.5303Inside the right side of the positive T-zone
100−216447Right side of the T-zone3.64*1054.3115Inside the right side of the positive T-zone
200−162338Right side of the T-zone1.99*1054.1887Inside the right side of the positive T-zone
300−130272Right side of the T-zone1.31*1054.1107Inside the right side of the positive T-zone
500−93195Right side of the T-zone6.39*1044.0138Inside the right side of the positive T-zone
finII30−328569Right side of the T-zone7.98*1056.1925Inside the right side of the positive T-zone
100−198354Right side of the T-zone4.11*1055.7473Inside the right side of the positive T-zone
200−140254Right side of the T-zone2.63*1055.1994Inside the right side of the positive T-zone
300−108198Right side of the T-zone1.84*1054.8146Inside the right side of the positive T-zone
500−74137Right side of the T-zone1.01*1054.3354Inside the right side of the positive T-zone
fout30−270444Right side of the T-zone8.94*1036.3299Outside the right side of the positive T-zone
100−151264Right side of the T-zone7.72*1036.357Outside the right side of the positive T-zone
200−100182Right side of the T-zone7.07*1035.1923Outside the right side of the positive T-zone
300−73138Right side of the T-zone6.27*1034.467Outside the right side of the positive T-zone
500−4793Right side of the T-zone7.64*1033.7292Outside the right side of the positive T-zone
fout20−615−560T-zone4.3946
100−282−244T-zone4.6647
200−177−146T-zone4.6524
300−128−102T-zone4.7011
500−83−63T-zone4.8375

Simulation of the positive fault.

TABLE 3

Location of the faultTransition resistance value/ΩK1K2Direction of faultT1T2PJudgment results of A1Judgment results of A2
fout4067−53Left side of the T-zone2.58*1020.6972Outside the left zone of the negative T-zone
10049−38Left side of the T-zone1.76*1020.7191Outside the left zone of the negative T-zone
20038−28Left side of the T-zone1.67*1020.7415Outside the left zone of the negative T-zone
30030−22Left side of the T-zone1.85*1020.766Outside the left zone of the negative T-zone
50021−15Left side of the T-zone1.46*1020.776Outside the left zone of the negative T-zone
finI40259−190Left side of the T-zone2.48*1050.605Inside the left zone of the negative T-zone
100123−91Left side of the T-zone4.30*1040.6435Inside the left zone of the negative T-zone
20080−59Left side of the T-zone1.25*1040.6706Inside the left zone of the negative T-zone
30059−43Left side of the T-zone6.49*1030.6954Inside the left zone of the negative T-zone
50038−28Left side of the T-zone2.28*1030.7447Inside the left zone of the negative T-zone
finI50455−235Left side of the T-zone2.97*1050.2953Inside the left zone of the negative T-zone
100305−157Left side of the T-zone1.23*1050.2876Inside the left zone of the negative T-zone
200229−118Left side of the T-zone6.73*1040.2818Inside the left zone of the negative T-zone
300183−94Left side of the T-zone4.61*1040.2765Inside the left zone of the negative T-zone
500131−67Left side of the T-zone2.26*1040.2658Inside the left zone of the negative T-zone
finI601,586−673Left side of the T-zone5.63*1050.2116Inside the left zone of the negative T-zone
100810−317Left side of the T-zone1.96*1050.2169Inside the left zone of the negative T-zone
200539−202Left side of the T-zone1.21*1050.2184Inside the left zone of the negative T-zone
300402−147Left side of the T-zone7.29*1040.2255Inside the left zone of the negative T-zone
500266−94Left side of the T-zone3.74*1040.2415Inside the left zone of the negative T-zone
finII40−7981711Right side of the T-zone5.15*1050.2116Inside the right zone of the negative T-zone
100−393886Right side of the T-zone2.29*1050.2169Inside the right zone of the negative T-zone
200−258594Right side of the T-zone1.25*1050.2184Inside the right zone of the negative T-zone
300−191446Right side of the T-zone7.54*1040.2255Inside the right zone of the negative T-zone
500−126298Right side of the T-zone3.99*1040.2415Inside the right zone of the negative T-zone
finII50−323658Right side of the T-zone8.13*1050.2165Inside the right zone of the negative T-zone
100−216445Right side of the T-zone3.28*1050.2192Inside the right zone of the negative T-zone
200−163337Right side of the T-zone1.87*1050.2222Inside the right zone of the negative T-zone
300−131271Right side of the T-zone1.27*1050.2235Inside the right zone of the negative T-zone
500−94195Right side of the T-zone5.93*1040.2233Inside the right zone of the negative T-zone
finII60−326567Right side of the T-zone7.37*1050.1734Inside the right zone of the negative T-zone
100−196353Right side of the T-zone4.24*1050.1832Inside the right zone of the negative T-zone
200−138254Right side of the T-zone2.73*1050.2013Inside the right zone of the negative T-zone
300−106198Right side of the T-zone1.82*1050.2177Inside the right zone of the negative T-zone
500−72137Right side of the T-zone1.09*1050.2438Inside the right zone of the negative T-zone
fout60−270442Right side of the T-zone6.88*1030.1686Outside the right zone of the negative T-zone
100−151263Right side of the T-zone6.08*1030.1622Outside the right zone of the negative T-zone
200−100182Right side of the T-zone5.26*1030.1878Outside the right zone of the negative T-zone
300−74138Right side of the T-zone5.39*1030.2141Outside the right zone of the negative T-zone
500−4892Right side of the T-zone5.39*1030.2518Outside the right zone of the negative T-zone
fout50−617−246Inside of the T-zone0.2255
100−283−216Inside of the T-zone0.2143
200−177−147Inside of the T-zone0.2181
300−129−103Inside of the T-zone0.2273
500−82−63Inside of the T-zone0.2434

Simulation of the negative fault.

From Tables 2, 3, it can be seen that when the fault occurs at , , and , the transition resistance changes in the range of ; protection A1 and protection A2 can correctly determine fault direction and fault location, correctly determine the fault pole line, and have high sensitivity in the occurrence of high-resistance ground fault. The protection method was found to be 100% correct for different fault locations and transition resistances.

Summary

In this study, a protection scheme for hybrid multiterminal UHVDC lines based on the CEEMDAN–Teager energy operator is proposed, which uses the protection principle to discriminate the fault direction by the polarity of the sudden change in the line mode component of the fault current when a fault occurs on both sides of the T-zone, and then according to the rectifier-side boundary or line end inverter-side boundary on the fault transient current high-frequency signal attenuation characteristics, to determine the left side of the T area inside and outside the fault area or the right side of the T area inside and outside the fault area. The protection principle has the following advantages:

  • 1) When the fault occurs, because the normal operation of DC current has a clear direction and size, the current on both sides of the line will be obvious to sudden changes, and one can use the polarity of the current line mode component of the sudden change in the construction of the direction of the criterion.

  • 2) The adaptive nature of CEEMDAN decomposition and accurate identification ability of the Teager energy operator are used to determine the faults inside and outside the left side of the T-zone and the right side of the T-zone, respectively.

  • 3) The method in this study does not require high sampling frequency and has strong resistance to transition resistance, and the time window is 4 ms, which can quickly and accurately determine the faults inside and outside the zone.

Statements

Data availability statement

The original contributions presented in the study are included in the article/Supplementary Material; further inquiries can be directed to the corresponding author.

Author contributions

CX was responsible for providing ideas and methods and providing an experimental platform. YC was responsible for deriving formulas, reviewing, and verifying. LW was responsible for model building, simulation, data analysis, and manuscript writing. GB, SC, and JG wrote sections of the manuscript. All authors participated in the reading and approved the submitted version.

Funding

The research is funded by the National Natural Science Foundation of China (52067009).

Conflict of interest

Author CX is studying for his doctor’s degree in Tianjin University and employed by the Electric Power Research Institute, Southern Power Grid Yunnan Electric Power Co., Ltd. Author YC works at the Key Laboratory of Smart Grid of Education Ministry of Tianjin University.

The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Publisher’s note

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors, and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.

References

  • 1

    BoussaadiaF . (2019), Reliability Analysis of Transmission Lines protection Systems of the SONELGAZ Power System[C]//Algerian Large Electrical Network Conference. 0. 10.1109/CAGRE.2019.8713173

  • 2

    ChenS.ShuH.XieJ.CaiZ.ZhangW. (2013). Frequency Characteristics of UHVDC Transmission Line and its Boundary[J]. Electric Power Automation Equipment33 (11), 134139+153. 10.3969/j.issn.1006-6047.2013.11.024

  • 3

    ChenZ.ZhouZ.WangX. (2019). Research on protection Scheme of Hybrid Multi-Terminal DC Transmission Lines[J]. Power Syst. Tech.43 (07), 26172622. 10.13335/j.1000-3673.pst.2018.2400

  • 4

    ColominasM. A.SchlotthauerG.TorresM. E.FlandrinP. (2013). Noise-Assisted Emd Methods in Action[J]. Adv. Adaptive Data Anal.4 (04). 10.1142/S1793536912500252

  • 5

    GaoS.GaoYue.SongG. (2020). A protection Method Based on Instaneous Engery of Teager Operator for Modular Multilevel Converter Multiterminal Flexible Direct Current Grid[J]. J. Xi’an Jiaotong Univ.54 (09), 4048. 10.7652/xjtuxb202009004

  • 6

    GaoS.ZengZ.SongG. (2021). A Differential protection Scheme for Hybrid Three-Terminal DC System[J]. J. Xi’an Jiaotong Univ.55 (01), 1726. 10.7652/xjtuxb202101003

  • 7

    HeJ.ChenK.LiM.LuoY.LiangC.XuY. (2020). Review of protection and Fault Handling for a Flexible DC Grid. Prot. Control. Mod. Power Syst.5, 15. 10.1186/s41601-020-00157-9

  • 8

    KarimianA.HosseinianS. H. (2020). Online Tracking of Voltage Flicker for Inverter‐based Distributed Generation Using Teager Energy Operator [J]. Int. Trans. Electr. Energ. Syst.30 (4). 10.1002/2050-7038.12292

  • 9

    LeS.WuY.GuoY.VecchioC. D. (2021). Game Theoretic Approach for a Service Function Chain Routing in NFV with Coupled Constraints. IEEE Trans. Circuits Syst.68, 35573561. Published online. 10.1109/TCSII.2021.3070025

  • 10

    LiB.HeJ.FengY.LiY.LiG.QiuH. (2016). Key Techniques for Protection of Multi-Terminal Flexible DC Grid[J]. Automation Electric Power Syst.40 (21), 212. 10.7500/AEPS20160601011

  • 11

    LiH.ZhangK.WangG., Fault Area Discrimination Method for Parallel Multi-Terminal Hybrid HVDC DC Line[J]. Automation Electric Power Syst., 2019, 43(04): 119125.±179+126-128. 10.7500/AEPS20180615004

  • 12

    LiJ.LiQ. (2015). Medium Term Electricity Load Forecasting Based on CEEMDAN-Permutation[J]. Electric Machines and Control19 (008), 7080. 10.15938/j.emc.2015.08.011

  • 13

    LiS.ChenW.YinX.ChenD.TengY. (2019). A Novel Integrated Protection for VSC-HVDC Transmission Line Based on Current Limiting Reactor Power[J]. IEEE Trans. Power Deliv.35 (1), 226233. 10.1109/tpwrd.2019.2945412

  • 14

    LiZ.JiangW.Abu-SiadaA.LiZ.XuY.LiuS. (2021). Research on a Composite Voltage and Current Measurement Device for HVDC Networks. IEEE Trans. Ind. Electron.68 (9), 89308941. 10.1109/tie.2020.3013772

  • 15

    LinX.QiL.FanL. (2020). Blocking Pilot protection Based on Ratio of Superimposed Energy for VSC-MTDC Grid[J]. Automation Electric Power Syst.40 (04), 28+16. 10.16081/j.epae.202004024

  • 16

    LiuY.YangN.DongB.WuL.YanJ.ShenX.et al (2020). Multi-Lateral Participants Decision-Making: A Distribution System Planning Approach with Incomplete Information Game. IEEE Access8, 8893388950. 10.1109/access.2020.2991181

  • 17

    MuniappanM. (2021). A Comprehensive Review of DC Fault protection Methods in HVDC Transmission Systems. Prot. Control. Mod. Power Syst.6 (1), 120. 10.1186/s41601-020-00173-9

  • 18

    RenZ.ChengJ.XingQ. (2017). A Harmonic Detection Method Based on CEEMDAN and Teager Energy Operator Algorithm[J]. Power Syst. Prot. Control. (9), 5662. 10.7667/PSPC160634

  • 19

    ShenX.OuyangT.KhajorntraidetC.LiY.LiS.ZhuangJ. (2021a). Mixture Density Networks-Based Knock Simulator. Ieee/asme Trans. Mechatron., 1. 10.1109/TMECH.2021.3059775

  • 20

    ShenX.OuyangT.YangN.ZhuangJ. (2021b). Sample-based Neural Approximation Approach for Probabilistic Constrained Programs. IEEE Trans. Neural Netw. Learn. Syst., 18. 10.1109/TNNLS.2021.3102323

  • 21

    ShenX.RaksincharoensakP. (2021a). Pedestrian-aware Statistical Risk Assessment. IEEE Trans. Intell. Transport. Syst., 19. 10.1109/TITS.2021.3074522

  • 22

    ShenX.RaksincharoensakP. (2021b). Statistical Models of Near-Accident Event and Pedestrian Behavior at Non-signalized Intersections. J. Appl. Stat., 121. 10.1080/02664763.2021.1962263

  • 23

    ShenX.ZhangX.OuyangT.LiY.RaksincharoensakP. (2020a). Cooperative Comfortable-Driving at Signalized Intersections for Connected and Automated Vehicles. IEEE Robot. Autom. Lett.5 (4), 62476254. 10.1109/LRA.2020.3014010

  • 24

    ShenX.ZhangY.SataK.ShenT. (2020b). Gaussian Mixture Model Clustering-Based Knock Threshold Learning in Automotive Engines. Ieee/asme Trans. Mechatron.25 (6), 29812991. 10.1109/TMECH.2020.3000732

  • 25

    ShenX.ZhangY.ShenT.KhajorntraidetC. (2017). Spark advance Self-Optimization with Knock Probability Threshold for Lean-Burn Operation Mode of SI Engine. Energy122 (3), 110. 10.1016/j.energy.2017.01.065

  • 26

    SongG.HouJ.GuoB.ChenZ.et al (2020). Pilot protection of Hybrid MMC DC Gridbased on Active Detection. J. Prot. Control. Mod. Power Syst.V5 (1), 8296. 10.1186/s41601-020-0152-2

  • 27

    TianP.WuQ.Huangj. (2021). Research on protection Strategy of a Hybrid Multi-Terminal DC System Based on LCC and FHMMC[J]. Power Syst. Prot. Control.49 (01), 170177. 10.19783/j.cnki.pspc.200211

  • 28

    ToyodaM.WuY. (2021). Mayer-type Optimal Control of Probabilistic Boolean Control Network with Uncertain Selection Probabilities. IEEE Trans. Cybern.51, 30793092. 10.1109/tcyb.2019.2954849

  • 29

    VanraJ.DhamiS. S.PablaB. S. (2017). Non-Contact Incipient Fault Diagnosis Method of Fixed-Axis Gearbox Based on CEEMDAN. R. Soc. Open Sci.4 (8), 170616. 10.1098/rsos.170616

  • 30

    WangL.ShaoY. (2020). Fault Feature Extraction of Rotating Machinery Using a Reweighted Complete Ensemble Empirical Mode Decomposition with Adaptive Noise and Demodulation Analysis[J]. Mech. Syst. signal Process.138 (Apr), 10654511106545.20. 10.1016/j.ymssp.2019.106545

  • 31

    WangY.FanX.ZhangB. (2019). The Analytical Analysis and Protection Setting of Traveling Wave Protection in VSC-HVDC Grid[J]. Proc. CSEE39 (11), 32013212. 10.13334/j.0258-8013.pcsee.181633

  • 32

    WuY.GuoY.ToyodaM. (2021). Policy Iteration Approach to the Infinite Horizon Average Optimal Control of Probabilistic Boolean Networks. IEEE Trans. Neural Netw. Learn. Syst.32 (6), 29102924. 10.1109/TNNLS.2020.3008960

  • 33

    YangN.YeD.ZhouZ.CuiJ.ChenD.WangX. (2018). Research on Modelling and Solution of Stochastic SCUC under AC Power Flow Constraints[J]. IET Generation, Transm. Distribution12 (15), 36183625. 10.1049/iet-gtd.2017.1845

  • 34

    YangN.HuangY.HouD.LiuS.YeD.DongB.et al (2019). Adaptive Nonparametric Kernel Density Estimation Approach for Joint Probability Density Function Modeling of Multiple Wind Farms. Energies12, 1356. 10.3390/en12071356

  • 35

    YangN.LiuS.DengY.XingC. (2021b). An Improved Robust SCUC Approach Considering Multiple Uncertainty and Correlation. IEEJ Trans. Elec Electron. Eng.16, 2134. 10.1002/tee.23265

  • 36

    YangN.QinT.WuL.HuangY.HuangY.XingC.et al (2022). A Multi-Agent Game Based Joint Planning Approach for Electricity-Gas Integrated Energy Systems Considering Wind Power Uncertainty. Electric Power Syst. Res.204, 107673. ISSN 0378-7796. 10.1016/j.epsr.2021.107673

  • 37

    YangN.YangC.WuL.ShenX.JiaJ.LiZ.et al (2021c). Intelligent Data-Driven Decision-Making Method for Dynamic Multi-Sequence: An E-Seq2Seq Based SCUC Expert System. IEEE Trans. Ind. Inf., 1. 10.1109/TII.2021.3107406

  • 38

    YangN.YangC.XingC.YeD.JiaJ.ChenD.et al (2021a). Deep Learning‐based SCUC Decision‐making: An Intelligent Data‐driven Approach with Self‐learning Capabilities. IET Gener. Transm. Distrib., 112. 10.1049/gtd2.12315

  • 39

    ZhangLei.XieY.YeJ.XueT.ChengJ.LiZ.et al (2021). Intelligent Frequency Control Strategy Based on Reinforcement Learning of Multi-Objective Collaborative Reward Function[J]. Front. Energ. Res. Early Access. 10.3389/fenrg.2021.760525(SCI)

  • 40

    ZhengX.WangS.LiN.XiaoH.JiangW. (2016). A LCC and MMC Series Hybrid HVDC Topology Suitable for Bulk Power Overhead Line Transmission[J]. Power Syst. Tech.40 (01), 5563. 10.13335/j.1000-3673.pst.2016.01.008

  • 41

    ZhuB.DingF.VilathgamuwaD. M. (2020). Coat Circuits for DC-DC Converters to Improve Voltage Conversion Ratio. IEEE Trans. Power Electron.35 (4), 36793687. 10.1109/TPEL.2019.2934726

Summary

Keywords

hybrid multiterminal UHVDC system, line protection, CEEMDAN, Teager energy operator, PSCAD/EMTDC simulation

Citation

Xing C, Wang L, Bi G, Chen S, Gao J and Che Y (2022) A Study of Protection Method for Hybrid Multiterminal UHVDC Lines Based on CEEMDAN–Teager Energy Operator. Front. Energy Res. 10:840967. doi: 10.3389/fenrg.2022.840967

Received

21 December 2021

Accepted

24 January 2022

Published

21 February 2022

Volume

10 - 2022

Edited by

Xun Shen, Tokyo Institute of Technology, Japan

Reviewed by

Hardeep Singh, Sophia University, Japan

Sandeep Kumar, Lovely Professional University, India

Updates

Copyright

*Correspondence: Yanbo Che,

This article was submitted to Smart Grids, a section of the journal Frontiers in Energy Research

Disclaimer

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.

Outline

Figures

Cite article

Copy to clipboard


Export citation file


Share article

Article metrics